B-2
95-8676
3.1
• For installations in which both the Ci and Li of the intrinsically safe apparatus exceeds 1% of the Co and Lo parameters
of the associated apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be
exceeded. The reduced capacitance shall not be greater than 1 µF for Groups IIA and/or IIB, and 600 nF for Group IIC.
Additional Safety Notes:
• The following warning is on the product: Warning: Do not open when an explosive gas atmosphere may be present. For
ambient temperature above 60°C use field wiring suitable for maximum ambient temperature. For temperature below
–10°C use suitable field wiring for the lowest temperature.
• The ambient temperature range is limited to –55°C to +75°C (for Ex db version) or –50°C to +75°C (for Ex db eb
version).
• Cable, bushings and the conduit entries shall be of a type already certified according to relevant ATEX standard, so the
protection principle employed will not be impaired.
• Unused conduit entries shall be closed using stop plugs certified for the conditions of use (IP66/IP67 minimum). The stop
plugs should be removable only with the aid of a tool.
• The terminal compartment for Eclipse without relays is designed for either an increased safety “e” termination or a
flameproof “d” termination of the supply cable. If a flameproof connection is chosen, then an ATEX certified cable entry
device certified to EN60079 must be used. The Eclipse with relays requires Ex d cable entry devices only.
• Shielded cable is required.
• The measuring function of the Infrared Gas Detector model PIRECL CO2 version, for explosion protection, according to
Annex II clause 1.5.5, 1.5.6 and 1.5.7 of the Directive 94/9/EC is NOT covered in this EC-Type Examination Certificate.
EN Standards:
EN 50270: 2006
EN 60079-0: 2012 + A11:2013
EN 60079-1: 2014
EN 60079-7: 2015
EN 60079-11: 2012
EN 60529: 1991+ A1 2000
EN 61000-6-4 (Emissions)
EN 61000-6-2 (Immunity)
EN 61010-1:2010
CE: Conforms to:
Low Voltage Directive: 2006/95/EC (until April 19th, 2016)
2014/35/EU (from April 20th, 2016)
EMC Directive: 2004/108/EC (until April 19th, 2016)
2014/30/EU (from April 20th, 2016)
ATEX Directive: 2009/94/6/EEC (until April 19th, 2016)
2014/34/EU (from April 20th, 2016)
Marine Equipment Directive: 96/98/EC, 2015/90/EU