12V Return
Upper Relay PCA
NC
COM
NO
FAULT
NC
COM
NO
ALARM 3
NC
COM
NO
ALARM 2
NC
COM
NO
ALARM 1
Enclosure
(Orange) 4
Alarm Connector
(Black) 5
(White) 1
(Blue) 6
(Red) 2
1
1
2
3
4
5
6
(Green) 3
Lower Relay PCA
NC
COM
NO
FAULT
NC
COM
NO
ALARM 3
NC
COM
NO
ALARM 2
NC
COM
NO
ALARM 1
12V Battery Power
Figure 8 6-pin External Alarm Connector for ‘Wet’ Alarm Contacts
The Smart Wireless® CXT is also available with ‘Dry’ relay contacts (Figure 9). Dry relay Contacts allow
the user to control annunciators that operate off an exterior power source that relies on the controller to
provide only contact closure to apply voltage to the annunciator. The ‘dry’ relays are rated for 120-
220VAC/24VDC, 2A max. It is important to note that the ‘Dry’ contact feature utilizes a common return
for all annunciators.
Relay PCA
NC
COM
NO
FAULT
NC
COM
NO
ALARM 3
NC
COM
NO
ALARM 2
NC
COM
NO
ALARM 1
Enclosure
ALARM 2
(Green) 3
Alarm Connector
(Pin 2 is not used)
ALARM 3
(Orange) 4
FAULT
(Blue) 6
ALARM 1
(White) 1
COM
(Black) 5
1
1
2
3
4
5
6
Figure 9 External Alarm Connector Pin out for ‘Dry’ alarm contacts