Low Pressure Alarms (Below 97 PSIG) / Evaporator Coil Icing
POSSIBLE CAUSES
Faulty or improperly set hot-gas bypass
valve
Insufficient evaporator air flow rate
Lack of refrigerant
Restricted refrigerant filter-drier
Defective expansion valve
Restriction in refrigeration piping
REMEDY
Set hot-gas valve to maintain 30°F suction
(97 PSIG) or replace if defective
Assure coil is clean and belts are tight
Re-evaluate system charge
Evaluate filter pressure drop and replace if
necessary
Evaluate expansion valve performance and
replace if necessary
Check coil for kinks in tubing and check for
debris in distributor