background image

6

107100

VENT-FREE PROPANE/LP HEATER

For more information, visit www.desatech.com

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_____________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. =51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_____________________ Btu/Hr

Gas water heater*

_____________________ Btu/Hr

Gas furnace

_____________________ Btu/Hr

Vented gas heater

_____________________ Btu/Hr

Gas fireplace logs

_____________________ Btu/Hr

Other gas appliances* _____________________ Btu/Hr

Total

_____________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________________ Btu/Hr (maximum the space can support)

_____________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Example:

Gas water heater

30,000

Btu/Hr

Vent-free heater   +

30,000

Btu/Hr

Total                     =

60,000

Btu/Hr

Summary of Contents for Comfort Glow RFP30TA

Page 1: ...stallation and service must be performed by a qualified installer service agency or the gas supplier RFP30TA WARNING Improper installa tion adjustment alteration ser vice or maintenance can cause inju...

Page 2: ...shuts off do not relight until you provide fresh outside air If heater keeps shutting off have it serviced 7 To prevent the creation of soot follow the instructions in Cleaning and Main tenance page 1...

Page 3: ...g o dk irln fg pd fA SD FK IG LF JI als kd idk oe m kg o dk irln fg pd f AS DF KI GL FJ I als kd idk oe m kg o dk irln fg pd fA SD FK IG LF JI als kd idk oe m kg o dk irln fg pd f AS DF KI GL FJ I als...

Page 4: ...te brass front trim in brass trim package 2 Slide the head of two truss head screws from hardware packet into each end of brass front trim see Figure 4 3 Line up screws with holes in front panel see F...

Page 5: ...communicating only iftherearedoorlesspassagewaysorventila tion grills between them PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code NFPA 54 ANS Z223 1 Sec tion5 3...

Page 6: ...of all fuel burning appliances in the space Vent free heater _____________________ Btu Hr Gas water heater _____________________ Btu Hr Gas furnace _____________________ Btu Hr Vented gas heater ____...

Page 7: ...entilation for required size of ventilation grills or ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two per manent openings one with...

Page 8: ...r walls WARNING Never install the heater in a bedroom or a bathroom in a recreational vehicle where curtains furniture clothing or other flammable objects are less than 36 inches from the front top or...

Page 9: ...bracket Marking Screw Locations 1 Tape mounting bracket to wall where heater will be located Make sure mounting bracket is level WARNING Maintainminimum clearances shown in Figure 11 If you can provi...

Page 10: ...Mounting Bracket INSTALLATION Continued Attaching Mounting Bracket to Wall Note Wall anchors mounting screws and spacers are in hardware package The hard ware package is provided with heater Attachin...

Page 11: ...card shipping screws 3 Line up mounting holes on top of hearth base with holes in bottom of heater see Figure 16 4 Using a Phillips screwdriver secure hearth base to heater with four sheet metal screw...

Page 12: ...tects it from freezing rain or sleet We recommend that you install a sediment trap in supply line as shown in Figure 19 Locate sediment trap where it is within reach for cleaning Install in piping sys...

Page 13: ...leak 5 Correct all leaks at once 6 Reconnect heater and equipment shutoff valve to gas supply Check re connected fittings for leaks Open Closed Equipment Shutoff Valve Figure 21 Checking Gas Joints Fi...

Page 14: ...Figure 23 Pilot GRH OV 015 Control Knob Ignitor Button PIL OT L O O F F H I IGNITOR LIGHTING INSTRUCTIONS Ignitor Button Control Knob Figure 22 Control Knob In The OFF Position 7 Keep control knob pre...

Page 15: ...ur own comfort levels THERMOSTAT CONTROL OPERATION MANUAL LIGHTING PROCEDURE Figure 24 Correct Pilot Flame Pattern Figure 25 Incorrect Pilot Flame Pattern Check pilot flame pattern and burner flame pa...

Page 16: ...reatesoot We recommendthatyoucleantheuniteverythree months during operation and have heater in spected yearly by a qualified service person Wealsorecommendthatyoukeeptheburner tube and pilot assembly...

Page 17: ...ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 2 Reconnect ignitor cable 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind base panel 4 Replac...

Page 18: ...nte nance page 16 or replace burner orifice 1 Turn heater off when using furniture polish wax carpet cleaners or similar products OBSERVED PROBLEM Burner does not light after ODS pilot is lit Delayed...

Page 19: ...s off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion Moisture condensationnoticedonwindows REMEDY 1 This is common with most heaters If noise is exce...

Page 20: ...East Valparaiso IN 46383 9704 All States 219 462 7441 1 800 362 6951 sales portableheaterparts com techservice portableheaterparts com FBD 1349 Adams Street Bowling Green KY 42103 3414 270 846 1199 1...

Page 21: ...molding Available in light oak finish walnut finish or an unfin ished hardwood ready to stain or paint Complete assembly and installation instruc tions included ACCESSORIES Purchasetheseheateraccesso...

Page 22: ...7100 VENT FREE PROPANE LP HEATER For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN RFP30TA 1 2 9 10 10 12 13 14 15 17 19 20 23 24 25 6 26 6 7 1 1 3 1 28 5 16 18 4 22 1 1 1 21 11...

Page 23: ...Cable 1 11 098249 01 Nut M5 2 12 107486 01 ODS Pilot Assembly 1 13 103447 01 Burner 1 14 099387 03 3 16 Pilot Tubing 1 15 103845 10 Injector 1 16 NJF 8C Nut Hex 1 17 099415 06 Pressure Regulator 1 18...

Page 24: ...by improper installation Travel diagnostic cost labor transportationandanyandallsuchothercostsrelatedtorepairingadefectiveheaterwillbetheresponsibilityoftheowner TO THE FULL EXTENT ALLOWED BY THE LAW...

Reviews: