VenTing insTallaTion

Continued

10 FOOT RULE

All flue gas outlet chimney terminations must 
extend a minimum of 3 feet in height above the 
highest point where it passes through the roof 
and must be at least 2 feet above the high

-

est point of the roof that is within a horizontal 
distance of 10 feet (see Figure 17).

FINISHING FIREPLACE

Combustible  materials,  such  as  wallboard, 
gypsum board, sheet rock, drywall, plywood, 
etc. may make direct contact with sides and 
top around fireplace face. It is important that 
combustible materials do not overlap the face 
itself. Brick, glass, tile or other noncombustible 
materials may overlap front face provided they 
do not obstruct essential openings like louvered 
slots or any other opening. When overlapping 
with a noncombustible facing material, use only 
noncombustible mortar or adhesive.

24" Min.

24" Min.

18" 

Min.

Typ.

Figure 16 - Multiple Chase Installation

10'

2' Min.

10'

3' Min.

2' Min.

3' Min.

Level of 
Flue Gas 
Outlet

Figure 17 - 10 Foot Rule

Figure 18 - Gas Line Knockout

Side 
Firebrick 
Finished 
Side

Refractory 
Knockout 
Plug

Outside of 

Fireplace

Gas Line 
Conduit
Insulation

Gas 
Conduit 
Cover

1/2" Dowel

Remove 
Knockout

opTional gas line insTallaTion

 CAUTION: Do not seal open-

ings on the rooftop flashing. Fol-

low the installation instructions 

provided  with  the  termination 

being used.

CHASE INSTALLATIONS

Instructions for chase installations are includ

-

ed with chase style termination chosen. In a 
multiple chase installation, be sure to provide 
adequate  distance  between  terminations  to 
prevent smoke spillage from one termination 
to another. We suggest that terminations be 
separated at least 24" center to center and 
stacked at a vertical height difference of 18" 
(see Figure 16).

Note: If a decorative shroud is to be installed, 

contact the manufacturer for specifications.

Gas  line  hook  up  should  be  done  by  your 
supplier or a qualified service person.

Note:  Before  you  proceed,  make  sure  your 

gas supply is turned off.

Use only a 1/2" black iron pipe and appropri

-

ate fittings. 
1.  Remove knockout indentation on refractory 

or  firebrick  wall  located  above  refractory 
hearth floor. The knockout indentation must 
be firmly tapped with any solid object such 
as a 1/2" dowel until it is released. Remove 
fragmented portions of refractory (see Fig

-

ure 18).

Summary of Contents for (V)G36

Page 1: ...ies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted bef...

Page 2: ...omponent part not manu factured or approved by DESA Heat ing LLC in combination with a DESA Heating LLC fireplace system Proper installation is the most important step in ensuring safe and continuous...

Page 3: ...ACH SIDE COMBUSTIBLE WALL BOARD NO COMBUSTIBLE MATERIAL ON FACE MINIMUM 12 TO PERPENDICULAR SIDEWALL HEARTH EXTENSION 74 X 20 1 CHIMNEY AIRSPACE CLEARANCE TO COMBUSTIBLE MATERIAL TERMINATION SQUARE CH...

Page 4: ...et This measurement includes fireplace chimney sections and height of termination assembly at level of the flue gas outlet see Figure 15 page 9 28 25 58 125 67 125 45 25 Figure 1 Framing Dimensions 86...

Page 5: ...e 3 WARNING Hearthextension is to be installed only as shown in Figure 3 Fireplace Installation Continued Figure 3 Hearth Extension Seal Gap Fireplace Front Ember Protector Fireplace Front Raised Hear...

Page 6: ...equired for Wall Installation Air Inlet Eyebrow Vented Crawl Space Check Local Codes Before Installing in a Vented Crawl Space Optional Outside air Kit Model ak4 ak4f Installation of an outside air ki...

Page 7: ...th of double wall pipe see offset chart and Figure 7 2 Chimney weight above offset rests on return elbow Straps must be securely nailed to rafters or joists see Figure 8 details a and b 3 Maximum leng...

Page 8: ...th Attic Space Above Ceiling Existing Ceiling Frame Firestop Spacer Screws or Staples Min of 8 Firestop Spacer Screws or Staples Min of 8 Penetrating the roof To maintain a 1 clearance to the pipe on...

Page 9: ...area and flashing base Secure in position by nailing through shingles see Figure 13 DO NOT NAIL THROUGH FLASHING CONE Figure 14 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Install...

Page 10: ...shed Side Refractory Knockout Plug Outside of Fireplace Gas Line Conduit Insulation Gas Conduit Cover 1 2 Dowel Remove Knockout Optional Gas Line Installation CAUTION Do not seal open ingsontherooftop...

Page 11: ...E FOR LEAK TESTING AND DO NOT OPER ATEANYAPPLIANCE IFALEAK IS DETECTED LEAK TESTING SHOULD BE DONE BYAQUALI FIED SERVICE PERSON Seal Opening with Refractory Cement Outside of Fireplace Gas Line Condui...

Page 12: ...y open doors enough so that you can access spring clips with a phillips screwdriver Tighten screws See Figure 23 Figure 22 Installing Bi Fold Doors Spring Clip Insert Pin into Spring Clip Pivot Hole I...

Page 13: ...rsfullyopenedordoorsfully closed Doors ifleftpartlyopen may draw gas and flame out of the fireplace opening creating risks of both fire and smoke Cleaning Glass Clean glass with any commercial glass c...

Page 14: ...s 116084 02 G36 Models Right Brick Refractory 116082 01 VG36 Models 116082 02 G36 Models Left Brick Refractory 116081 01 VG36 Models 116081 02 G36 Models Rear Brick Refractory 116083 01 VG36 Models 11...

Page 15: ...eady You can also visit DESA Heating LLC s web site at www desatech com Replacement Parts Continued Accessories Bi Fold Glass Door BDG36 36 Black Finish BDG36B 36 Brushed Brass Finish BDG36P 36 Platin...

Page 16: ...2 Pitch SQUARE CHASE TOP TERMINATION STL 12D Round ToP TErminations RLT 12D and RLT 12HT DESA Heating LLC 2701 Industrial Drive Bowling Green KY 42101 www desatech com NOT A UPC 116010 01 Rev E 06 08...

Reviews: