background image

CONNECTIONS AND HARDWARE

The HART Communicator can interface with the Open Path Eclipse from the onboard I.S. communication port,
from the control room, or from any wiring termination point in the analog output signal loop.  To communicate, con-
nect the HART communicator in parallel with the Open Path Eclipse analog signal or load resistor.  The connec-
tions are non-polarized.

NOTE

The HART Communicator needs a minimum of 250 ohms resistance in the loop to function properly.  The
HART Communicator does not measure loop current directly.

ONLINE MENU

When HART communication is established with the receiver, the first menu displayed is the OPGD RX Root menu:

To select any of the 5 menu options shown, highlight the desired option using the up/down arrow key, and then
press the “right arrow” key.

COMMONLY USED HART COMMANDS

The most commonly used HART commands for the Model OPECL are:

1. Setting the real time clock

2. Setting alarm thresholds & latch/nonlatch functions

3. Setting the analog fault code menu

4. Performing full system alignment

5. Performing zero calibration

6. Assigning a nonvolatile tag name to the receiver

7. Defining a nonvolatile descriptor for future reference

8. Interrogating the history menu for information including total running hours, max/min exposed temperature,

calibration and event logs.

A-3

95-8556

2.1

OPGD RX Root Menu

1)  Process Menu
2)  Status Menu
3)  Setup Menu
4)  Calibration Menu
5)  Test Menu

Summary of Contents for Open Path Eclipse OPECL

Page 1: ...Infrared Hydrocarbon Gas Detector Open Path Eclipse Model OPECL Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 87...

Page 2: ...1 Wiring Cable Requirements 11 Power Wiring Size and Maximum Length 12 Optional Relays 12 Wiring Procedure 13 STARTUP 16 ALIGNMENT 16 Overview 16 Basic Alignment Procedure 16 Fine Alignment Procedure...

Page 3: ...along with mounting fixture hardware Both modules are powered from an external 24 volt DC supply The receiver provides the measurement signal outputs and is furnished with an onboard status indicatio...

Page 4: ...ture A xenon lamp illuminates the linear detection path from the transmitter to the receiver In the event that the primary lamp fails the back up lamp is brought into service The receiver recognizes t...

Page 5: ...on via a flashing red color and a HIGH alarm condition via a steady red color The OPECL internal magnetic switch or HART Field Communicator can be used to reset latched alarms A short duration magneti...

Page 6: ...communicator for system setup commissioning and diagnostics Onboard LED Indicator Indicates normal fault and backup lamp operation status Green indicates normal operation Amber indicates operation in...

Page 7: ...this output The factory default for full scale 5 LFL meters output is 20 mA MODBUS interfaces also have the ability to calibrate the 4 mA and 20 mA levels FAULT INDICATION Faults and status conditions...

Page 8: ...or MODBUS communication FAULT RELAY Form C Type NO NC Energized during Normal mode De Energized on Fault or loss of power Contact Rating 5 amperes at 30 VDC Non Latching Operation only not programmab...

Page 9: ...001 see Appendix B Class I Div 2 Groups A B C D T4 Type 4X CENELEC Standard range and long range models 0539 II 2 G DEMKO 03 ATEX 135898X EEx de ib IIC T5 T5 Tamb 40 C to 60 C IP67 Transmitter Receive...

Page 10: ...diameter pipe Refer to Figure 3 for mounting dimensions SHIPPING WEIGHT Transmitter with mounting plate 35 pounds 16 kg Receiver with mounting plate 35 pounds 16 kg WARRANTY 3 year limited warranty f...

Page 11: ...por density and flashpoint should be identified and used to assist in selecting the optimum detector mounting locations within the area The detector must be installed by qualified personnel only follo...

Page 12: ...longterm outdoor operation in very cold climates is intended extra shielding covers are recommended to prevent accumulation of snow and ice on the windows Deluge and Flooding The modules are rated IP6...

Page 13: ...source of 24 Vdc power is being utilized verify that system requirements are met NOTE If disconnection of power is required separate disconnect capability must be provided WIRING CABLE REQUIREMENTS A...

Page 14: ...y the resistance of the wire ohms foot value available in wire manufacturer s specification data sheet 3 Divide by 2 For example Consider an installation using 18 AWG wiring with a power supply provid...

Page 15: ...g terminal configuration for the OPECL receiver with relays Figures 11 through 14 show the 4 to 20 mA output of the OPECL receiver in various wiring schemes Figure 15 shows the OPECL wired to a Model...

Page 16: ...N 4 to 20 MA B2051 TOTAL LOOP RESISTANCE 250 OHMS MINIMUM 600 OHMS MAXIMUM Figure 12 Detector Wired for Non Isolated 4 to 20 ma Current Output Sourcing Figure 11 Detector Wired for Non Isolated 4 to 2...

Page 17: ...Sinking CURRENT OUTPUT CHASSIS GROUND POWER SENSOR EXTERNAL RESET HIGH ALARM HIGH ALARM OC AUX ALARM AUX ALARM OC LOW ALARM LOW ALARM OC FAULT FAULT OC 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 TO 32 VD...

Page 18: ...g all OPECL systems The following instructions cover the use of the Telescope Alignment Tool 3 Calibration Magnet 4 For installations with module separation distances between 5 and 30 meters a range r...

Page 19: ...e to dead center on the window of the receiver module Tighten the vertical alignment locking nuts so that no movement will occur 17 95 8556 2 1 VERTICAL ALIGNMENT LOCKING NUTS 2 VERTICAL ADJUSTMENT BO...

Page 20: ...y performing a zero calibration 15 Perform a zero calibration Refer to Zero Calibration in the Calibration section of this manual Any faults or alarms that may be present as a result of the alignment...

Page 21: ...eceiver module s onboard HART communication port 2 Turn on the HART communicator and check for OPECL device recognition When HART communication is established the OPGD Rx Root menu will be displayed o...

Page 22: ...bject such as cardboard until a beam block fault is generated CALIBRATION CALIBRATION OVERVIEW Although routine calibration of the Open Path Eclipse is normally not required the device supports non in...

Page 23: ...Zero Calibration 1 Apply magnet for 2 seconds minimum to initiate calibration A The onboard LED turns to steady red B The current output decreases to 1 mA 2 When zero calibration is complete A The onb...

Page 24: ...ipment transportation prepaid to the factory in Minneapolis 22 95 8556 2 1 Fault Condition Corrective Action Low 24 volts 24 vdc operating voltage is out of range Verify proper wiring to the detector...

Page 25: ...t flange internal 009186 001 Spare Pan Tilt Mounting Kit for one OPECL module only 007907 001 Sun Shield for one module 008925 001 Spare electronics lamp module for OPECL transmitter 008926 001 Spare...

Page 26: ...priate DDL s for the Open Path Eclipse are included within your Communicator To review the device descriptions programmed into your HART Communicator 1 From the Main menu press to access Offline menu...

Page 27: ...igh Alarm Level 2 High Alarm Latch 3 Low Alarm Level 4 Low Alarm Latch RTC Menu 1 RTC Menu Setup Menu 1 OPGD Option Menu 2 Hart Output Menu 3 Com 485 Menu 4 Config Flt Output Menu 5 Gas Type Menu 6 Ra...

Page 28: ...first menu displayed is the OPGD RX Root menu To select any of the 5 menu options shown highlight the desired option using the up down arrow key and then press the right arrow key COMMONLY USED HART...

Page 29: ...RITTEN UNLESS OTHERWISE SPECIFIED DIMENSION TOLERANCE INCH MM INCH MM REMOVE ALL BURRS BREAK ALL EDGES AND SHARP CORNERS THIS DRAWING AND SPECIFICATION CONTAIN PROPRIETARY INFORMATION AND ANY REPRODUC...

Page 30: ...Printed in USA Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Reviews: