Example:

Gas water heater

_____________ Btu/Hr

Vent-free fireplace

_____________ Btu/Hr

Total

_____________ Btu/Hr

4.

Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.

________ Btu/Hr (maximum the space can support)

________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space
can support)

73,000 Btu/Hr (actual amount of
Btu/Hr used)

The space in the example is a confined space because
the actual Btu/Hr used is more than the maximum
Btu/Hr the space can support. You must provide ad-
ditional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an uncon-
fined space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building.

B. Vent room directly to the outdoors. See Ventila-

tion Air From Outdoors

.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support,  the space is an un-
confined space. You will need no additional fresh
air ventilation.

 WARNING: If the area in

which the heater may be oper-
ated is smaller than that defined
as an unconfined space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 Section
5.3 or applicable local codes

.

40,000
33,000
73,000

AIR FOR COMBUSTION

AND VENTILATION

Continued

Figure 4 - Ventilation Air from Outdoors

Figure 3 - Ventilation Air from Inside

Building

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un-
confined space. When ventilating to an adjoining
unconfined space, you must provide two perma-
nent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting
the two spaces (see options 1 and 2, Figure 3).
You can also remove door into adjoining room (see
option 3, Figure 3). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation
 for required size of
ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills
or ducts. You must provide two permanent open-
ings: one within 12" of the ceiling and one within
12" of the floor. Connect these items directly to
the outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.

IMPORTANT: 

Do not provide openings for inlet

or outlet air into attic if attic has a thermostat-con-
trolled power vent. Heated air entering the attic
will activate the power vent.

Summary of Contents for LMFP33NR

Page 1: ...o not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructi...

Page 2: ...ance may be installed in an aftermarket permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating pla...

Page 3: ...p this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower insert heat exch...

Page 4: ...This fireplace needs fresh air ventilation to run properly This fireplace has an Oxygen Deple tion Sensing ODS safety shutoff system The ODS shuts down the fireplace if enough fresh air is not availab...

Page 5: ...odes in some areas pro hibit the use of vent free heaters SAFETY DEVICE This fireplace has a pilot with an Oxygen Deple tion Sensing ODS safety shutoff system The ODS pilot is a required feature for v...

Page 6: ...g of all appliances installed in that space and an unconfined space as a space whose vol ume is not less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the aggregate input rating of all ap...

Page 7: ...Section 5 3 or applicable local codes 40 000 33 000 73 000 AIR FOR COMBUSTION AND VENTILATION Continued Figure 4 Ventilation Air from Outdoors Figure 3 Ventilation Air from Inside Building Outlet Air...

Page 8: ...top of your fireplace except where standoff spacers are integrally attached If standoff spacers are attached to your fireplace these spacers can be placed directly against wall or framing materials U...

Page 9: ...anging screws 10 x 6 25 shoul der into holes in cabinets Place the assembled trimontofireplacecabinet Alignhangingnotches on trim with hanging screws on side of fireplace see Figure 7 Push trim firmly...

Page 10: ...ocate access hole so cabinet mantel will cover it when installed Note You can secure base to floor using wood screws Countersinkscrewheadsandputtyover 5 Route flexible gas line through access hole in...

Page 11: ...gh opening If installing in a corner use dimensions shown in Figure 14 for the rough opening The height is 33 which is the same as the wall opening above 2 If using blower install duplex outlet to the...

Page 12: ...er the equip ment shutoff valve The flexible gas line must be the last item installed on the gas piping See Installing Gas Piping to Fireplace Loca tion pages 13 and 14 9 Carefully set fireplace in fr...

Page 13: ...ulator WARNING A qualified ser vice person must connect fire place to gas supply Follow all local codes CAUTION Neverconnectpro pane LP fireplace directly to the propane LPsupply Thisfireplace require...

Page 14: ...valve to fireplaces ApplypipejointsealantlightlytomaleNPTthreads This will prevent excess sealant from going into pipe Excess sealant in pipe could result in clogged fireplace valves Never use sealan...

Page 15: ...through one of the access holes NOTICE Most building codes do not permit concealed gas con nections A flexible gas line is provided to allow accessibility fromthefireplace seeFigure22 The flexible gas...

Page 16: ...r gas meter for natural gas or using compressed air 4 Check all joints of gas supply piping system Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 5 Correct all leaks...

Page 17: ...accordance with these diagrams or failure to use only parts specifically approved withthisheatermayresultinprop erty damage or personal injury WARNING After installation and periodically thereafter ch...

Page 18: ...RECEIVER AND HAND HELD REMOTE CONTROL Four AA batteries and threeAAA batteries are re quired to operate this heater with the wireless hand held remote control set Four AA batteries must be installed i...

Page 19: ...nce and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glass doors never operate this heater with glass doors c...

Page 20: ...son or gas supplier for repairs Note If pilot goes out repeat steps 4 through 8 9 Slightly push in and turn control knob coun terclockwise to the ON position OPERATING HEATER Continued AUTO MAN Contro...

Page 21: ...is set press the up or down key to start the timer When the desired time has elapsed the appli ance will automatically switch off Child Safety Lock Out To lock the remote control keys press the On Off...

Page 22: ...st or lint Periodically in spect these holes for any blockage and clean if needed Blocked air holes will create soot MAIN BURNER Periodically inspect all burner flame holes with the fireplace running...

Page 23: ...ressed air in a can please follow the directions on the can If you don t follow directions on the can you could damage the pilot assembly 1 Shut off the unit including the pilot Allow the unit to cool...

Page 24: ...pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo igni...

Page 25: ...ed burner 3 Gas regulator defective 1 Not enough air 2 Gas regulator defective 3 Residues from manufacturing processes and logs curing REMEDY 1 Press in control knob fully 2 AfterODS pilotlights keepc...

Page 26: ...Operate burners until air is re moved from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum installa tion clearances see pages 9 through 13 4 Clean burners see C...

Page 27: ...ile heater is running 2 Refill supply tank propane LP only 3 Locate and correct all leaks see Checking Gas Connec tions page 16 1 Open window and or door for ventilation 2 Contact local natural or pro...

Page 28: ...ill not produce specified heat for propane LP unit propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local gas supplier REPLACEMENT PARTS Note Use only orig...

Page 29: ...maximize heat distribution FIREBOX BRICK LINER G8000A Series Not Shown For all models Ceramic fiber firebox liner adds the look of real brick INFORMATION VIDEO 108917 01 For all models A care and mai...

Page 30: ...www desatech com 111604 01E 30 ILLUSTRATED PARTS BREAKDOWN MODELS LMFP33PR AND LMFP33NR SHOWN 17 26 4 8 12 25 20 21 7 6 4 3 2 1c 1b 1a 5 1d 1e 9 27 14 13 15 16 22 11 10 19 23 18 24 28...

Page 31: ...1 Burner 2 9 M11084 38 M11084 38 Screw 8 16 x 38 4 10 104236 01CK 104236 01CK Painted Base Assy 1 11 M12461 26 M12461 26 Screw 10 32 x 38 4 12 Firebox Bottom 1 13 M50104 02 M50104 02 Bushing 1 14 0982...

Page 32: ...www desatech com 111604 01E 32 ILLUSTRATED PARTS BREAKDOWN FIREBOX LMFP33PR AND LMFP33NR 4 11 14 8 14 9 3 14 9 9 2 1 6 7 10 14 12 5 14 13 16 15...

Page 33: ...ht Front Side 1 4 Left Front Side 1 5 098304 01 Phillips Pan Head Screw 10 16 x 38 9 6 104239 01CK Top Front Louver 1 7 101712 03 Firebox Hood 1 8 Firebox Support 2 9 099230 02 Shoulder Screw 4 10 Fir...

Page 34: ...____________________________________________________ ___________________________________________________________ ___________________________________________________________ ___________________________...

Page 35: ...____________________________________________________ ___________________________________________________________ ___________________________________________________________ ___________________________...

Page 36: ...inal factory replacement parts voids this warranty The heater MUST be installed by a qualified in staller in accordance with all local codes and instructions furnished with the unit This warranty does...

Reviews: