MW2
Series
11
2.0
Installation
•
Heater Mounting
Heater Mounting
WARNING
!
Improper suspension of the infrared heater may result in collapse and being crushed.
Always suspend from a permanent part of the building structure that can support the
total force and weight of the heater.
Failure to maintain minimum clearances to combustibles may result in fire and/or
explosion, property damage, serious injury, or death. Always maintain minimum
clearances and post signs or provided tags (F/N: LL001) adjacent to heater’s controller.
Signs should state the hazards for the particular application and be legible to the building
occupants. Consult the factory or a factory representative for additional information on
signage compliance.
The heater can be suspended with chains or rigid threaded rod. Local codes, or conditions that would
cause the unit to move (e.g., wind drafts, blowers, crane rails, etc.), may require rigid threaded rod.
Consult all applicable codes before installation.
The heater must be level from side to side and may be 0° to 45° on horizontal. Refer to Figures 2.2 and
2.3.
Chart 2.3
•
Physical Dimensions (inches)
Model No.
A
B
C
MW2-24X1
23.50
9.625
24.50
MW2-24X2
23.50
15.25
24.50
MW2-24X3
23.50
21.00
24.50
MW2-33X1
32.50
9.625
33.50
MW2-33X2
32.50
15.25
33.50
MW2-33X3
32.50
21.00
33.50
MW2-46X1
45.50
9.625
46.50
MW2-46X2
45.50
15.25
46.50
MW2-46X3
45.50
21.00
46.50
Figure 2.2
•
Heater Dimensions
Figure 2.3
•
Mounting Centers
11.625
B
C
Mount Heater Level
- End to End -
(Center of Mounts)
A
3.75