MW2
Series
10
2.0
Installation
•
Design
Figure 2.1
•
Heating Application
Series
Lamp
Qty.
Recommended
Mounting Height (Ft.)*
[Dim. A]
Recommended
Distance Between
Heaters (Ft.) [Dim. B]
Approximate
Square Foot
Coverage
Approximate
Watts per
Square Foot
MW2-24
1
7 to 9
2 to 7
200
4
2
7 to 9
3 to 9
200
8
3
8 to 10
4 to 11
300
8
MW2-33
1
7 to 9
3 to 9
200
6
2
8 to 10
4 to 11
300
8
3
8 to 10
5 to 13
300
11
MW2-46
1
8 to 10
4 to 11
300
7 to 10
2
10 to 14
5 to 13
500
8 to 12
3
10 to 15
6 to 15
500
12 to 18
Chart 2.1
•
Basic Heating Application Chart
When comfort heating people, two heaters should be used to heat both sides of the individual. Heater
installation shall comply with all IOPM, NEC, ANSI/NFPA-70, CEC, and local restrictions.
* Clearances to combustibles published in this manual and on safety labels must be maintained at all
times. Factory recommended mounting heights are listed as a guideline. If infrared heaters are mounted
too low or too high, they may result in discomfort or lack of heat.
Type of Building
Watts Req. per Square
Foot at Floor Level
Insulated
10
Uninsulated
16
Outdoor Sheltered
25 to 30
Outdoor Unsheltered
30 to 45
Chart 2.2
•
Estimating Required Load
Dim A*
Dim B