background image

Assembly and Wiring Procedure

Connect the external wiring to the appropriate terminals
on the DCU terminal wiring board.  See Figure 9.

IMPORTANT

Insulate the shields to prevent shorting to the
device housing or to any other conductor.

Attach the sensor to the DCU enclosure.  Do not over-
tighten.  If a sensor separation kit is being used, attach
the sensor to the separation kit junction box and wire
the device as described below.

CAUTION

The sensor threads can be coated with an appro-
priate grease to ease both the initial installation
and future replacement of the sensor.  Detector
Electronics offers a silicone free grease that is
especially suited for use with catalytic type com-
bustible gas sensors (part number 102868-001).
The use of other lubricants is not recommended,
since some materials can cause irreversible dam-
age to the sensing element.  SILICONE based
lubricants or compounds must NEVER be used.

Screw the transmitter board to the standoffs as shown in
Figure 8.  Connect the sensor plug to the transmitter
board.

Attach the communication module to the standoffs
mounted on the transmitter board.  Connect the ribbon
cable from the terminal wiring board to the communica-
tion module.

Set the address for the device (see “Addressability” on
page 3).

Sensor Separation with DCUEX

If the installation requires mounting the sensor in a dif-
ferent location than the DCUEX, observe the following
guidelines.

When separating a combustible gas sensor from the
DCUEX, two options exist:

1.   Preferred Method

Mount the transmitter PC board inside the sensor
separation junction box.  This assembly can be
separated from the DCUEX by up to 1000 feet using
three conductor 18 AWG shielded cable.
(Regardless of separation distance, operating volt-
age at the transmitter MUST be at least 18 vdc to
ensure proper operation.)  See Figure 10.

Assemble the DCUEX without the transmitter board
similar to the DCU as shown in Figure 4.   Plug the
sensor into P2 on the transmitter board.  Use a
three conductor 18 AWG shielded cable to connect
P1 on the transmitter board to terminals 2, 3 and 4
on the DCU terminal board (see Figure 10).
Connect the shield to the ground terminal in the
DCUEX junction box.

2.

Alternate Method.

If the transmitter board must be mounted separate
from the sensor (high temperature applications,
etc.), separate the sensor only, leaving the transmit-
ter PC board inside the DCUEX enclosure.  When
using this installation option, see Table 2 for maxi-
mum wiring distances.

Mount the sensor directly to the separation kit junc-
tion box.  Use three conductor shielded cable for
the connection between the terminal block in the
separation kit junction box and P1 on the transmitter
board.  A plug with screw terminals is provided for
connecting the cable to P1 on the transmitter board.
Observe the wiring color code.  Connect the shield
to the ground terminal in the DCUEX junction box.

7

90-1118

1

2

3

4

5

6

7

8

9

10

SIG

+

DCU TERMINAL BOARD

DCU TRANSMITTER BOARD1

(MIDDLE BOARD)

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

B1877

NOTES: 1 Catalytic Combustible Gas Sensor

Plugs into Connector Pins on the
Middle Board inside the Junction Box.

2 Connections Wired at the Factory.

2

2

2

Figure 9—DCU Transmitter Board Connected 

to Terminal Wiring Board

Summary of Contents for Eagle Quantum EQ2200DCU

Page 1: ...patented fault isolation Utilizes state of the art communication technology Pass through communication circuitry on power loss Ten bit signal resolution capability Two alarm setpoints Non volatile mem...

Page 2: ...tus indicat ing LEDs that are visible through a viewing window on the enclosure cover and supports single person non intrusive calibration with a Det Tronics gas sensor DETECTOR ENCLOSURE The NEMA 4X...

Page 3: ...ork segment The DCU communicates with the LCU over the digital highway as shown in Figure 2 In the event of a single open or short circuit on the digital highway all units will be fully functional con...

Page 4: ...e Do not over tighten If a sensor separation kit is used attach the sensor to the separation kit junction box and wire the device as described in the Sensor Separation section CAUTION The sensor threa...

Page 5: ...ions for the detectors Whenever practical detectors should be placed where they are easily accessible for calibration WARNING Do not apply power to the system with the cover removed unless the area ha...

Page 6: ...ch other using the standoffs provided See Figure 8 NOTE Be sure to note correct orientation of the trans mitter board If the transmitter board is rotated 180 from proper orientation the device will no...

Page 7: ...sensor separation junction box This assembly can be separated from the DCUEX by up to 1000 feet using three conductor 18 AWG shielded cable Regardless of separation distance operating volt age at the...

Page 8: ...E mail detronics detronics com The specifications contained within this document are subject to change without notice R E GISTERED BY UL AND B S I N O A2305 NO 2582 6 ISO 9001 R E G I STERED F I R M R...

Reviews: