13

104323

OWNER’S MANUAL

CONNECTING TO GAS
SUPPLY

Figure 22 - External Regulator with Vent
Pointing Down

 WARNING: A qualified ser-

vice person must connect fire-
place to gas supply. Follow all
local codes.

 CAUTION: Never connect fire-

place directly to the propane/LP
supply. This fireplace requires
an external regulator (not sup-
plied). Install the external regula-
tor between the fireplace and pro-
pane/LP supply.

 CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
or greater diameter to allow
proper gas volume to fireplace. If
pipe is too small, undue loss of
pressure will occur.

 

 CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incoming gas pressure to between 11 and
14 inches of water. If you do not reduce
incoming gas pressure, fireplace regulator
damage could occur. Install external regu-
lator with the vent pointing down as shown
in Figure 22. Pointing the vent down pro-
tects it from freezing rain or sleet.

Install sediment trap in supply line as shown
in Figure 23. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into fireplace controls. If sediment
trap is not installed or is installed wrong,
fireplace may not run properly.

Propane/LP
Supply Tank

Vent Pointing Down

External Regulator

Attaching Wood Base to Solid
Floor

For attaching base to solid floors (concrete
or masonry)

Note:

 Floor anchors and mounting screws

are in hardware package. The hardware pack-
age is provided with fireplace.

1.

Drill holes at marked locations using
5/16" drill bit. For solid floors (concrete
or masonry), drill at least 1" deep.

2.

Fold floor anchor as shown in Figure 21.

3.

Insert floor anchor (wings first) into
hole. Tap anchor flush to floor.

4.

Insert mounting screws through base
and into floor anchors.

5.

Tighten screws until base is firmly fas-
tened to floor.

Installation must include a manual shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
fireplace (see Figure 23).

IMPORTANT:

 Install main gas valve

(manual shutoff valve) in an accessible
location. The main gas valve is for turning
on or shutting off the gas to the appliance.

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged fireplace valves.

Continued

Figure 23 - Gas Connection

3" Minimum

From External
Regulator
(11" W.C.** to
14" W.C.
Pressure)

A.G.A. Design-Certified Manual
Shutoff Valve with 1/8" NPT Tap*

Gas Control

Approved Flexible
Gas Hose

Tee Joint

Pipe
Nipple

Cap

Sediment Trap

*Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer.
See Accessories, pages 26 and 27.

**Minimum inlet pressure for purpose of input adjustment.

Extension Cord

Use extension cord if needed. The cord must
have a three-prong, grounding plug and a
three-hole receptacle. Make sure cord is in
good shape. It must be heavy enough to carry
the current needed. An undersized cord will
cause a drop in line voltage. This will result
in loss of power and overheating. Use a No.
16 AWG cord for lengths less than 50 feet.

Figure 21 - Folding Anchor

INSTALLATION

Continued

Summary of Contents for Vanguard VMH26PR

Page 1: ...t Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improperinstallation adjustment alteration service or maintenance can cause injury or p...

Page 2: ...cool before touching 18 Carefully supervise young children when they are in same room with fire place 19 Do not use fireplace if any part has been under water Immediately call a quali fied service te...

Page 3: ...hipping damage If fireplace is damaged promptly inform dealer where you bought fireplace PRODUCT FEATURES SAFETY PILOT This fireplace has a pilot with an Oxygen Depletion Sensor Shutoff System ODS The...

Page 4: ...ges 26 and 27 Install op tional blower now Follow installation instructions provided with blower 5 Gently place back log on burner sup port see Figure 2 The log should fit flat against top of burner s...

Page 5: ...in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the outside atmosphere...

Page 6: ...__________ Btu Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the act...

Page 7: ...Crawl Space To Attic AIR FOR COMBUSTION AND VENTILATION Continued VENTILATION AIR Ventilation Air From Inside Building Thisfreshairwouldcomefromanadjoining unconfined space When ventilating to an adj...

Page 8: ...UTION This fireplace cre ateswarmaircurrents Thesecur rents move heat to wall surfaces next to fireplace Installing fire place next to vinyl or cloth wall coverings or operating fireplace where impuri...

Page 9: ...ight 26 26 7 8 Front Width 26 3 4 26 7 8 Depth 9 1 2 10 1 2 Bottom 3 4 3 4 1 Frame in rough opening Use dimen sions shown in Figure 8 for the rough opening If installing in a corner use dimensions sho...

Page 10: ...on wood base 3 Place mantel around fireplace base as sembly 4 Assemble brass trim kit See Assem bling Brass Trim 5 Firmly snap brass trim kit on shoulder screws Shoulder screws are located on fireplac...

Page 11: ...of valve cover shield 2 Make sure the wire harness is firmly connected to the terminals on the blower bracket assembly 3 Note the wire locations on back of AUTO OFF ON switch The terminals on back of...

Page 12: ...e box cover to secure the wiring Wir ing should be routed through the bushing in the hole on the outer casing of heater 1 Install a snap bushing found in hard ware kit into one of the holes found rear...

Page 13: ...ing base to solid floors concrete or masonry Note Floor anchors and mounting screws areinhardwarepackage Thehardwarepack age is provided with fireplace 1 Drill holes at marked locations using 5 16 dri...

Page 14: ...he fireplace The flexible gas supply line con nection to the manual shutoff valve should be accessible 4 Apply pipe joint sealant lightly to male threads of gas connector attached to flexible gas line...

Page 15: ...k for a leak Apply a mixture of liquid soap and water to all joints Bubbles forming show a leak Correct all leaks at once TestPressuresEqualToorLessThan 1 2 PSIG 1 Close manual shutoff valve see Fig u...

Page 16: ...should be done by a quali fied installer familiar with low voltage wiring procedures INSTALLATION Continued OPTIONAL WIRELESS HAND HELD REMOTE CONTROL ACCESSORIES GHRC Series GHRCT Series Installing...

Page 17: ...t wire to bottom contact of switch see Figure32 2 Connect remaining wire terminal to the TH terminal on the control valve Make sure that wire terminals are in the positions on your unit as pictured in...

Page 18: ...screen in place Make sure fire place screen is installed before running fireplace 1 STOP Read the safety information column 1 2 Make sure manual shutoff valve is fully open 3 Set switch in OFF positio...

Page 19: ...structions on page 18 1 After lighting let pilot flame burn for about one minute Turn control knob to ON position Adjust flame adjust ment knob anywhere between HI and LO Slide the selector switch to...

Page 20: ...page 17 of this manual IMPORTANT The hand held remote control unit must be near the heater Do not keep the hand held remote control unit too close to the heater The thermostat on the hand held re mot...

Page 21: ...ct Burner Flame Pattern Figure43 IncorrectBurnerFlamePattern WARNING If yellow tipping occurs your fireplace could pro duce increased levels of carbon monoxide If burner flame pat tern shows yellow ti...

Page 22: ...aged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind b...

Page 23: ...Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Observe minimum installation clea...

Page 24: ...produces a clicking ticking noise just after burner is lit or shut off Heater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor d...

Page 25: ...air inlet holes prior to each heating season Blocked air holes will create soot We rec ommend that you clean the unit every 2 500 hours of operation or every three months Wealsorecommendthatyoukeepth...

Page 26: ...o stain or paint Complete assembly instructions in cluded Three sided brass trim kit included CABINET MANTEL WITH BUILT IN HEARTH BASE AND TRADITIONAL SQUARE LEG STYLING Unfinished GM923U Finished GM9...

Page 27: ...ed under warranty PARTS UNDER WARRANTY Contact authorized dealers of this product If they can t supply original replacement part s call DESA International s Technical Service Department at 1 800 323 5...

Page 28: ...SIC HEARTH FIREPLACE VMH26PR 28 ILLUSTRATED PARTS BREAKDOWN VMH26PR 39 37 38 22 40 11 28 30 12 7 35 25 10 4 9 7 23 1 2 8 4 4 14 6 24 33 34 31 32 13 17 21 5 26 18 15 27 1 27 2 41 41 41 41 3 29 16 18 17...

Page 29: ...1 Baffle 1 24 101628 01 Flexible Connector 1 25 104305 01 Control Shield 1 26 103295 01CJ Screen Assembly 1 27 103058 01 Log Set Assembly 1 27 1 104058 01 Branch Service Kit 1 27 2 104058 02 Back Log...

Page 30: ...cts caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective fireplace will be the responsibility of the owner TO T...

Reviews: