Table 4: Technical specifications(240V 3 phases)
RATING AND
SUPxx-A2403D12
SUPxx-A2403D20
PERFORMANCE
Motor 1/3 HP / 240V Motor 1 HP / 240V
Capacity
24
30
Power, total @
240V
/ 208V (Kw)
24
/ 18
30
/ 22.5
Power, first stage @
240V
/ 208V (Kw)
15
/ 9
15
/ 11.3
Net capacity @
240V
(BTU/h) / 208V
81,891
/ 61,509
102,360
/ 76,884
Temperature rise range @ 240V (°F)
1
60-80
60-80
ELECTRICAL SYSTEM
Volts - Hertz - Phase
3 wires 240/208 - 60 - 3
Electrical element #1 @
240V
/ 208V (Kw)
4
/ 3.1
5
/ 3.7
Electrical element #2 @
240V
/ 208V (Kw)
4
/ 3.1
5
/ 3.7
Electrical element #3 @
240V
/ 208V (Kw)
4
/ 3.1
5
/ 3.7
Electrical element #4 @
240V
/ 208V (Kw)
4
/ 3.1
5
/ 3.7
Electrical element #5 @
240V
/ 208V (Kw)
4
/ 3.1
5
/ 3.7
Electrical element #6 @
240V
/ 208V (Kw)
4
/ 3.1
5
/ 3.7
Blower motor Consumption @
240V
/ 208V (Amp. Max.)
2.6
/ 2.3
5.9
/ 5.1
Heating Elements Consumption @
240V
/ 208V (Amp)
57.8
/ 50.1
72.2
/ 62.6
Total Consumption @
240V
/ 208V (Amp)
60.4
/ 52.3
78.1
/ 67.7
Ampacity @
240V
/ 208V (Amp)
76
/ 66
93
/ 81
Suggested breaker size @
240V
/ 208V (Amp)
2
80
/ 70
100
/ 90
BLOWER DATA
3
Blower speed at 1
st
stage
LOW
LOW
Blower speed at 0.50” W.C. stat.
MED-HIGH
MED-LOW
Blower speed at 0.20” W.C. stat.
MED-HIGH
MED-LOW
Motor (HP) / number of speeds
1/3 HP / 3 speeds
1 HP / 4 speeds
Nominal blower size (diam. X width)
12 x 8
12 x 9
GENERAL INFORMATION
Overall dim. (width x depth x height)
22" x 22" x 36.5"
Supply
20” x 20”
Return
18” x 18”
Filter quantity and size
(1) 20" x 20"
Shipping weight
48 Kg / 105 lbs
Maximum cooling capacity
3 tons
5 tons
1) Select a blower speed that will generate the specified temperature rise.
2) Calculated on the basis of standard C22.2-236.
3) Factory adjusted for a static pressure of 0.5" W.C.
12
Summary of Contents for ADVANTAGE SUPXX-A120D12
Page 16: ...Figure 13 lectrical diagram Supreme Comfort PSC 15...
Page 17: ...Figure 14 lectrical diagram Supreme Advantage PSC 16...
Page 23: ...7 NOTES 22...
Page 24: ...23...