Det-Tronics UVIR Series Instructions Manual Download Page 6

95-8546

4

17.3

Quick Fire (High Speed)

The Quick Fire (High Speed) feature can be used in 

conjunction with the TDSA signal processing method.  

This method overrides TDSA requirements in the event 

of a sudden and intense signal, such as the result of a 

flash fire. When Quick Fire is activated, the detector is 

capable of responding to an intense fire signal in less 

than 30 milliseconds (0.030 seconds). Using the Quick 

Fire feature in conjunction with TDSA signal processing 

allows the detector to provide a high speed response to 

a large, non-flickering fire (such as in high pressure gas 

applications). Additionally, when the Quick Fire feature 

and TDSA signal processing are used in conjunction, the 

detector maintains an ability to respond to fires that start 

very small and grow in size and intensity over time.

UV DETECTOR OPTIONS

The UV detector output (measured in counts per second) 

is compared to the fire threshold (the “sensitivity” 

setting). If the radiant energy level from the fire exceeds 

the selected alarm threshold level, the fire alarm output is 

activated. In every application, it is crucial to ensure that 

the radiant ultraviolet energy level from the expected fire 

at the required distance from the detector will exceed the 

selected sensitivity level.

The UV detector in the X5200, X5200G, and X5200M can 

be programmed for:

 

– Arc Rejection

 

– Standard Signal Processing

Arc Rejection

The Arc Rejection mode enables the detector to 

prevent nuisance fire alarms caused by UV from short-

duration electrical arcs or electrostatic discharge, 

while maintaining the ability to reliably detect the UV 

radiation given off by a flame. Typical applications that 

benefit from arc rejection logic include electrostatic 

coating processes and uncontrolled environments where 

transient UV sources can be present, such as many 

typical outdoor applications. Most false alarm sources 

have short transient UV signatures, while fire creates 

a long UV signature over many seconds. Most fires 

are detected in a few seconds (see response times in 

Appendix A).

Standard Signal Processing

Standard signal processing is recommended for high-

speed suppression systems only. To allow for high-speed 

operation, the standard processing mode does not 

incorporate the arc rejection programming. This mode 

should only be used in a controlled, indoor environment.

GENERAL APPLICATION 

INFORMATION

RESPONSE CHARACTERISTICS

Response is dependent on the detector's sensitivity 

setting, arc rejection, and time delay settings. Other 

factors include distance, type of fuel, temperature of the 

fuel, and time required for the fire to come to equilibrium.  

As with all fire tests, results must be interpreted according 

to an individual application.

See Appendix A for third-party approved fire test results.  

Additional fire test results are available from Det-Tronics.

Welding

Electric arc welding is a source of intense ultraviolet 

radiation. UV radiation from arc welding readily scatters 

and can deflect across significant distances, even when 

direct obstructions exist. Any open door or window can 

allow nuisance UV radiation from arc welding to enter an 

enclosed area, causing a possible response from the UV 

detector.

It is recommended that the system be bypassed during 

welding operations in situations where the possibility of a 

false alarm cannot be tolerated. Gas welding mandates 

system bypass, since the gas torch is an actual fire. Arc 

welding rods can contain organic binder materials in 

the flux that burn during the welding operation and are 

detectable by the detector. Welding rods with clay binders 

do not burn and will not be detected by the detector.  

However, system bypass is always recommended, since 

the material being welded may be contaminated with 

organic substances (paint, oil, etc.) that will burn and 

possibly cause the detector to alarm.

Artificial Lighting

The detector should not be located within 3 feet (0.9 m) 

of artificial lights. Excess heating of the detector could 

occur due to heat radiating from the lights.

EMI/RFI Interference

The detector is resistant to interference by EMI and RFI, 

and is EMC Directive compliant and CE marked. It will 

not respond to a 5 watt walkie-talkie at distances greater 

than 1 foot (0.3 m).

Non-Carbon Fires

The UV/IR Fire Alarm response of the detector is limited to 

carbonaceous fuels. It should not be used to detect fires 

from fuels that do not contain carbon, such as hydrogen, 

sulfur, and burning metals. The Auxiliary relay can be 

configured to change states upon a UV alarm only.  

When configured in this manner, the UV sensor within the 

detector can be used to detect non-carbonaceous fires.

Summary of Contents for UVIR Series

Page 1: ...17 3 Rev 4 17 95 8546 Instructions UVIR Flame Detector Series X5200 X5200G and X5200M...

Page 2: ...e Damage 8 Wiring Procedure 8 Setting Device Network Addresses EQ and EQP Models Only 14 STARTUP PROCEDURE 15 Fire Alarm Test 15 TROUBLESHOOTING 15 MAINTENANCE 16 Cleaning Procedure 16 oi Plate Remova...

Page 3: ...and outdoor applications The standard output configuration includes fire fault and auxiliary relays Output options include 0 to 20 mA output in addition to the three relays Pulse output for compatibil...

Page 4: ...ault conditions Table 2 indicates the condition of the LED for each status ATTENTION The X5200 and X5200M contain a source tube that is filled with a gas mixture containing Krypton 85 Kr85 a radioacti...

Page 5: ...oi function COMMUNICATION The detector is furnished with an RS 485 interface for communicating status and other information with external devices The RS 485 supports Modbus protocol with the detector...

Page 6: ...ng mode does not incorporate the arc rejection programming This mode should only be used in a controlled indoor environment GENERAL APPLICATION INFORMATION RESPONSE CHARACTERISTICS Response is depende...

Page 7: ...ust be avoided For example if IR radiation with an intensity that exceeds the fire threshold of the IR sensor should reach the detector as a flickering signal and if at the same time an electric arc w...

Page 8: ...nert and are not absorbed by the body No special handling measure or personal protection equipment is needed for the UVIR detectors Not applicable to model X5200G which does not contain Kr85 The follo...

Page 9: ...me detection monitoring This will minimize the possibility of false alarms caused by activities outside the area requiring protection The detector must be mounted on a rigid surface in a low vibration...

Page 10: ...the cable length Typically 16 AWG or 2 5 mm2 shielded cable is recommended Wires should be stripped 3 8 inch 9 mm A minimum input voltage of 18 Vdc must be present at the detector NOTE Refer to Power...

Page 11: ...ensure that the insulating material of the wiring terminal block will not be affected by the heat generated by EOL resistors observe the following guidelines when installing the resistors 1 Required...

Page 12: ...IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING Figure 7 Ex d Wiring Option C2137 FIRE ALARM PANEL DETECTOR ALARM ALARM 24 VDC EOL DEVICE 4 oi TEST 3 9 8 7 6 5 4 3 2 1 19...

Page 13: ...urrent Output Sinking 24 VDC mA PLC 600 MAX AT 24 VDC D2140 oi TEST 1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 mA mA 29 28 27 26 25 24 23 22 21 MAN Oi DETECTOR 24 VDC Vin Vin Vin Figure 11 Detecto...

Page 14: ...of this manual for switch setting procedure 5 Check all field wiring to be sure that the proper connections have been made 6 Replace the device cover and apply input power 7 Make the final sighting ad...

Page 15: ...4 1 SHIELD 6 3 COM2 COM1 P1 P2 P3 P4 IN OUT B B COMMON C C SUPPLY A A CH 1 CH 5 IN OUT B B COMMON C C SUPPLY A A CH 2 CH 6 IN OUT B B COMMON C C SUPPLY A A CH 3 CH 7 IN OUT B B COMMON C C SUPPLY A A...

Page 16: ...s to the network address switches For hazardous areas the area must be de classified before attempting disassembly of the device Always observe precautions for handling electrostatic sensitive devices...

Page 17: ...ing at the detector before checking system wiring for continuity 6 If all wiring checks out and cleaning of the oi plate window did not correct the fault condition check for high levels of background...

Page 18: ...urface of the windows during cleaning can create static electricity that could result in unwanted output activation 2 Clean the viewing windows and reflective surfaces of the oi plate using a clean cl...

Page 19: ...000 general 500 alarms Microprocessor controlled heated optics for increased resistance to moisture and ice Automatic manual or magnetic oi testing Easily replaceable oi plate Fire fault and auxiliary...

Page 20: ...e Fault relay has redundant terminals and normally open contacts normally energized operation and latching or non latching operation Auxiliary relay Form C 5 amperes at 30 Vdc The auxiliary relay has...

Page 21: ...ted for up to 14 AWG wire and are DIN VDE rated for 2 5 mm2 wire Screw terminal required torque range is 3 5 4 4 in lbs 0 4 0 5 N m Important 18 Vdc minimum must be available at the detector For ambie...

Page 22: ...regulations from the country of source of return TDG RID ADR etc These units are classified as UN2911 Radioactive Material Excepted Package Article Not applicable to model X5200G not subjected to UN2...

Page 23: ...D TYPE 4M 4 Port Metric M25 4N 4 Port 3 4 NPT TYPE OUTPUTS 11 Relay 13 Relay and 0 20 mA 14 Eagle Quantum Premier EQP 15 Relay and Pulse 23 HART Relay and 0 20 mA 24 Eagle Quantum TYPE APPROVALS T SIL...

Page 24: ...ectors Part Number Description 102740 002 Magnet 007739 001 Magnet and Extension Pole 007290 001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors 007290 002 Q...

Page 25: ...onds n Heptane 1 x 1 foot 50 15 2 8 Add 2 seconds for EQP model High Sensitivity UV Low Sens IR Hi Arc TDSA On Quick Fire Off Fuel Size Distance feet m Typical Response Time seconds n Heptane 1 x 1 fo...

Page 26: ...dulated 5 1 5 2 inch dia Heptane 5 1 5 2 500 w shielded quartz halogen lamp modulated 5 1 5 2 inch dia Heptane 5 1 5 2 1500 w electric quartz heater unmodulated 10 3 2 inch dia Heptane 5 1 5 3 1500 w...

Page 27: ...Vertical degrees Typical Vert Response Time seconds Methane 32 inch plume 7 5 2 2 45 45 0 9 0 2 45 30 0 1 0 1 Very High Sensitivity UV IR Low Arc TDSA On Quick Fire On Fuel Size Distance feet m Horizo...

Page 28: ...incandescent lamp modulated 3 0 9 1 x 1 foot n Heptane 40 12 6 500 w halogen lamp unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 1 500 w halogen lamp modulated 3 0 9 1 x 1 foot n Heptane 40 12 11 1500 w...

Page 29: ...for use in Class II Groups E F G Hazardous Locations CAN CSA C22 2 No 30 M1986 Explosion Proof Enclosures for Use in Class I Hazardous Locations CAN CSA C22 2 No 94 M91 Special Purpose Enclosures CAN...

Page 30: ...type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 IP67 rated suitable for the conditions of us...

Page 31: ...shall maintain the degree of ingress protection IP66 IP67 for the apparatus Unused conduit entries shall be closed with suitable blanking elements NOTE For ATEX installations the detector housing mus...

Page 32: ...talled Unused entries shall be closed with suitable certified blanking elements The metal housing for the Ultraviolet Infrared UVIR flame detector must be electrically connected to earth ground For am...

Page 33: ...proval VdS Construction Product Regulation VdS G 203058 VdS 2344 VdS 2504 EN 54 10 A1 BRE Construction Product Regulation 0832 CPR F1178 EN 54 10 A1 0832 CPR F1685 EN 54 10 A1 EN 54 17 LPCB 973e 05 EN...

Page 34: ...T6 Tamb 55 C to 60 C T5 Tamb 55 C to 75 C RUSSIA VNIIPO CERTIFICATE OF CONFORMITY TO TECHNICAL REGULATIONS GOST R 53325 2012 C US 01 B 02841 BRAZIL UL BR 17 0216X Ex db eb IIC T6 T5 Ex tb IIIC T80 C...

Page 35: ...System Corporate Office 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com All trademarks are the property of their respective owners 2017 Detector Electronics Corporation All rights...

Reviews: