background image

 

 

12 

 

 

MAINTENANCE 

WARNING 

 

Electrical shock hazard. 

 

Turn  OFF  power  and  fuel  to  the  furnace  before  any 
disassembly or servicing. 

 

Failure  to  do  so  can  result  in  death,  bodily  injury  and/or 
property damage.

 

 

Preventive maintenance is the best way to avoid unnecessary 
expense  and  inconvenience.  Have  your  heating  system  and 
burner  inspected  by  a  qualified  service  technician  at  regular 
intervals.  

 

To  maintain  the  reliability  and  optimal  performance  of  the 
furnace,  have  a  complete  combustion  check  done  after  the 
annual maintenance call. Do not attempt to repair the furnace 
or its controls. Call a qualified service technician. 
 

Before calling for repair service check the following 
points: 

1.  Check the oil tank gauge and make sure that the valve is 

open; 

2.  Check fuses and the circuit breaker; 

3.  Check if the main disconnect switch is ON ; 

4.  Set the thermostat above room temperature; 

5.  If  ignition  does  not  occur,  turn  off  the  disconnect  switch 

and call a qualified service technician. 

 
When  ordering  replacement  parts,  please  specify  the 
complete furnace model number and serial number. 

 

4.1  CLEANING

 

THE

 

HEAT

 

EXCHANGER 

It  is  not  generally  necessary  to  clean  the  heat  exchanger  or 
flue  pipe  every  year,  but  it  is  advisable to have the oil burner 
service technician check the unit before each heating season 
to  determine  whether  the  cleaning  or  replacement  of  parts  is 
necessary.  

 

If  a  cleaning  is  necessary,  the  following  steps  should  be 
performed:  
 
1.  Turn OFF all utilities upstream from the furnace; 

2.  Disconnect the flue pipe; 

3.  Remove  the  flue  collar  panel  located  at  the  front  of  the 

furnace; 

4.  Remove the heat exchanger baffles; 

5.  Disconnect the oil line and remove the oil burner; 

6.  Clean  the  secondary  tubes  and  the  primary  cylinder  with 

a stiff brush and a vacuum cleaner; 

7.  Before  re-assembling  the  unit,  the  heat  exchanger  and 

combustion  chamber should be inspected to determine if 
replacement is required; 

8.  After  the  cleaning,  replace  the  heat  exchanger  baffles, 

flue collar plate and oil burner; 

9.  Readjust the burner for proper operation. 

 

4.2  CLEANING

 

THE

 

BLOCKED

 

VENT 

SHUT-OFF

 

DEVICE

 

(BVSO) 

For  continuous  safe  operation,  the  Blocked  Vent  Shut-off 
device (BVSO) must be inspected and maintained annually 
by a qualified service technician. 

1.  Disconnect power to the appliance; 

2.  Remove  the  two  screws  holding  on  the  BVSO 

assembly cover; 

3.  Remove the cover; 

4.  Remove the two screws holding the control box to the 

heat transfer tube assembly. Sliding the control box in 
the  appropriate  direction  will  unlock  it  from  the  heat 
transfer tube assembly; 

5.  Carefully remove any build-up from the thermal switch 

surface; 

 

CAUTION

 

Do not dent or scratch the surface of the thermal switch. If 
the thermal switch is damaged it MUST be replaced. 

 

6.  Clean  and  remove  any  build-up  or  obstruction  inside 

the heat transfer tube; 

7.  Re-mount,  lock  and  fasten  the  control  box  with  the  2 

screws removed in step 4; 

8.  Re-attach  the  assembly  cover  with  the  screws 

removed in step 2; 

9.  Re-establish power to the unit. 

4.3  CLEANING

 

THE

 

BURNER

 

HEAD

 

 

Once annually, remove the retention head and electrodes 
from the drawer assembly and remove all foreign matter, 
if  necessary. Also clean the extremity of the burner tube, 
if necessary. 

4.4  CHANGING

 

THE

 

NOZZLE

 

 

Change  the  nozzle  once  a  year  with  the  one specified in 
table 6. 

 

4.5  CHANGING

 

THE

 

OIL

 

FILTER

 

 

Tank Filter 

The tank filter should be changed as required. Follow the 
manufacturer’s instructions. 

 

Secondary Filter  

The 10 micron, or finer, filter cartridge should be changed 
annually. Follow the manufacturer’s instructions. 

4.6  CHANGING

 

THE

 

AIR

 

FILTER

 

 

Dirty filters have an impact on the efficiency of the 
furnace and increase fuel consumption. 
 
Air filters should be changed at least once a year. Very 
dusty conditions, the presence of animal hair and the like 
will require more frequent changing or cleaning.  
 
 
 
 

Summary of Contents for AMP154SD

Page 1: ...erbrooke Québec Canada J1L 1V8 www dettson ca Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE US C DNS 1225A ...

Page 2: ...s of ventilation air openings in a closet door 4 Figure 2 Upflow Installation 4 Figure 3 Downflow Installation 5 Figure 4 Horizontal Installation 5 Figure 5 Thermostat wiring heating and air conditioning with 4 speed motor 5 Figure 6 Thermostat wiring heating and air conditioning with ECM variable speed motor 6 Figure 7 Thermostat wiring heating and air conditioning heat pump with ECM variable spe...

Page 3: ...nformation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform to local codes or in the absence of same to codes of the country having jurisdiction The information contained in this manual is intended for use by a qualified technician familiar with safety proced...

Page 4: ... designed for outdoor installation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to premature failure of the equipment The minimum clearances from combustible material for each of the positions are specified in Table 4 If the furnace is installed in a basement or on a dirt floor in a c...

Page 5: ...ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for that purpose The appliance must be installed in accordance with the current ANSI NFPA 70 National Electrical Code CSA C22 1 Canadian Electrical Code Part 1 and or local codes The control system depends on the correct polarity of the power supply Connect HOT wi...

Page 6: ...own in table 1 and based on a pump pressure of 100 psi Always select nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking 2 5 2 Air and Turbulator Settings Before starting the burner for the first time adjust the air and turbulator settings to those listed in this manual Once the burner becomes operational final adjustments will be required Refer...

Page 7: ...ove the three pole plug from the BVSO outlet on the furnace 3 The burner must shut off immediately while the blower continues to run to the end of the cool down cycle If the test is not in line with the above call a QUALIFIED SERVICE TECHNICIAN 2 8 COMBUSTION AIR SUPPLY AND VENTILATION WARNING Poisonous carbon monoxide gas hazard Comply with NFPA 31 U S and CSA B139 Canada standards for the instal...

Page 8: ...at only outside air be used for combustion a Commercial buildings b Buildings with indoor pools c Furnaces installed near chemical storage areas The installation must carefully be verified to ensure that the combustion air comes from outside 2 10 1 Air filter A properly sized air filter must be installed on the return air side of the unit Refer to the Technical Specifications table 6 for the corre...

Page 9: ...fier on the HUM terminal It supplies 120 VAC electric power when the burner is in operation A 24 VAC signal can also be supplied from the W and C terminals on the blower electronic board to activate a switching relay Also refer to the instructions supplied with the accessory 2 13 2 Electronic Air Cleaner EAC The EAC terminal on the electronic board supplies 120 VAC when the blower is operating in ...

Page 10: ...he oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 Pressure adjustment The oil pressure must be adjusted according to the Technical Specifications of this manual An adjustment screw and a connection for a pressure gauge are located on the oil pump for that purpose Also refer to the burner instruction manual 3 3 3 Combustion Check IMPORTANT The...

Page 11: ...iant heat from the heat exchanger 0 3 m 12 from the plenum of the main take off is usually sufficient 4 The temperature rise is calculated by subtracting the return air temperature from the supply air temperature 5 If the temperature rise is lower or exceeds the temperature specified in Table 6 change to the next lower or higher blower speed tap until the temperature rise falls to the target If th...

Page 12: ...t exchanger and combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9 Readjust the burner for proper operation 4 2 CLEANING THE BLOCKED VENT SHUT OFF DEVICE BVSO For continuous safe operation the Blocked Vent Shut off device BVSO must be inspected and maintained annually by a qualifi...

Page 13: ...rvice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient temperature F Chimney draft W C Overfire draft W C Test performed by ...

Page 14: ...A 0 90 70A Minimum and Maximum pump pressure PSIG 145 150 145 150 Combustion air adjustment turbulator damper 1 0 3 75 3 0 4 25 1 0 3 75 3 0 4 25 AFUE From CSA B212 standard and Canadian regulation 86 4 85 7 86 4 85 7 AFUE From ASHRAE 103 standard and US regulation 86 1 85 0 86 1 85 0 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse size Amps Control transformer ...

Page 15: ...n Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 68 13 45 sec 19 60 sec 38 3 min B 1 ON 2 OFF 0 80 13 45 sec 19 30 sec 38 3 min C 1 OFF 2 ON All 13 45 sec 100 0 sec 100 2 min D 1 ON 2 ON All 13 90 sec 100 0 sec 100 2 min No adjustment required A C size PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time All NO DELAY NO DELAY 100 90 sec OIL HEATIN...

Page 16: ...F FURNACE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 BOTTOM FURNACE 2 Ø 2 54 cm 1 3 5 08 cm 2 4 BACK FURNACE OPPOSITE SIDE OF THE BURNER 1 7 62 cm 3 7 62 cm 3 7 62 cm 3 PLENUM OR HORIZONTAL WARM AIR DUCT WITHIN 6 ft OF FURNACE 2 5 08 cm 2 7 62 cm 3 5 08 cm 2 FURNACE 2 N A 5 08 cm 2 N A FLUE PIPE AROUND FLUE PIPE 22 86 cm 9 22 86 cm 9 22 86 cm 9 FRONT FURNACE BURNER SIDE 1 45 72 cm 18 45 72 cm 18 45 72 cm 18 ...

Page 17: ...17 Figure 9 Furnace Dimensions ...

Page 18: ...18 Figure 10 Wiring diagram 4 speed motor PSC ...

Page 19: ...19 Figure 11 Wiring diagram variable speed motor ECM ...

Page 20: ...20 Figure 12 Parts list with 4 speed motor PSC B500111A ...

Page 21: ...640 WIRE CHANNEL INT 30 B03829 BLOWER DIVIDER 31 B03838 BLOWER SLIDE One blower slide included 32 B03835 02 LATERAL BAFFLE 33 B03867 01 FILTER RACK KIT 34 B03828 FLOOR 35 B03855 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 36 B03857 REAR PANEL ASSEMBLY Panel insulation and baffles included 37 B03864 REAR PANEL INSULATION 38 B03836 REAR BAFFLE 39 B01682 SUPPORT ELECTRONICS BOX 4...

Page 22: ...22 Figure 13 Parts list with variable speed motor ECM B50112A ...

Page 23: ...CHANNEL INT 29 B03829 BLOWER DIVIDER 30 B03838 BLOWER SLIDE One blower slide included 31 B03835 02 LATERAL BAFFLE 32 B03867 01 FILTER RACK KIT 33 B03828 FLOOR 34 B03855 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 35 B03857 REAR PANEL ASSEMBLY Panel insulation and baffles included 36 B03864 REAR PANEL INSULATION 37 B03836 REAR BAFFLE 38 B01682 SUPPORT ELECTRONICS BOX 39 L01F009...

Reviews: