background image

5

107435

OWNER’S MANUAL

For more information, visit www.desatech.com

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ____________________ cu. ft. (volume of space)

Example: 

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =  2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_________________ Btu/Hr

Gas water heater*

_________________ Btu/Hr

Gas furnace

_________________ Btu/Hr

Vented gas heater

_________________ Btu/Hr

Gas heater logs

_________________ Btu/Hr

Other gas appliances* +

_________________ Btu/Hr

Total                            =

_________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

 51,200 Btu/Hr (maximum the space can support)

69,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining

room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3 or applicable local codes.

Example:

Gas water heater

30,000

Btu/Hr

Vent-free heater  +

39,000

Btu/Hr

Total                        =

69,000

Btu/Hr

Summary of Contents for Comfort Glow S39PT

Page 1: ...our gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improperinstallation adjustment alteration serv...

Page 2: ...ter screen in place Make sure heater screen is in place before running heater 8 To prevent the creation of soot follow the instructions in Cleaning and Main tenance page 15 9 Before using furniture po...

Page 3: ...ater is designed for vent free opera tion State and local codes in some areas prohibit the use of vent free heaters Figure 1 Vent Free Propane LP Gas Stove UNPACKING 1 Remove top inner pack 2 Tilt car...

Page 4: ...ater shall notbeinstalledinaconfinedspace or unusually tight construction unless provisions are provided foradequatecombustionandven tilation air Read the following in structions to insure proper fres...

Page 5: ...____Btu Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amo...

Page 6: ...ilation grills or ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two per manent openings one within 12 of the ceiling and one within...

Page 7: ...reater clearances from floor ceiling and adjoining side and back walls Carefullyfollowtheinstructionsbelow This stove is a freestanding unit designed to set directly on the floor IMPORTANT You must ma...

Page 8: ...ly INSTALLATION Continued CONNECTING TO GAS SUPPLY WARNING A qualified service personmustconnectheatertogas supply Follow all local codes Installation Items Needed Beforeinstallingheater makesureyouha...

Page 9: ...y Check re connected fittings for leaks CAUTION Make sure exter nal regulator has been installed between propane LP supply and heater SeeguidelinesunderCon necting to Gas Supply page 8 Test Pressures...

Page 10: ...ools required Phillips screwdriver NOTICE Shutoffgasheaterduring the following blower installation 1 Remove 2 screws from rear tabs on top trim Pull trim forward to remove see Figure 12 2 Remove top p...

Page 11: ...rofblowerwheelandthere are no foreign objects in blower wheel 17 Carefully replace stove top panel Align holes and replace six screws removed in step 1 page 10 Slide top trim onto top panel Attach wit...

Page 12: ...s of wire harness into the hole in firebox back panel from front of firebox Pull the ends of the harness to the top of firebox near blower see Figure 20 14 Align holes in the switch cover assem bly wi...

Page 13: ...be lighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavi...

Page 14: ...ermo couple cools the heater will shut down If pilot flame pattern is incorrect as shown in Figure 25 turn heater off see To Turn Off Gas to Appliance seeTroubleshooting pages 16 through 18 Figure 24...

Page 15: ...reeofdust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Yourlocalcomputerstore hardwarestore or home center may carry compressed air in a can You can use a vac...

Page 16: ...ntrol valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is l...

Page 17: ...nute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Observe minimum installation clearances see pages 7 through 9 4 Clean burner see Cleaning...

Page 18: ...er produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion Burner flame is excessively large and is very near or touc...

Page 19: ...t adjustment Baltimore Electric 1348 Dixwell Avenue Hamden CT 06514 0322 1 800 397 7553 203 248 7553 Parts Department Portable Heater Parts 342 N County Rd 400 East Valparaiso IN 46383 9704 All States...

Page 20: ...20 107435 VENT FREE PROPANE LP PEDESTAL STOVE For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN S39PT 6 5 8 4 10 3 2 1 12 13 11 10 9 7...

Page 21: ...age 24 of this manual KEY PART NO NUMBER DESCRIPTION QTY 1 107433 02 Log Set 1 2 104286 01 ODS Pilot LP 1 3 098249 01 ODS Nut 2 4 107090 02 Burner Outlet Tube 1 5 102843 01 Burner Clip 1 6 099056 17 B...

Page 22: ...107435 VENT FREE PROPANE LP PEDESTAL STOVE For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN S39PT 1 10 4 13 3 2 14 7 16 15 11 18 20 5 6 9 8 17 12 23 21 19 19 26 26 22 22 21 25...

Page 23: ...Bottom 1 14 107093 01 Brass Trim Firebox 1 15 105576 01 Knob 1 16 101386 02 Door Hinge 2 17 099230 02 Shoulder Screw 4 18 107079 01CJ Heat Deflector 1 19 102455 12 Louver Small 2 20 102455 13 Louver L...

Page 24: ...t s call DESA International s Parts Department at 1 800 972 7879 for referral information WhencallingDESAInternational haveready model number of your heater the replacement part number ACCESSORIES Pur...

Page 25: ..._________________________________________ _______________________________________________________________________________________________ ______________________________________________________________...

Page 26: ...ts caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE F...

Reviews: