If the Smart Wireless® CXT is ordered with the Relay PCA option, the Relay PCA can be configured to
provide either ‘Wet’ or ‘Dry’ contacts for external annunciator activation.
The ‘Wet’ contact option
provides a nominal 11V Battery Power to external annunciators when an alarm is initiated. These wet relay
outputs are rated for 9-11.1 VDC, 2A max total (A1, A2, A3, and FLT outputs combined). The ‘Wet’
contacts are available on a 5 pin (Figure 7) or 6-pin (Figure 8) Alarm Connector. These outputs are
specifically meant for external 12V annunciators such as the external A1 C1D2 Horn or four-strobe/two-
strobe alarm bar, which is designed to operate on the unit’s 12V Battery.
The 6-pin Alarm connector is intended for use with the Detcon Four-Strobe or Two-Strobe Alarm Bar. The
Two-Strobe Alarm Bar has strobes that are activated when alarm 1 or alarm 2 are active on the CXT
controller. The Four Strobe alarm bar has strobes that can be configured to activate individually when a
specific sensor is in alarm (See Section 5.3.2 for configuration information).
W e tR ela y C onn
e ctor R a ti
ngs
Voltage: 9-11.2 VDC
Current: 2 Amps max through single relay connector (2 Amps max total across all pins).
CAUTION
When utilizing ‘Wet’ contacts, the maximum power that can be drawn by the
annunciators is 2A.
12V Battery Power
12V Return
Relay PCA
NC
COM
NO
FAULT
NC
COM
NO
ALARM 3
NC
COM
NO
ALARM 2
NC
COM
NO
ALARM 1
Enclosure
ALARM 2
(Gray) 3
Alarm Connector
ALARM 3
(Brown) 4
FAULT
(BLUE) 5
ALARM 1
(White) 2
GND
(Black) 1
1
1
2
3
4
5
Figure 7 5-pin External Alarm Connector for ‘Wet’ Alarm Contacts