Det-Tronics Eagle Quantum EQ2200DCU Manual Download Page 4

NOTE

Refer to the Eagle Quantum system manual,
form number 95-8470, for complete instructions
regarding wiring and installation.

EQ2200DCU DIGITAL COMMUNICATION UNIT USED
WITH DET-TRONICS H

2

S/O

2

SENSORS OR OTHER

TWO-WIRE 4 TO 20 MA DEVICES

Determine the best mounting locations for the detectors.
Whenever practical, detectors should be placed where
they are easily accessible for calibration. 

WARNING

Do not apply power to the system with the cover
removed unless the area has been verified to be
free of combustible gases or vapors.

The DCU utilizes the following:

1.

A terminal wiring board mounted at the bottom of
the junction box.

2.

A communication module mounted above the termi-
nal wiring board using the standoffs provided.  See
Figure 4.

Assembly and Wiring Procedure

Attach the sensor to the DCU enclosure.  Do not over-
tighten.  If a sensor separation kit is used, attach the
sensor to the separation kit junction box and wire the
device as described in the “Sensor Separation” section.

CAUTION

The sensor threads can be coated with an appro-
priate grease to ease installation.  Also lubricate
the cover threads.

Connect the external wiring to the appropriate terminals
on the DCU terminal wiring board.  Refer to Figure 5 for
terminal identification.  See Figure 6 for an example of a
Det-Tronics electrochemical sensor wired to a DCU.

4

A1571

COMMUNICATION MODULE

STANDOFFS (4)

TERMINAL WIRING BOARD

Figure 4—Printed Circuit Boards in Universal DCU

1

2

3

4

5

6

7

8

9

10

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

A1726

Figure 5—Terminal Identification for DCU

1

2

3

4

5

6

7

8

9

10

BLACK

RED

GREEN

DCU

H2S/TOXIC/O2

14

13

12

11

+

+

24 VDC

POINTWATCH CALIBRATE

4 TO 20 MA IN

+

A

B

A

B

SENSOR POWER

COM 2

COM SHIELD

COM 1

A1875

Figure 6—Electrochemical Sensor Connected to DCU

Summary of Contents for Eagle Quantum EQ2200DCU

Page 1: ...patented fault isolation Utilizes state of the art communication technology Pass through communication circuitry on power loss Ten bit signal resolution capability Two alarm setpoints Non volatile mem...

Page 2: ...tus indicat ing LEDs that are visible through a viewing window on the enclosure cover and supports single person non intrusive calibration with a Det Tronics gas sensor DETECTOR ENCLOSURE The NEMA 4X...

Page 3: ...ork segment The DCU communicates with the LCU over the digital highway as shown in Figure 2 In the event of a single open or short circuit on the digital highway all units will be fully functional con...

Page 4: ...e Do not over tighten If a sensor separation kit is used attach the sensor to the separation kit junction box and wire the device as described in the Sensor Separation section CAUTION The sensor threa...

Page 5: ...ions for the detectors Whenever practical detectors should be placed where they are easily accessible for calibration WARNING Do not apply power to the system with the cover removed unless the area ha...

Page 6: ...ch other using the standoffs provided See Figure 8 NOTE Be sure to note correct orientation of the trans mitter board If the transmitter board is rotated 180 from proper orientation the device will no...

Page 7: ...sensor separation junction box This assembly can be separated from the DCUEX by up to 1000 feet using three conductor 18 AWG shielded cable Regardless of separation distance operating volt age at the...

Page 8: ...E mail detronics detronics com The specifications contained within this document are subject to change without notice R E GISTERED BY UL AND B S I N O A2305 NO 2582 6 ISO 9001 R E G I STERED F I R M R...

Reviews: