95-8546
12
17.3
EQP Model
1. Connect external wires to the appropriate terminals
inside the device junction box, shown in Figure 13.
See Figure 14 for terminal identification.
2. Connect the shield of the power cable to earth
ground at the power source.
3. Connect shields for the LON cable as indicated. See
Figure 15.
NOTE
DO NOT ground any shields at the detector
housing.
4. With input power disconnected, set the device
network address. (See the “Setting Device Network
Addresses” section of this manual for switch setting
procedure.)
5. Check all field wiring to be sure that the proper
connections have been made.
6. Replace the device cover and apply input power.
7. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
NOTE
Refer to the Eagle Quantum Premier system
manual, number 95-8533, for information regarding
power requirements, network communication
cable requirements, and configuration.
Figure 14—Wiring Terminal Identification for EQP Model
Figure 13—Detector Terminal Block (EQP Model)
6
5
4
3
2
1
16
15
14
13
12
11
SHIELD
SHIELD
COM 1 A
COM 2 A
COM 1 B
COM 2 B
PWR SHIELD
PWR SHIELD
+Vin
+Vin
–Vin
–Vin
C2089