Se nti
nel C X T
Sentinel CXT Instruction Manual
Rev. 1.7
Page 26 of 49
C O N FIG U R A T IO N SU M M A R Y
C H A N N EL S:##
A O 4S:##
W IR EL ESS T R A N SC EIV ER W T S:##
R L 4/
A L A R M ST A T IO N C O U N T :##
[R U N SY ST EM A U T O C O N FIG U R E]
4. Swipe the ENTER marker to initiate the search. The CXT controller will perform an incremental
search for available 700/100 and 600 serial sensors starting with Modbus
™
address 01h and analog
inputs with a minimum current of 1.80mA.
N O T E
All sensors must be powered on to be detected correctly.
N O T E
The channel tags for the analog inputs will be set to “PPM H2S” by default. These can be
changed in the Utilities menu (Section 11.2).
N O T E
The channel tags for detected serial sensors will be set to gas type and units by default.
These can be changed through the Utilities menu.
5. The search will continue until Modbus
™
address 7Fh is reached or until it is terminated by swiping
the ENTER marker which will save the serial sensors. When all of the connected sensors are
identified, swipe ENTER to begin detecting alarm stations with Modbus
™
address 80h.
6. The search will continue until Modbus
™
address 8Fh is reached or until it is terminated by swiping
the ENTER marker which will save the alarm stations. When all of the connected alarm stations are
identified, swipe ENTER to begin detecting wireless radios with Modbus
™
address 01h.
7. The search will continue until Modbus
™
address 7Fh is reached or the search is terminated by
swiping the ENTER marker which will save the wireless radio modules found.
N O T E
A swipe of the PROG marker at any time while in search mode will cancel the search and
restore the default settings. Any devices found up to that point will not be saved.
5.4.2 SetC ha nnel D a ta
The Setup Channel Data menu configures each channel represented by its assigned sensor or device. When
a sensor or device is added to the controller, the information can be added/modified in this menu.
Information to be configured is as follows:
1. Slave ID fixed
2. Device Type fixed
3. Analog Input fixed
4. Decimal Point DA4 only
5. Range DA4 only
6. Type
7. RL4 Bank Count
1. Upon entering this menu, the LCD will display:
C H A N N EL 1 D A T A :
D EC IM A L P O IN T :#
SL A V EID :##
R A N G E:#####
D EV IC ET Y P E:X X X
T Y P E:X X X X X X X X X
A N A L O G IN P U T :#
R L 4B A N K C N T :X X X