Det-Tronics UVIR Series Instructions Manual Download Page 5

3

95-8546

17.3

The detector signals a fault condition when less than half of 

the detection range remains. This is indicated by the Fault 

output and is evident by the yellow color of the LED on the 

face of the detector. See the "Troubleshooting" section for 

further information.

Magnetic 

oi

 / Manual 

oi

The detector also incorporates both Magnetic 

oi

 (Mag 

oi

)

 

and Manual 

oi

 

(Man 

oi

) features that provide 

the same calibrated test as the Automatic 

oi

, and in 

addition actuates the Alarm output to verify operation for 

preventive maintenance requirements.  These features 

can be performed at any time and eliminate the need for 

testing with a non-calibrated external test lamp.

CAUTION

These tests require disabling of all extinguishing 
devices to avoid release resulting from a successful 
test.

The Mag 

oi

 test is performed by placing a magnet at the 

location marked "MAG OI" on the outside of the detector 

(see Figure 2). The Man 

oi

 test is accomplished by 

connecting the 

oi

 lead (terminal 22) to power supply minus 

via an external switch. The magnet or switch must be held 

in place for a minimum of 6 seconds to complete the test. 

Either of these test methods activates the calibrated UV 

and IR emitters. If the resulting signal meets the test criteria, 

indicating that greater than half of the detection range 

remains, the fire alarm output of the detector is activated. 

On models with relay, 0–20 mA, or HART outputs, this 

condition remains until the magnet is removed or the switch 

is released, regardless of whether the detector has been 

configured for latching or non-latching operation. The fire 

alarm output condition stays active for three seconds on 

Eagle Quantum Premier models. 

If less than half of the detection range remains, no alarm 

is produced and a fault is generated. The fault indication 

can be reset by momentarily applying the Mag 

oi

 or Man 

oi

 switch. In this case, the detector's optics should be 

cleaned and the 

oi

 tests should be repeated. See the 

"Cleaning Procedure" section of this manual for details.

NOTE

Refer to Appendix A for FM verification of the  

oi

 

function.

COMMUNICATION

The detector is furnished with an RS-485 interface for 

communicating status and other information with external 

devices. The RS-485 supports Modbus protocol, with the 

detector configured as a slave device.

For HART communication, connect a HART communicator 

across a 250 ohm resistor in the 0-20 mA loop. HART output 

models do not support RS-485 Modbus protocol.

NOTE

The EQP model uses LON/SLC communication.  RS-485 
and HART communication are not available on the EQP 
model. 

DATA LOGGING

Data logging capability is also provided. Status conditions 

such as normal, power down, general and 

oi

 faults, pre-

alarm, fire alarm, time and temperature are recorded. 

Each event is time and date stamped, along with the 

temperature and input voltage. Event data is stored in 

non-volatile memory when the event becomes active 

and again when the status changes.   Data is accessible 

using the Inspector Connector accessory, RS-485, or the 

EQP Controller.

INTEGRAL WIRING COMPARTMENT

All external wiring to the device is connected within 

the integral junction box. The detector is furnished with 

four conduit entries, with either 3/4 inch NPT or M25 

threads.

SIGNAL PROCESSING OPTIONS

The X5200, X5200G, and X5200M feature signal 

processing options for both the UV and IR sensor. These 

options determine the type of logic that the detector will 

use for processing fire signals to customize the detector 

to the application.  

IR DETECTOR OPTIONS

The IR detector in the X5200, X5200G, and X5200M can 

be programmed for:

 

TDSA enabled

 

Both TDSA and Quick Fire enabled (either initiates 

fire alarm)

Time Domain Signal Analysis (TDSA)

The TDSA signal processing technique analyzes the 

input signal in real time, requiring the IR signal to flicker 

randomly in order to recognize it as a fire condition.

Using TDSA signal processing, the detector ignores 

regularly chopped blackbody sources (occurring in areas 

where moving conveyors and hot objects in proximity 

to one another result in a regularly chopped IR signal), 

because it looks for a less uniform signal. However, in the 

presence of a regularly chopped signal, the detector is 

more susceptible to false alarms due to sporadic IR that 

functions as a trigger when occurring in conjunction with 

the regularly chopped signal.

Summary of Contents for UVIR Series

Page 1: ...17 3 Rev 4 17 95 8546 Instructions UVIR Flame Detector Series X5200 X5200G and X5200M...

Page 2: ...e Damage 8 Wiring Procedure 8 Setting Device Network Addresses EQ and EQP Models Only 14 STARTUP PROCEDURE 15 Fire Alarm Test 15 TROUBLESHOOTING 15 MAINTENANCE 16 Cleaning Procedure 16 oi Plate Remova...

Page 3: ...and outdoor applications The standard output configuration includes fire fault and auxiliary relays Output options include 0 to 20 mA output in addition to the three relays Pulse output for compatibil...

Page 4: ...ault conditions Table 2 indicates the condition of the LED for each status ATTENTION The X5200 and X5200M contain a source tube that is filled with a gas mixture containing Krypton 85 Kr85 a radioacti...

Page 5: ...oi function COMMUNICATION The detector is furnished with an RS 485 interface for communicating status and other information with external devices The RS 485 supports Modbus protocol with the detector...

Page 6: ...ng mode does not incorporate the arc rejection programming This mode should only be used in a controlled indoor environment GENERAL APPLICATION INFORMATION RESPONSE CHARACTERISTICS Response is depende...

Page 7: ...ust be avoided For example if IR radiation with an intensity that exceeds the fire threshold of the IR sensor should reach the detector as a flickering signal and if at the same time an electric arc w...

Page 8: ...nert and are not absorbed by the body No special handling measure or personal protection equipment is needed for the UVIR detectors Not applicable to model X5200G which does not contain Kr85 The follo...

Page 9: ...me detection monitoring This will minimize the possibility of false alarms caused by activities outside the area requiring protection The detector must be mounted on a rigid surface in a low vibration...

Page 10: ...the cable length Typically 16 AWG or 2 5 mm2 shielded cable is recommended Wires should be stripped 3 8 inch 9 mm A minimum input voltage of 18 Vdc must be present at the detector NOTE Refer to Power...

Page 11: ...ensure that the insulating material of the wiring terminal block will not be affected by the heat generated by EOL resistors observe the following guidelines when installing the resistors 1 Required...

Page 12: ...IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING Figure 7 Ex d Wiring Option C2137 FIRE ALARM PANEL DETECTOR ALARM ALARM 24 VDC EOL DEVICE 4 oi TEST 3 9 8 7 6 5 4 3 2 1 19...

Page 13: ...urrent Output Sinking 24 VDC mA PLC 600 MAX AT 24 VDC D2140 oi TEST 1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 mA mA 29 28 27 26 25 24 23 22 21 MAN Oi DETECTOR 24 VDC Vin Vin Vin Figure 11 Detecto...

Page 14: ...of this manual for switch setting procedure 5 Check all field wiring to be sure that the proper connections have been made 6 Replace the device cover and apply input power 7 Make the final sighting ad...

Page 15: ...4 1 SHIELD 6 3 COM2 COM1 P1 P2 P3 P4 IN OUT B B COMMON C C SUPPLY A A CH 1 CH 5 IN OUT B B COMMON C C SUPPLY A A CH 2 CH 6 IN OUT B B COMMON C C SUPPLY A A CH 3 CH 7 IN OUT B B COMMON C C SUPPLY A A...

Page 16: ...s to the network address switches For hazardous areas the area must be de classified before attempting disassembly of the device Always observe precautions for handling electrostatic sensitive devices...

Page 17: ...ing at the detector before checking system wiring for continuity 6 If all wiring checks out and cleaning of the oi plate window did not correct the fault condition check for high levels of background...

Page 18: ...urface of the windows during cleaning can create static electricity that could result in unwanted output activation 2 Clean the viewing windows and reflective surfaces of the oi plate using a clean cl...

Page 19: ...000 general 500 alarms Microprocessor controlled heated optics for increased resistance to moisture and ice Automatic manual or magnetic oi testing Easily replaceable oi plate Fire fault and auxiliary...

Page 20: ...e Fault relay has redundant terminals and normally open contacts normally energized operation and latching or non latching operation Auxiliary relay Form C 5 amperes at 30 Vdc The auxiliary relay has...

Page 21: ...ted for up to 14 AWG wire and are DIN VDE rated for 2 5 mm2 wire Screw terminal required torque range is 3 5 4 4 in lbs 0 4 0 5 N m Important 18 Vdc minimum must be available at the detector For ambie...

Page 22: ...regulations from the country of source of return TDG RID ADR etc These units are classified as UN2911 Radioactive Material Excepted Package Article Not applicable to model X5200G not subjected to UN2...

Page 23: ...D TYPE 4M 4 Port Metric M25 4N 4 Port 3 4 NPT TYPE OUTPUTS 11 Relay 13 Relay and 0 20 mA 14 Eagle Quantum Premier EQP 15 Relay and Pulse 23 HART Relay and 0 20 mA 24 Eagle Quantum TYPE APPROVALS T SIL...

Page 24: ...ectors Part Number Description 102740 002 Magnet 007739 001 Magnet and Extension Pole 007290 001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors 007290 002 Q...

Page 25: ...onds n Heptane 1 x 1 foot 50 15 2 8 Add 2 seconds for EQP model High Sensitivity UV Low Sens IR Hi Arc TDSA On Quick Fire Off Fuel Size Distance feet m Typical Response Time seconds n Heptane 1 x 1 fo...

Page 26: ...dulated 5 1 5 2 inch dia Heptane 5 1 5 2 500 w shielded quartz halogen lamp modulated 5 1 5 2 inch dia Heptane 5 1 5 2 1500 w electric quartz heater unmodulated 10 3 2 inch dia Heptane 5 1 5 3 1500 w...

Page 27: ...Vertical degrees Typical Vert Response Time seconds Methane 32 inch plume 7 5 2 2 45 45 0 9 0 2 45 30 0 1 0 1 Very High Sensitivity UV IR Low Arc TDSA On Quick Fire On Fuel Size Distance feet m Horizo...

Page 28: ...incandescent lamp modulated 3 0 9 1 x 1 foot n Heptane 40 12 6 500 w halogen lamp unmodulated 3 0 9 1 x 1 foot n Heptane 40 12 1 500 w halogen lamp modulated 3 0 9 1 x 1 foot n Heptane 40 12 11 1500 w...

Page 29: ...for use in Class II Groups E F G Hazardous Locations CAN CSA C22 2 No 30 M1986 Explosion Proof Enclosures for Use in Class I Hazardous Locations CAN CSA C22 2 No 94 M91 Special Purpose Enclosures CAN...

Page 30: ...type of explosion protection increased safety e for use with the terminal compartment in type of explosion protection increased safety e They shall be IP66 IP67 rated suitable for the conditions of us...

Page 31: ...shall maintain the degree of ingress protection IP66 IP67 for the apparatus Unused conduit entries shall be closed with suitable blanking elements NOTE For ATEX installations the detector housing mus...

Page 32: ...talled Unused entries shall be closed with suitable certified blanking elements The metal housing for the Ultraviolet Infrared UVIR flame detector must be electrically connected to earth ground For am...

Page 33: ...proval VdS Construction Product Regulation VdS G 203058 VdS 2344 VdS 2504 EN 54 10 A1 BRE Construction Product Regulation 0832 CPR F1178 EN 54 10 A1 0832 CPR F1685 EN 54 10 A1 EN 54 17 LPCB 973e 05 EN...

Page 34: ...T6 Tamb 55 C to 60 C T5 Tamb 55 C to 75 C RUSSIA VNIIPO CERTIFICATE OF CONFORMITY TO TECHNICAL REGULATIONS GOST R 53325 2012 C US 01 B 02841 BRAZIL UL BR 17 0216X Ex db eb IIC T6 T5 Ex tb IIIC T80 C...

Page 35: ...System Corporate Office 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com All trademarks are the property of their respective owners 2017 Detector Electronics Corporation All rights...

Reviews: