background image

FRENCH PG. 75

W415-2354 / B / 12.09.20

ADD MANUAL TITLE 

Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 103 Miller Drive, Crittenden, Kentucky, USA, 41030

Phone 1 (866) 820-8686 • www.napoleon.com • [email protected]

CERTIFIED TO THE CANADIAN AND AMERICAN NATIONAL STANDARDS: 

CSA 2.22 AND ANSI Z21.50 FOR VENTED DECORATIVE GAS APPLIANCES

INSTALLER: 

Leave this manual with the appliance

CONSUMER: 

Retain this manual for future reference

ADD PRODUCT CODE HERE (TRADE GOTHIC LT STD FONT)

NATURAL GAS MODELS:

PROPANE GAS MODELS:

Product Name / Code

(MUST use title from Price Book)

ADD ____ ILLUSTRATED

ADD PRODUCT IMAGE

CSA / 

INTERTEK

LOGO

SAFETY INFORMATION

- Do not store or use gasoline or other 

fl ammable vapors and liquids in the vicinity of 

this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

:

•  Do not try to light any appliance.

•  Do not touch any electrical switch; do not 

use any phone in your building.

•  Immediately call your gas supplier from a 

neighbour’s phone. Follow the gas    

supplier’s   instructions.

•  If you cannot reach your gas supplier, call 

the fi re department.

- Installation and service must be 

performed by a qualifi ed installer, service 

agency, or the supplier.

This appliance may be installed in an aftermarket, 

permanently located, manufactured home (USA 

only) or mobile home, where not prohibited by 

local codes.

This appliance is only for use with the type of gas  

indicated on the rating plate. This appliance is 

not convertible for use with other gases, unless 

a certifi ed kit is used. 

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly 

could result in serious injury, death, or 

property damage.

WARNING

!

ENGLISH 

$10.00

FOR INDOOR USE ONLY

IF INSTAL OPERATION, ADD SERIAL 

NUMBER LABEL HERE

IF SEPARATE MANUALS, ADD “PLACE 

BARCODE LABEL ON THE OWNER’S MANUAL”

GX36NTR-1 / GX36NTRE-1

GX36PTR-1 / GX36PTRE-1

Ascent™ X 36

INSTALLATION  MANUAL

PLACE BARCODE LABEL ON THE 

OWNER’S MANUAL

Safety Barrier

Barrièr

e de Pr

otection

Summary of Contents for Ascent X 36

Page 1: ...al switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire d...

Page 2: ...touching hot surfaces Even after the appliance is off it will remain hot for an extended period of time Check with your local hearth specialty dealer for safety screens and hearth guards to protect c...

Page 3: ...and repair should be done by a qualified service person It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean For outdoor products only this...

Page 4: ...ing chimney 40 4 4 1 restricting vertical vents 41 5 0 electrical information 42 5 1 hard wiring connection 42 5 2 electronic wiring diagram 42 5 3 battery back up installation 43 6 0 gas installation...

Page 5: ...iance is a decorative product It is not a source of heat and not intended to burn solid fuel A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the appliance an...

Page 6: ...appliance 2 Install rough framing see rough framing section 3 Place the appliance in its final position 4 Install appliance venting see venting installation section 5 Install all electrical wirings s...

Page 7: ...aled combustion product The installation must conform with local codes or in absence of local codes the National Gas and Propane Installation Code CSA B149 1 in Canada or the National Fuel Gas Code AN...

Page 8: ...outez pas cet appareil aucun mat riau devant entretien contact avec les flammes autre que celui qui est fourni avec cet appareil par le fabricant Maximum horizontal extension X See installation manual...

Page 9: ...B 12 09 20 9 general information 34 5 8 879mm 9 1 16 230mm 15 3 8 391mm 4 102mm 7 178mm 35 889mm SAFETY BARRIER 24 610mm 2 3 16 55 5mm GAS INLET 15 3 4 400mm 8 203mm 1 5 dimensions FRONT VIEW SIDE VI...

Page 10: ...mes Examine the air terminal at least once a year to verify that it is unobstructed and undamaged Rigid and flexible venting systems must not be combined Different venting manufacturer components must...

Page 11: ...vertical runs and elbows Keep it pulled tight A 1 31 8mm air gap all around between the inner liner and outer liner is required for safe operation If approved for use with a power vent kit state This...

Page 12: ...W415 2354 B 12 09 20 EN 12 venting requirements See venting section REAR VENT 40 ft 12m Maximum 3 ft 1m minimum 16 40 6cm minimum 20 50 8cm Max 24 61cm minimum plus rise 24 61cm...

Page 13: ...1 periscope termination 12 30 5cm minimum to grade 30 76 2cm minimum 30 76 2cm minimum 34 5 8 87 9cm 30 MINIMUM 12 MINIMUM TOP EXIT INSTALLATION REAR EXIT INS 30 MINIMUM MAXIMUM 10FT VENT LENGTH 20 5...

Page 14: ...deck or overhang N 16 40 6cm 16 40 6cm Clearance above the roof O 2 0 6m 2 0 6m Clearance from an adjacent wall including neighbouring buildings P 8 2 4m 8 2 4m Roof must be non combustible without o...

Page 15: ...m 4 2 times the vertical rise equal to or greater than the horizontal run 3 times the vertical rise equal to or greater than the horizontal run 13 2A REAR EXIT Horizontal Termination Vertical Terminat...

Page 16: ...al of both horizontal vent lengths Hr and offsets Ho in feet HR combined horizontal vent lengths in feet HO offset factor 03 total degrees of offset 90 in feet VT combined vertical vent lengths in fee...

Page 17: ...90 03 270 90 5 4 FT 1 7m HT HR HO 4 5 FT 1 4m 5 4 FT 1 6m 9 9 FT 3m HT VT 9 9 FT 3m 11 FT 3 4m 20 9 FT 6 4m Formula 1 HT VT 9 9 FT 3m 11 FT 3 4m Formula 2 HT VT 40 FT 12 2m 20 9 FT 6 4m 40 FT 12 2m S...

Page 18: ...75 FT 7 5m Since both formulas are met this vent configuration is acceptable The shaded area within the lines represents acceptable values for HT and VT 90 V1 H1 H2 90 Example V1 4 FT 1 2m V2 1 5 FT 0...

Page 19: ...haded area within the lines represents acceptable values for HT and HT HT VT 16 3B For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT VT Formula 2 HT V...

Page 20: ...5 9 16 3_2D For vent configurations requiring more than two 90 elbows the following formulas apply Formula 1 HT 3 5VT Formula 2 HT VT 24 75 feet 7 5m Example V1 4 FT 1 2m V2 1 5 FT 0 5m VT V1 V2 4FT 1...

Page 21: ...T 18 2A For vent configurations requiring one or more 90 elbows top exit or one or more 90 elbows rear exit the following formulas apply Formula 1 HT VT Formula 2 HT VT 40 feet 12 2m Example V1 5 FT 1...

Page 22: ...llowing formulas apply Formula 1 HT 3 VT Formula 2 HT VT 40 feet 12 2m Example V1 2 FT 0 6m V2 1 FT 0 3m V3 1 5 FT 0 5m VT V1 V2 V3 2FT 0 6m 1FT 0 3m 1 5FT 0 5m 4 5 FT 1 4m H1 6 FT 1 8m H2 2 FT 0 6m H...

Page 23: ...s securing the deflector from inside the top front of the firebox refer to Figure 1 D Place the gasket provided over the 4 102mm flue collar assembly and bend along perforation E From inside the fireb...

Page 24: ...aust plate and slide the shield in place by sliding its slotted openings behind the screwheads tighten the two previously loosened screws Refer to the illustration below C Reinstall the door and safet...

Page 25: ...gasket onto the back of the appliance using the 4 previously removed screws FIG 2 E Remove the 1 1 2 38 1mm thick batt of insulation and discard FIG 2 F Remove the 4 screws securing the inner cover pl...

Page 26: ...constructed entirely of non combustible materials Materials consisting entirely of steel iron brick tile concrete slate glass or plasters or any combination thereof are suitable Materials that are rep...

Page 27: ...ns to combustibles is required NOTE The minimum clearances from the top of the horizontal vent pipe to combustible materials may be reduced from 3 76 2mm to 1 25mm in those installations with a minimu...

Page 28: ...ND MIN 155 8 39 7cm 155 39 7 2 50 8mm CEILING ENCLOSURE PLAFOND TOP EXIT ENCLOSURE The appliance requires a minimum enclosure height of 50 1 2 128 3cm For temperature requirements the enclosure space...

Page 29: ...ound and above the appliance must be left unobstructed 241 8 61 2cm MINIMUM PLUSRISE COMBUSTIBLE NON COMBUSTIBLE 1 25mm 3 76 2mm BRICK 0 0mm IF NON COMBUSTIBLE FINISHINGISUSED SUCHASBRICK ANDSTONE 93...

Page 30: ...TE The vent shield is telescopic and must be adjusted to shield the full depth of the combustible wall penetration See venting section 24 61cm COMBUSTIBLE NON COMBUSTIBLE 1 25mm BRICK 0 0MM IF NON COM...

Page 31: ...enclosure space around and above the appliance must be left unobstructed NOTE The vent shield is telescopic and must be adjusted to shield the full depth of the combustible wall penetration See ventin...

Page 32: ...After rough framing place the appliance in its final position A B For heavier finishing materials such as marble we recommend adding extra support to the frame Ensure there is adequate floor support f...

Page 33: ...plosion or asphyxiation Improper support of the entire venting system may allow vent to sag and separate Use vent run supports and connect vent sections per installation instructions Risk of fire do n...

Page 34: ...between the pipe and the firestop Bend the tabs for reduced side clearances or move the shield for reduced top clearances dependent on specific appliance clearances Do not fill the air space between t...

Page 35: ...iling that the venting system passes through Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the fire...

Page 36: ...king into account the additional length needed for the finished wall surface Apply a heavy bead of the red RTV silicone W573 0002 not supplied to the inner sleeve of the air terminal Slip the vent pip...

Page 37: ...e top of the air terminal is 16 40 6cm above the highest point that it penetrates the roof E Remove nails from the shingles above and to the sides of the air terminal connector Place the flashing over...

Page 38: ...ilicone W573 0002 not supplied C Insert the vent pipes through the firestop maintaining the required clearance to combustibles Apply a heavy bead of Red RTV Silicone W573 0002 not supplied to both the...

Page 39: ...ector Place the flashing over the air terminal connector and slide it underneath the sides and upper edge of the shingles Ensure that the air terminal connector is properly centered within the flashin...

Page 40: ...he air intake flex liner and the exhaust collar must be connected to the exhaust flexible liner Both Simpson Duravent and Selkirk co linear to co axial adaptors have been approved on this appliance Fo...

Page 41: ...pproved restrictor kit This kit is not recommended for short vertical vent runs Depending on the model and or year of your appliance mounting holes may not exist A If mounting holes exist remove the s...

Page 42: ...e appliance wall switch Incorrect wiring will damage controls All wiring should be done by a qualified electrician and shall be in compliance with local codes In the absence of local codes use the cur...

Page 43: ...ntrol module to the black wire of the battery back up Ensure the protective sleeve covers the connections as shown below F Install 4 AA size batteries ensure the positive and negative ends correspond...

Page 44: ...o not change Installation and servicing to be done by a qualified installer Move the appliance into position and secure If equipped with a flex connector the appliance is designed to accept a 1 2 13mm...

Page 45: ...ll electrical power to the appliance and re install the batteries into the transmitter Set thermostat to desired setting if equipped I Turn on the remote wall switch to the appliance J If the applianc...

Page 46: ...ilot if the appliance is not used This countdown will reset anytime the appliance main burner is used Therefore if the appliance is regularly used day to day the pilot will remain on However this syst...

Page 47: ...not continue to burn repeat steps E through I J With pilot lit turn gas knob counter clockwise to the ON position K If equipped with the flame adjustment valve push and turn the knob to high L Turn o...

Page 48: ...ances to combustibles Failure to comply with these instructions may cause a fire or cause the appliance to overheat Ensure all clearances i e back side top vent mantel front etc are clearly maintained...

Page 49: ...e Safety barrier Safety barrier WARNING Glass may be hot Do not touch glass until cooled If equipped with door latches that are part of a safety system they must be properly engaged Do not operate the...

Page 50: ...oor and screen must be removed B Remove the securing screws from the top of the firebox as shown C Install the front hood ensure it is angled downward when installed D Reinstall the previously removed...

Page 51: ...If greater projections are desired increase the clearance to the sides bottom and top by 2 50 8mm for every additional 1 25 4mm of projection If using an optional surround the same rule applies starti...

Page 52: ...2mm 34 5 8 88cm M A N T E L H E I G H T 0 2 50 8mm 2 4 6 8 10 12 MANTEL DEPTH INCHES 4 101 6mm 6 152 4mm 10 254mm 12 30 5cm 8 203 2mm WARNING 45 4 Risk of fire Maintain all specified air space clearan...

Page 53: ...tion Installing electronics or other materials that may be sensitive to heat on a recessed wall will also reduce the effect of direct heat note Add Image Recesses or alcoves above the appliance must b...

Page 54: ...BURNER SUPPORT WITH APPROPRIATE LA BELS I E STUDS PILOT SHIELD BURNER PORTS ETC IF NOT APPLICABLE HIDE THIS SECTION AND USE BOXES BELOW Insert only if applicable Log Number Part Number Description 1...

Page 55: ...2 3 4 4 Pin 1 2 3 4 5 5 Pin 6 D1 D2 Notch Notch Notch A1 A2 B2 B1 Stud Log 2 Stud Log 2 C1 Stud Log 3 D1 D2 Studs Log 4 1 1 2 1 2 A1 A2 B1 B2 A2 C1 3 1 2 3 1 2 3 4 4 Pin 1 2 3 4 5 5 Pin 6 D1 D2 Notch...

Page 56: ...glow when exposed to direct flame however care should be taken to not block off the burner ports Blocked burner ports can cause an incorrect flame pattern carbon deposits and delayed ignition PHAZER l...

Page 57: ...e blower rubbing against the floor of the appliance G Pivot the blower into the bottom of the appliance Ensure the gasket remains in place between the blower and outer shell while sliding the blower a...

Page 58: ...es Natural Gas millibars Propane inches Propane millibars Inlet 7 minimum 4 5 17 4mb minimum 11 2mb 13 minimum 11 32 4mb minimum 27 4mb Outlet 3 5 8 7mb 10 24 9mb This appliance has an air shutter tha...

Page 59: ...rvice person ADD IMAGE HERE 36 1 12 7mm 9 5mm of thermocouple 9 5 Flame must envelop upper 3 8 to 1 2 12 7mm 9 5mm of Flame sensor SIT ELECTRONIC IGNITION 3 8 1 2 9 5mm 12 7mm La fl la 3 8 1 2 9 5mm 1...

Page 60: ...he burner 5 If your appliance is equipped with a safety barrier cleaning may be necessary due to excessive lint dust from carpeting pets etc simply vacuum using the brush attachment 6 If your applianc...

Page 61: ...ss the blower and clean using a soft brush and vacuum Re assemble the various components in reverse order Inspect the relief system The appliance relieves through the main glass door or through the fl...

Page 62: ...ng instructions Razor blades steel wool or other metallic objects must not be used on both surfaces of the glass Doing so can remove a thin layer of metal from the razor blades steel wool or other met...

Page 63: ...arts can be ordered through your Authorized dealer distributor For warranty replacement parts a photocopy of the original invoice will be required to honour the claim When ordering replacement parts a...

Page 64: ...es 09 13 16 W010 3554 Door Latch W290 0282 Exhaust Bracket Gasket W010 3490 SER Exhaust Collar Assembly Front Baffle W018 0158 SER W290 0054 RP4 7 Flange Gasket 4 Restrictor Plate Safety Barrier Assem...

Page 65: ...22 4 9 W432 0078 Manifold Flex Pipe W725 0025 Valve NG W725 0026 Valve P W335 0039 Pilot Hood W455 0070 Pilot Orifice 62 NG W455 0068 Pilot Orifice 35 P W357 0001 Push Button Ignitor W500 0276 SER Ven...

Page 66: ...10 2763 W010 2808 Description Pilot Tube w Fittings 6 Connector Thermosensor Pilot gasket Valve NG Valve P Pilot Assembly NG Pilot Assembly P Yes Yes Yes Yes Yes W455 0068 Pilot Orifice 35 P 2 W456 00...

Page 67: ...ame is impinging on the glass logs rocks media or combus tion chamber Ensure the media is positioned correctly in the appliance Open air shutter to increase the primary air Check the input rate check...

Page 68: ...r if equipped Reset program hold reset button on receiver and wait for 2 beeps Release after second beep Press small flame button on remote within 20 seconds you will hear an additional beep this sign...

Page 69: ...te Minimal voltage from thermocou ple or resistance in circuit ports Parts include ON OFF switch receiver thermocurrent connec tions or temperature switches Measure the voltage it should read a least...

Page 70: ...EADINGS BE SURE TO TURN SCREWS CLOCKWISE FIRMLY TO RESEAL DO NOT OVER TORQUE Leak test with a soap and water solution Air shutter improperly adjusted Return air shutter to specified opening see ventur...

Page 71: ...ulty Loosen and tighten thermocouple Clean thermocouple and valve connection Replace thermocouple Replace valve Faulty valve Replace Pilot burning no gas to main burner gas knob is on HI wall switch t...

Page 72: ...not be caused by mechanical systems such as exhaust fans furnaces clothes dryers etc Any damages to the appliance combustion chamber heat exchanger plated trim or other components due to water weathe...

Page 73: ...EN W415 2354 B 12 09 20 73 notes 29 1...

Page 74: ...oute Transcanadienne Montr al Qu bec H4T 1A3 24 Napoleon Road Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky USA 41030 Phone 1 866 8...

Page 75: ...en ou le fournisseur Cet appareil peut tre install dans une maison pr fabriqu e mobile d j install e demeure si les r glements locaux le permettent Cet appareil doit tre utilis uniquement avec le type...

Page 76: ...s ou autres objets doivent tre gard s une distance d au moins 4 pieds 1 22m du devant de l appareil Assurez vous de disposer de mesures de s curit ad quates pour emp cher les jeunes enfants de toucher...

Page 77: ...alifi Il est imp ratif que les compartiments de contr le le br leur et les passages de circulation d air soient gard s propres afin de fourni une combustion et une circulation d air ad quates Produits...

Page 78: ...112 4 4 terminaison verticale travers une chemin e existante 113 4 4 1 renstreignant des vents verticaux 114 5 0 information lectrique 115 5 1 branchement par c ble 115 5 2 sch ma de c blage lectroniq...

Page 79: ...e est temp rature ambiante ou lorsqu il est chauff l aide d un s choir cheveux ou d une autre source de chauleur similaire Cet appareil est un produit d coratif L appareil n est pas une source de chal...

Page 80: ...sition finale 4 Installez l vacuation de l appareil voir la section installation d vacuation 5 Installez toutes c blages lectrique voir la section information lectrique 6 Installez les conduites de ga...

Page 81: ...mm Un d tecteur de monoxyde de carbone est requis dans toutes les pi ces contenant des appareils aliment s au gaz L appareil n est pas approuv pour installation dans une chambre coucher ou une salle d...

Page 82: ...ourni avec cet appareil par le fabricant Maximum horizontal extension X See installation manual for greater extensions minimum vent lengths and maximum vent lengths L extension horizontale maximale X...

Page 83: ...on g n rales FR 1 5 dimensions Vue de face Vue du c t Vue de dessus 34 5 8 879mm 9 1 16 230mm 15 3 8 391mm 4 102mm 7 178mm 35 889mm SAFETY BARRIER 24 610mm 2 3 16 55 5mm GAS INLET 15 3 4 400mm 8 203mm...

Page 84: ...e les probl mes de performance ou de condensation qui peuvent survenir dans les maisons construites troitement en particulier dans les climats froids Pour une performance optimale de l appareil et une...

Page 85: ...e entr e pav e situ e entre deux maisons unifamiliales et servant aux deux maisons Les codes ou r glementations locaux peuvent exiger des d gagements diff rents Ne laissez pas la gaine flexible se tas...

Page 86: ...415 2354 B 12 09 20 86 FR exigences d vacuation 24 61cm minimum plus la pente Voir la section VACUATION 40 FT 12m Maximum 3 ft 1m minimum 24 61cm 16 40 6cm minimum 20 50 8cm MAX VACUATION SUR L ARRI R...

Page 87: ...u du sol 30 76 2cm minimum 30 76 2cm minimum 34 5 8 87 9cm 2 2 2 installation en coin Lorsque l vent est install en coin la longueur maximale du conduit d vacuation est de 20 50 8cm de course horizont...

Page 88: ...vertures Q 3 0 9m 3 0 9m Voir le tableau pour les dimensions d un mur plus large R 6 1 8m 6 1 8m Voir la tableau pour les dimensions d un mur plus profond La terminaison ne doit pas tre install e sur...

Page 89: ...s courses horizontales Hr et des d viations Ho en pieds HR longueur des courses horizontales combin es en pieds HO facteur de la valeur d une d viation 0 03 du total des degr s de d viation 90 en pied...

Page 90: ...8m H2 2 PI 0 6m HR H1 H2 2 5PI 0 8m 2PI 0 6m 4 5 PI 1 4m HO 0 03 trois coudes 90 90 0 03 270 90 5 4 PI 1 6m HT HR HO 4 5PI 1 4m 5 4PI 1 6m 9 9 PI 3m HT VT 9 9PI 3m 11PI 3 4m 20 9 PI 6 4m Formule 1 HT...

Page 91: ...sont respect es cette configuration d vacuation est acceptable La section ombrag e l int rieur des lignes repr sente des valeurs acceptables pour HT et VT 90 V1 H1 H2 90 Exemple V1 4 PI 1 2m V2 1 5 P...

Page 92: ...T 16 3B Lorsque la configuration de l vacuation exige plus qu un coude de 90 les formules suivantes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 9 PI 2 7m V2 6 PI 1 8m VT V1...

Page 93: ...uration de l vacuation exige plus qu un coude de 90 les formules suivantes s appliquent Formule 1 HT 3 5VT Formule 2 HT VT 24 75 pieds 7 5m Exemple V1 4 PI 1 2m V2 1 5 PI 0 5m VT V1 V2 4PI 1 2m 1 5PI...

Page 94: ...ntes s appliquent Formule 1 HT VT Formule 2 HT VT 40 pieds 12 2m Exemple V1 5 PI 1 5m V2 6 PI 1 8m V3 10 PI 3 1m VT V1 V2 V3 5PI 1 5m 6PI 1 8m 10PI 3 1m 21PI 6 4m H1 8 PI 2 4m H2 2 5 PI 0 8m HR H1 H2...

Page 95: ...16 1 PI 4 9m HT VT 16 1PI 4 9m 4 5PI 1 4m 20 6 PI 6 3m Formule 1 HT 3VT 3VT 3 PI 0 9m x 4 5 PI 1 4m 13 5 PI 4 1m 16 1PI 4 9m 13 5 PI 4 1m Puisque cette formule n est pas respect e cette configuration...

Page 96: ...102mm et plier le long de la perforation E De l int rieur de la chambre de combustion ins rez le collet d vacuation de 4 102mm Installez le d flecteur du ventilation arri re sur le col 4 102mm de com...

Page 97: ...e d flecteur en glissant les ouvertures en forme de fentes derri re les t tes de vis puis resserrez les vis R f rez vous l illustration ci dessous C R installez la porte et l assemblage de l cran de p...

Page 98: ...manuel et les vis sont emball s s par ment dans leur propre sac I partir de l int rieur de la foyer installez le collet d vacuation de 4 101 6mm avec le joint d tanch it vers le haut du foyer et fixe...

Page 99: ...ondant la norme ASTM E 136 m thode de test standard du comportement des mat riaux dans une fournaise avec tube vertical 1382 F 750 C et la norme UL763 sont consid r s comme tant des mat riaux non comb...

Page 100: ...3 76 2mm au dessus doit tre maintenu sur toutes les courses horizontales NOTE Les d gagements minimaux entre le haut de l vent et les mat riaux combustibles peut tre r duite de 2 50 8mm dans ces insta...

Page 101: ...ceinte autour de l appareil et au dessus doit demeurer sans obstruction Voir la section dimensions minimale de l ossature pour plus d informations sur la r duction d vacuation tuyau sup rieur d gageme...

Page 102: ...L VACUATION L ARRI RE Pour la ventilation arri re ne d passement pas 10 254mm de section horizontale de ventilation Voir la section vacuation ENCEINTE AVEC VACUATION L ARRI RE L enceinte de l appareil...

Page 103: ...8mm 10 20 254mm 508mm VENTS 14 1 2 368mm 44 1118mm D GAGEMENTS MAXIMAUX DE VACUATION L ARRI RE EXEMPLE 1 NICHE BUMPOUT ALC VE INT RIEUR ENCEINTE AVEC VACUATION L ARRI RE L enceinte de l appareil doit...

Page 104: ...AUX DE VACUATION L ARRI RE EXEMPLE 2 ALC VE NICHE EXT RIEUR ENCEINTE AVEC VACUATION L ARRI RE L enceinte de l appareil doit avoir une hauteur minimale de 44 111 8cm Afin de respecter les contraintes d...

Page 105: ...brut placez l appareil dans sa position finale A B Pour les mat riaux de finition plus lourds comme du marbre nous vous recommandons d ajouter un support additionnel l ossature Assurez vous que le sup...

Page 106: ...fl chir ou de se s parer Utilisez des supports de conduit et racoordez les sections de conduits selon les instructions d installation Risque d incendie vitez que l isolant touche au conduit d vacuati...

Page 107: ...orient vers le haut La terminaison ne doit pas tre ench ss e dans le mur ou le rev tement ext rieur plus que l paisseur de la bride de la plaque de montage L cran protecteur doit tre fix en place en...

Page 108: ...duit d vacuation pour emp cher l arriv e d air froid dans la pi ce ou autour de l appareil Assurez vous que l espaceur coupe feu et le protecteur de conduit d vacuation conservent le d gagement n cess...

Page 109: ...assurant un chevauchement minimal de 2 50 8mm et fixez l aide d une minimum de trois vis B Installez la gaine flexible ext rieure en la glissant sur le manchon ext rieur de la terminaison et fixez l a...

Page 110: ...oints de la terminaison et du connecteur de terminaison et placez la terminaison par dessus le connecteur de terminaison en vous assurant que le manchon p n tre dans le trou de la terminaison Fixer av...

Page 111: ...ur Scellez avec du scellant haute temp rature rouge W573 0002 non fourni C Ins rez les deux vents dans l espaceur coupe feu en respectant les d gagements aux combustibles requis Appliquez un g n reux...

Page 112: ...es c t s du connecteur de terminaison Placez le solin par dessus le connecteur de terminaison et glissez le sous les c t s et le bord sup rieur des bardeaux Assurez vous que le connecteur de terminais...

Page 113: ...lexible d vacuation Les adaptateurs colin aire coaxial Simpson Duravent et Selkirk sont approuv s pour cet appareil Suivez les instructions d installation du fabricant du syst me d vacuation Des compo...

Page 114: ...du haut de la chambre de combustion aligner la plaque de bride comme illustr et fixer B Si les trous de fixation n existent pas aligner la plaque de bride comme illustr et fixer avec deux vis t le t t...

Page 115: ...ctrical Code ANSI NFPA NO 70 aux tats Unis Allumez toujours la veilleuse que ce soit pour la premi re fois ou lorsque l approvisionnement en gaz est puis avec la porte vitr e ouverte ou retir e 43 1 P...

Page 116: ...ntir que le manchon de protection couvre les connexions comme illustr e ci dessous F Installez quatre piles AA garantir que les extr mit s positive et n gative correspondent ceux identifi s sur le sau...

Page 117: ...e la soupape ont t faits en usine ne les modifiez pas L installation et l entretien doivent tre effectu es par un installateur qualifi Mettez l appareil en place et fixez le Si l appareil est muni d u...

Page 118: ...us bas si quip B Tournez l interrupteur murale de l appareil la position OFF C Coupez l alimentation lectrique l appareil si un travail d entretien doit tre faites D Tournez le soupape fermeture manue...

Page 119: ...Une minuterie commencera alors le d compte pendant environ sept jours avant d teindre la veilleuse si l appareil n est pas utilis Ce d compte se r initialisera chaque fois que le br leur principal de...

Page 120: ...gaz pendant que vous allumez la veilleuse en appuyant sur le bouton poussoir d ignition Gardez le bouton de contr le du gaz enfonc pendant une minute puis rel chez le Si la veilleuse ne reste pas allu...

Page 121: ...GAZ FRENCH 8 203 2mm AVERTISSEMENT Risque d incendie Conservez tous les d gagements aux mat riaux combustibles sp cifi es Ne pas respecter ces instructions peut causer un incendie ou une surchauffe As...

Page 122: ...soulager la pression AVERTISSEMENT AVERTISSEMENT La vitre peut tre chaude Ne touchez pas la vitre jusqu ce qu elle ait refroidi Si quip avec les loquets de porte qui font partie d un dispositif de s c...

Page 123: ...nt tre enl v s B Retirer les vis de fixation de la partie sup rieure de l appareil comme illustr C Installez l avant hotte assurer qu elle est inclin e vers le bas lorsqu il est install D Reinstaller...

Page 124: ...50 8mm pour chaque pouce 24 5mm suppl mentaire de projection Si vous utilisez un moulure optionelle les m me r gles s applique commen ant du sommet du moulure Garantir que les d gagements sont mainte...

Page 125: ...R D E L A T A B L E T T E HAUT DE L OUVERTURE 6 4 2 18 16 14 12 TABLETTE 2 51mm 43 1092mm MINIMUM PLUSLAPENTE 1 25mm 2 51mm 0 SIUNMAT RIAUDE FINITIONINCOMBUSTIBL ESTULTILIS TELQUE DELABRIQUEETDE LAPI...

Page 126: ...blette combustible pour plus d informations des d gagements de la tablette L installation des lectroniques ou d autres mat riaux qui peuvent tre sensibles la chaleur sur un mur en retrait permettra de...

Page 127: ...nental cr ent un effet r aliste et unique qui est diff rent dans chaque installation Prenez le temps de bien installer les braises incan descentes pour obtenir le meilleur effet possible Le couleur de...

Page 128: ...1 2 3 4 5 5 pingle 6 D1 D2 Encoche Encoche Encoche A1 A2 B2 B1 Tige B che 2 Tige B che 2 C1 Tige B che 3 D1 D2 Tiges B che 4 1 1 2 1 2 A1 A2 B1 B2 A2 C1 3 1 2 3 1 2 3 4 4 pingle 1 2 3 4 5 5 pingle 6 D...

Page 129: ...llumer lorsque expos s flamme directe cependant il faut veiller ne pas bloquer ou fermez les orifices du br leur Le blocage des orifices du br leur peut cr er une flamme irr guli re des d p ts de carb...

Page 130: ...re tincelles et enlevez le de l appareil B Enlevez la porte de l appareil en d gageant les loquets de la porte C D branchez le transformateur du module de commande et soulevez le du bas de l appareil...

Page 131: ...t peint S il y a des traces de peinture ou de surpulv risation enlevez les de l assemblage de la veilleuse ou remplacez le Une toile d meri ou un tampon r curage comme Scotch Brite peut tre utilis po...

Page 132: ...9 5mm 12 7mm Flame must envelop upper 3 8 to 1 2 12 7mm 9 5mm of thermocouple La flamme doit envelopper la thermocouple de 3 8 1 2 9 5mm 12 7mm PSE LONG SENSOR 3 8 1 2 9 5mm 12 7mm GX36 1 L ouverture...

Page 133: ...une cran de protection le nettoyage peut tre n cessaire en raison d un exc s de poussi re peluches des tapis animaux etc utilisez un l attachement du brosse sur aspirateur pour nettoyer l cran 6 Si vo...

Page 134: ...brosse souple et d un aspirateur R installez tous les composants dans l ordre inverse Inspectez le syst me de surpression L appareil dissipe la pression par la porte vitr e ou par les clapets sur le...

Page 135: ...la vitre risque de rester marqu e en permanance Ne touchez pas la surface int rieure ou ext rieur de la vitre avec des lames de rasoir de la laine d acier ou d autres objets m talliques puisque la min...

Page 136: ...remplacement de pi ce sous garantie une photocopie de la facture originale sera requise afin de pouvoir honorer la demande Lorsque vous commandez des pi ces donnez toujours l information suivante Mod...

Page 137: ...0242 SER W010 4006 SER W385 2010 W135 0690 W485 0051 W361 0016 W135 0689 W135 0685 W135 0688 W135 0686 W135 0687 W715 1040 SER Pour les pi ces de remplacement voir l assemblage de la soupape cran de p...

Page 138: ...W290 0029 14 W010 0798 16 W010 0799 15 W750 0112 10 17 16 L assemblage du br leur Injecteur de veilleuse 42 GN Injecteur de veilleuse 53 P Joint d tanch it de soupape Connecteur flexible Soupape GN S...

Page 139: ...248 W190 0176 W750 0267 W350 0702 W750 0294 W335 0039 W455 0070 10 41 15 44 18 4 W500 0276 SER 15 W432 0078 7 9 18 A W240 0013 En stock Oui Oui Oui Oui Oui Oui Oui Oui Oui Oui Oui Oui Oui Oui Assembla...

Page 140: ...nturi pour le r glage de l ouverture du volet d air dans le manual d installation Du carbone se d pose sur la vitre les b ches les roches les composants d coratifs ou les parois de la chambre de combu...

Page 141: ...ni V rifiez si les assemblages de le veilleuse et de la soupape sont bien mis la terre R cepteur si quip R initialisez la programme tenir le bouton de r initialiser sur le r cepteur attendre pour 2 bi...

Page 142: ...se La soupape s teint pendant une minute d ignition et ne fonctionne pas Tension minimale du thermocouple ou r sistance dans le circuit L interrupteur ON OFF t l commande connexions thermocourant ou i...

Page 143: ...LER NE SERREZ PAS TROP FORT V rifiez pour des fuites en appliquant une solution d eau savonneuse Le volet d air est mal r gl Voir la section r glage du venturi pour le r glage de l ouverture du volet...

Page 144: ...ocouple et la connexion la borne de la soupape Remplacez le thermocouple Remplacez la soupape La soupape est d fecteuse Remplacez la soupape La veilleuse br le pas de gaz au br leur principal le bouto...

Page 145: ...p riodes d humidit la condensation des produits chimiques ou produits d entretien nuisibles ne seront pas la responsabilit de Napol on Durant les dix premi res ann es Napol on remplacera ou r parera...

Page 146: ...W415 2354 B 12 09 20 146 FR notes 29 1...

Page 147: ...W415 2354 B 12 09 20 147 notes FR 29 1...

Page 148: ...DE CONFORT 7200 Route Transcanadienne Montr al Qu bec H4T 1A3 24 Napoleon Road Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky USA 41...

Reviews: