QTD2
Series
20
3.0
Installation
•
Sidewall Venting
Sidewall Venting
Guidelines:
Vent Pipe Angle
• To prevent moisture from entering the heater system, slope the vent pipe downward toward the
outlet 1/4 in. per foot of length.
Do not
pitch the heater.
• Vent must extend beyond any combustible overhang if the vent is less than 36 in. below the
combustible overhang.
Figure 3.11
•
Sidewall Venting Requirements
Building Overhang
Sidewall
Double-Wall
B-Vent
Single
Wall Vent
Vent
Adapter
Vent
Collar
Wall Thimble
Sidewall Vent Cap
6 in.
min.
B to C Adapter
Heater
1/4 in. downward
pitch per foot
36 in.
min.