background image

5

103449

OWNER’S MANUAL

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_______________________ Btu/Hr

Gas water heater*

_______________________ Btu/Hr

Gas furnace

_______________________ Btu/Hr

Vented gas heater

_______________________ Btu/Hr

Gas fireplace logs

_______________________ Btu/Hr

Other gas appliances* _______________________ Btu/Hr

Total                            _______________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Continued

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Example:

Gas water heater

40,000

Btu/Hr

Vent-free heater     +

33,000

Btu/Hr

Total

=

73,000

Btu/Hr

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

orif the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the
methods described in the 

National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

Summary of Contents for VS18NR

Page 1: ...roperty damage Refer to this manual for cor rect installation and operational proce dures For assistance or additional in formation consult a qualified installer service agency or the gas supplier WAR...

Page 2: ...with a fire placescreeninplace Makesurefireplace screen is closed before running heater 8 This log heater is designed to be smoke less If logs ever appear to smoke turn offheaterandcallaqualifiedservi...

Page 3: ...ed to ANS Z21 11 2 standard for unvented heaters State and local codes in some areas prohibit the use of vent free heaters This heater may also be operated as a vented decorative ANS Z21 60 product by...

Page 4: ...rating of one perm 6x10 11 kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to ar...

Page 5: ...ances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr max...

Page 6: ...d Crawl Space To Crawl Space To Attic Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 Ventilation Grills Into Adjoining Room Option 1 12 12 Figure 2 Ventila...

Page 7: ...l codes INSTALLATION CHECK GAS TYPE Use only natural gas If your gas supply is not natural gas do not install heater Call dealer where you bought heater for proper type heater INSTALLATION AND CLEARAN...

Page 8: ...ntel If not using a mantel follow the information below You must have noncombustible material s above the fireplace opening Noncombus tible materials such as slate marble tile etc must be at least 1 2...

Page 9: ...pening Underside of Mantel Shelf Mantel Shelf 12 A 20 241 2 271 2 30 All minimum distances are in inches 2 1 2 6 8 10 Minimum Noncombustible Material 8 Min 12 15 18 All minimum distances are in inches...

Page 10: ...rsarelevel Ifheaterisnotlevel heaterwill not work properly Area of Various Standard Round Flues Diameter ins Area sq ins 5 20 sq inches 6 29 sq inches 7 39 sq inches 8 51 sq inches INSTALLING DAMPER C...

Page 11: ...ed Purchase the optional A G A design certified manual shutoff valve from your dealer See Accessories page 23 Minimum inlet pressure for purpose of input adjustment Figure 13 Gas Connection Tee Joint...

Page 12: ...ts individual manual shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where manual shutoff valve was connected 3...

Page 13: ...ure 16 Push back of logs flush with metal grate bar Note 18 model has only one front log 2 Rest bottom middle log 2 behind metal posts on front burner Make sure the grooves in the bottom of the log fi...

Page 14: ...re to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not us...

Page 15: ...em etc For wall thermostat operation follow in struction supplied with thermostat acces sory GWMT1 For wall switch operation followinstructionssuppliedwithGWMS2 OPTIONAL REMOTE OPERATION NOTICE You mu...

Page 16: ...Off with the Hand Held Remote Unit Figure 24 Thermostat Hand Held Remote Control Unit Selections GHRCT only The log heater will automatically cycle between pilot and the heat setting that has been se...

Page 17: ...e pattern Theincorrectpilotflameisnottouch ing the thermocouple This will cause the thermocouple to cool When the thermo couple cools the heater will shut down If pilot flame pattern is incorrect as s...

Page 18: ...ware store or home center may carry com pressed air in a can You can use a vacuum cleaner in the blow position If using com pressed air in a can please follow the direc tions on the can If you don t f...

Page 19: ...D PROBLEM When ignitor button is pressed there is no spark at ODS pilot When ignitor button is pressed there is spark at ODS pilot but no ignition ODS pilot lights but flame goes out when control knob...

Page 20: ...en using furniture polish wax carpet cleaners or similar products 1 Replace 9 volt batteries in receiver and remote control OBSERVED PROBLEM One or both burners do not light after ODS pilot is lit Del...

Page 21: ...SIBLE CAUSE 1 Metal expanding while heating or con tracting while cooling 1 Heater burning vapors from paint hair spray glues cleaners chemicals new carpet etc See IMPORTANT state ment above 2 Low fue...

Page 22: ...r TECHNICAL SERVICE You may have further questions about in stallation operation or troubleshooting If so contact DESA International s Technical Service Department at 1 800 DESA LOG 1 800 337 2564 You...

Page 23: ...LL MOUNT ON OFF SWITCH GWMS2 Not Shown For all models Allows the gas log heater to be turned on and off with a wall switch WALL MOUNT THERMOSTAT SWITCH GWMS1 Not Shown For all models The desired comfo...

Page 24: ...URAL GAS LOG HEATER DESA INTERNATIONAL ILLUSTRATED PARTS BREAKDOWN VARIABLE CONTROL CFS18NR VS18NR VS24NR VS30NR 8 9 10 11 8 8 12 13 23 14 26 27 6 6 16 19 31 21 22 29 30 17 24 20 15 28 18 10 1 10 2 6...

Page 25: ...271 03 Ignitor Cable 1 14 102445 01 102445 01 102445 01 Piezo Ignitor 1 15 103588 01 103588 01 103588 01 Heat Shield 1 16 103782 01 103782 01 103782 01 Valve Bracket 1 17 M12461 26 M12461 26 M12461 26...

Page 26: ...such other costs related to repairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EX...

Reviews: