3.2.3 Outdoor Air Supplemental Information
3.2.3.1
LC and LV Operation Modes
No outside
air CFM
Outside air
damper closed
Evap by-pass damper
in open position
Outside
air filter
Standard
evaporator CFM
Standard evaporator
by-pass CFM
Condenser
Evap
Unoccupied Mode
(Blower on)
Condenser
Evap
Standard
evaporator CFM
Standard evaporator
by-pass CFM
No outside
air CFM
Outside air
damper closed
Outside
air filter
Evap by-pass damper
in open position
Figure 20 - LC Models left; LV Models right - Unoccupied Mode Operation
Figure 21 - LC Models left; LV Models right - Occupied Mode Operation
3.2.4 Determining if Outdoor Air Pre-Heating is Required
Desert Aire systems require that outdoor air be pre-heated if mixed air temperatures
inside the unit may fall below 45°F. To determine if an application requires outdoor air
pre-heating, the following study needs to be conducted:
1.
Determine the following:
•
Design return air temperature. For pool rooms, typically 82°F
•
Outdoor air winter design temperature. Use values as specified by
design
engineer
or
ASHRAE
tables
•
Total system CFM and required outdoor air CFM
Reduced evap by-pass
damper opening
Condenser
Evap
Outside air
damper open
Outside
air filter
Specified outside
air CFM
Outside air
damper open
Reduced evap by-pass
damper opening
Outside
air filter
Standard
evaporator CFM
Reduced evaporator
by-pass CFM
Condenser
Evap
Occupied Mode
(Blower on)
Specified outside
air CFM
Standard
evaporator CFM
Reduced evaporator
by-pass CFM