APPENDIX E
EN54 APPROVALS
The following accessories are EN54-10 and EN54-17 approved for use with X5200 and X5200G Flame Detectors:
Part Number
Description
102740-002
Magnet
007739-001
Magnet and Extension Pole
007290-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001
Q9033 Collar Attachment
Certification Bodies
Conventional Output
LON Output
Certificate/Approval
Number
Basis of Approval
Certificate/Approval
Number
Basis of Approval
VdS –
Construction Product Regulation
—
—
—
—
VdS
G 203085
VdS 2344
VdS 2504
EN 54-10 + A1
—
—
BRE –
Construction Product Regulation
0832 – CPR- F1838
EN 54-10 + A1
0832 – CPR – F1839
EN 54-10 + A1
EN 54-17
LPCB
973e/02
EN 54-10 + A1
973a/02
EN 54-10 + A1
EN 54-17
APPLICABLE TO MODEL X5200
Certification Bodies
Conventional Output
LON Output
Certificate/Approval
Number
Basis of Approval
Certificate/Approval
Number
Basis of Approval
VdS –
Construction Product Regulation
—
—
—
—
VdS
G 203058
VdS 2344
VdS 2504
EN 54-10 + A1
—
—
BRE –
Construction Product Regulation
0832 – CPR- F1178
EN 54-10 + A1
0832-CPR-F1685
EN 54-10 + A1
EN 54-17
LPCB
973e/05
EN 54-10 + A1
973a/05
EN 54-10 + A1
EN 54-17
APPLICABLE TO MODEL X5200G
INSTRUCTIONS FOR THE APPLICATION OF THE APPROVAL COMPONENT/SYSTEM
The installation of the X5200 and X5200G flame detectors meet the directional dependence requirements of EN 54-
10, Clause 5.4 for any
β
angle when the
α
angle does not exceed ±30° (total field of view = 60°).
A maximum achievable horizontal
α
angle of ± 45° (total Horizontal field of view = 90°) was obtainable with a
β
angle
of 0° (unit mounted in the upright position).
The X5200 and X5200G flame detectors are EN 54-10 approved for any combination of the following settings described for
each Class:
Setting
Class 1 (25 m)
Class 2 (17 m)
Class 3 (12 m)
UV Sensitivity
High or Very High
Medium, High, or Very High
Low, Medium, High, or Very High
IR Sensitivity
High or Very High
Medium, High, or Very High
Low, Medium, High, or Very High
Arc Rejection
Low, Medium, High, or Very High
Low, Medium, High, or Very High
Low, Medium, High, or Very High
TDSA
On
On
On
Quick Fire
On or Off
On or Off
On or Off