When no alarms or faults exist on the SmartWireless® CXT, the Main Display will show the status of all
the sensors in the gas detection system. When the SmartWireless® CXT is in alarm, the LCD display will
stay on the channel group with the channel in alarm. If multiple alarms/faults exist, the CXT will cycle
through group pages with alarms/faults including the transceiver, RL-4/alarm station, and AO-4 group
pages. At any time the user can manually cycle to any group page using the arrow switches. After a time
out period (15 seconds), the CXT will resume page cycle protocols based upon the existence of
alarms/faults.
Four LED indicators on the front panel show alarm and fault alarm output status. The LEDs represent
ALM 1 (yellow), ALM 2 (yellow), ALM 3 (red) and FAULT (blue).
N O T E
The CXT only cycles through sensor group pages when no alarms/faults exist.
5.3.1 Sensor G roup
X X >
Y Y Y "D e vi
ce T a g"
X X
– represents the corresponding channel number
Y Y Y
– the gas concentration value
"D e vi
ce T a g" –
Either user enter tag or COMM ERROR.
IN AL AR M # = Ifany channelisinany gasalarm condition,# isthealarm level.
IN FAU L T = Ifany gaschannelisinfault.
0 CO M M ER R = Ifany channelisnotappropriately com m unicatingw iththedevice.
5.3.2 T ra nsce i
ve r G roup
W T X X ‘Sta tus’ Y Y Y %
X X
– represents the transceiver Modbus slave address.
‘Status’
– Status message of the alarm station.
O FFL IN E= N otcom m unicating.
DC P O W ER = Com m unicating;linepow ered.
BAT T ER R = Com m unicating;cannotreadsm artbattery pack.
L O W BAT T = Com m unicating;sm artbattery tim etoem pty below thesetthreshold.
45+ DAYS = Com m unicating;sm artbattery packhasm orethan45 daysbeforeem pty.
0-45 DAYS = Com m unicating;thenum berofdaysuntilsm artbattery packisem pty.
5.3.3
YYY% - represents the link quality of the transceiver.
R e la y M odule
R M X X >‘Sta tus’
XX – represents the relay module Modbus slave address.
‘Status’– Status message of the relay module.
CO M M ER R = N otcom m unicatingw ithm odule.
R L 4 M O DU L E= Com m unicatingw ithm odule.
R FS ILEN CE= CX T ControllerisinR FS ilencem ode
AL M IN HIBIT = CX T ControllerisinAlarm Inhibitm ode
5.3.4
ALM TEST = CXT Controller is in Alarm Test mode
W i
reless A la rm Sta ti
on/
B M 25
A SX X ‘Sta tus’ Y Y Y %