QTD2
Series
38
5.0
Maintenance
•
Troubleshooting Guide
Troubleshooting ends.
Do the burners stay on for approx.
15 seconds and then shut off?
Continued from page 36.
Do the burners come on and turn
off immediately (1 to 2 seconds)?
Test for 24V at valve during the opening period (usually 7 to
10 seconds after power to heater). Is there 24V to valve for 15
seconds?
Yes
The following can cause the heater to shut down:
• Improper grounding.
• High winds.
• Dirty environment.
• Fluctuating gas pressure.
Do the burners
stay on?
No
Does the heater stay on
until the call for heat ends?
Yes
Yes
No
No
Yes
No
Diagnostic Indicator
LED
MODE
1 Flash
Start up.
2 Flashes
Flame. No call for heat.
3 Flashes
Ignition lockout.
4 Flashes
Valve relay lockout.
Replace circuit board.
Yes
No
Yes
Yes
No
Contact factory.