Troubleshooting
Although Desert Aire dehumidifiers have been designed for reliable and trouble-free operation,
you may occasionally encounter a service-related problem. If you cannot immediately
diagnose and fix the problem, do not be intimidated by the apparent complexity of the
dehumidifier. Your common sense and experience can help you solve the majority of these
problems.
These problems or complaints are frequently caused by improper interlocks between the
dehumidifier and the other equipment and accessories at the jobsite. You may need to consult
with other contractors who have worked on different portions of this project.
The following list will help you diagnose some of the most obvious symptoms of a system
which does not work properly.
4.1
The Blower Does Not Run
POSSIBLE CAUSES
“Occupied” switch is in the open position
Loss of main power
Damper is stuck or frozen, preventing the
actuator end switch from closing
Blower overload has tripped
Faulty control wiring
REMEDY
Close “occupied” switch
Check for tripped circuit breaker or blown fuses
Free the damper or replace the actuator if it is
defective
Correct cause and reset overload
Check for loose or incorrect wires on system
and controller