background image

7

4.  Compare the maximum Btu/Hr the space can 

support with the actual amount of Btu/Hr used.

 

 ______________

  Btu/Hr  (maximum  the 

space can support) 

 

 ______________

 Btu/Hr (actual amount of 

Btu/Hr used)

 

Example:

 

  51,200  Btu/Hr  (maximum  the  space  can 

 

support) 

  73,000  Btu/Hr  (actual  amount  of  Btu/Hr 

used)

The space in the above example is a confined 

space because the actual Btu/Hr used is more than 

the maximum Btu/Hr the space can support. You 

must provide additional fresh air. Your options 

are as follows:

A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. 

See 

Ventilation Air From Inside Building

.

B.  Vent room directly to the outdoors. See 

Ven-

tilation Air From Outdoors

.

C.  Install a lower Btu/Hr heater, if lower Btu/Hr size 

makes room unconfined.

  WARNING:  If  the  area  in 

which the heater may be oper

-

ated is smaller than that defined 

as an unconfined space or if the 

building  is  of  unusually  tight 

construction, provide adequate 

combustion and ventilation air 

by one of the methods described 

in the National Fuel Gas Code, 
ANSI Z223.1/NFPA 54 Section 5.3 

or applicable local codes. 

AIR FOR COMbUSTION 

AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining un

-

confined space. When ventilating to an adjoining 

unconfined space, you must provide two perma

-

nent openings: one within 12" of the ceiling and 

one within 12" of the floor on the wall connecting 

the two spaces (see options 1 and 2, Figure 2). You 

can also remove door into adjoining room (see 

option 3, Figure 2). Follow the 

National Fuel Gas 

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for 
Combustion and Ventilation

 for required size of 

ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or 

ducts. You must provide two permanent openings: 

one within 12" of the ceiling and one within 12" 

of the floor. Connect these items directly to the 

outdoors or spaces open to the outdoors. These 

spaces include attics and crawl spaces. Follow the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
Section 5.3, Air for Combustion and Ventilation
 for 

required size of ventilation grills or ducts. 

IMPORTANT: 

Do not provide openings for inlet 

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the attic 

will activate the power vent.

Figure 2 - Ventilation Air from Inside 

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12"

12"

Figure 3 - Ventilation Air from Outdoors

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Summary of Contents for LDL3924NR

Page 1: ...e in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service mu...

Page 2: ...s for installation only in a solid fuel burning mason ry or UL127 factory built fireplace orinalistedvent less firebox enclosure It is design certified for these installationsinaccordance with ANSI Z2...

Page 3: ...anual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower insert heat exchanger in...

Page 4: ...air ventilation to run properly This heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if enough fresh air is not available See Air for Combustion and Ven...

Page 5: ...ystem This heater has a piezo ignitor This system re quires no matches batteries or other sources to light heater Air For Combustion and Ventilation WARNING This heater shall not be installed in a con...

Page 6: ...municating directly with the space in which the appliances are installed through openings not furnished with doors are considered a part of the unconfined space Adjoining rooms are communicating only...

Page 7: ...is fresh air would come from an adjoining un confined space When ventilating to an adjoining unconfined space you must provide two perma nent openings one within 12 of the ceiling and one within 12 of...

Page 8: ...ted on floor or wall of fireplace If not drafting may cause pilot outage or sooting Useaheat resistantsealant Do not seal chimney flue damper WARNING Never install the heater in a bedroom or bathroom...

Page 9: ...minimum clearances If you can provide greater clearances from floor ceiling and adjoin ing wall LOG SIZING REQUIREMENTS Log Size Minimum Firebox Height Depth Front Width Rear Width 24 17 14 28 21 30 1...

Page 10: ...must operate heater with chimney flue damper open Go to Installing Damper Clamp Accessory for Vented Operation page 11 Mantel Clearances In addition to meeting noncombustible material clearances you m...

Page 11: ...PERATION Note When used as a vented heater appliance must be installed only in a solid fuel burning fireplace with a working flue and constructed of noncombustible material You may use this heater as...

Page 12: ...ing not provided Connect approved flexible gas hose to gas control fitting in heater see Figure 11 IMPORTANT Hold gas fitting with wrench when connecting flexible gas hose 2 Locate two masonry screws...

Page 13: ...equipment shutoff valve from your dealer See Accessories page 31 For propane LP units the installer must supply an external regulator The external regulator will reduce incoming gas pressure You must...

Page 14: ...hook up NPT tap must be upstream from heater see Figure 16 IMPORTANT Install equipment shutoff valve in an accessible location The equipment shutoff valve is for turning on or shutting off the gas to...

Page 15: ...ocated on or near gas meter for natural gas or using compressed air 4 Check all joints of gas supply piping system Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 5 C...

Page 16: ...approved withthisheatermayresultinprop erty damage or personal injury CAUTION After installa tion and periodically thereafter check to ensure that no flame comes in contact with any log With the heat...

Page 17: ...ighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settl...

Page 18: ...ill come on automatically within one minute when the control valve is in the ON position after the pilot is lit 1 STOP Read the safety information on page 17 2 Make sure equipment shutoff valve is ful...

Page 19: ...nits will have a slight curve but flame should be blue and have no yellow or orange color Figure 27 Pilot Propane LP Ignitor Electrode Pilot Burner Figure 28 Pilot Natural Ignitor Electrode Pilot Burn...

Page 20: ...lly switch off Child Safety Lock Out To lock the remote control keys press the On Off key then immediately press the up key see Figure 29 The lock out function is active when the lock icon is lit Repe...

Page 21: ...ry from pilots shown Cleaning and Maintenance WARNING Turn off heater and let cool before cleaning CAUTION You must keep control areas burners and circulating air passageways of heater clean Inspect t...

Page 22: ...inlet hole You may blow through a drinking straw if compressed air is not available Burner Tube Pilot Assembly Pilot Air Inlet Hole Ports Slots Burner Tube Injector Holder May Be Brass or Aluminum De...

Page 23: ...pleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor ca...

Page 24: ...d in 30 seconds 3 Wait one minute for safety interlock system to reset Repeat ignition operation 4 Fully open equipment shutoff valve 5 A Contact local natural or propane LP gas company B Clean ODS pi...

Page 25: ...es 9 through 11 4 Clean burners see Cleaning and Maintenance page 21 or replace burner orifice 1 Turn heater off when using furniture polish wax carpet cleaners or similar products 1 Refer to Air for...

Page 26: ...3 ODS pilot is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between con trol valve and burner 2 Gas leak See Warning statement at top o...

Page 27: ...ment Parts Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty Parts Under Warranty Contact authorized dealers of this product If they c...

Page 28: ...Parts Breakdown models LDL3924NR LDL3924PR LDL3930NR and LDL3930PR F F P O 11 28 2 3 25 18 5 19 10 7 7 6 4 20 24 16 14 26 9 23 23 15 16 8 23 23 23 17 21 1 12 13 22 27 1 27 2 27 3 27 4 27 5 27 6 27 7 2...

Page 29: ...rner Retainer Spring 1 20 103784 01 103784 01 103784 01 103784 01 Pilot Knob Extension 1 21 111442 02 111442 02 111442 02 111442 02 Digital Display Remote Control 1 22 111441 02 111441 02 111441 02 11...

Page 30: ...39 000 Type Gas Propane LP Natural Ignition Piezo Piezo Manifold Pressure 8 0 W C 3 5 W C Inlet Gas Pressure in of water Maximum 14 10 5 Minimum 11 5 For purpose of input adjustment Specifications Wi...

Page 31: ...ps deflect heat away from mantel or wall above fireplace Fits openings 28 to 48 wide DAMPER CLAMP GA6080 Not Shown For all models Permanently opens chimney flue damper for vented operation LAVA ROCK G...

Reviews: