UNVENTED PROPANE/LP GAS FIREPLACE

LFP33PRA

AIR FOR
COMBUSTION AND
VENTILATION

Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.

While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

Confined Space and Unconfined
Space

The National Fuel Gas Code, ANS Z223.1
defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000
Btu per hour (4.8 m

3

 per kw) of the aggre-

gate input rating of all appliances installed
in that space and an unconfined space as a
space whose volume is not less than 50
cubic feet per 1,000 Btu per hour (4.8 m

3

 per

kw) of the aggregate input rating of all
appliances installed in that space. Rooms
communicating directly with the space in
which the appliances are installed*, through
openings not furnished with doors, are con-
sidered a part of the unconfined space.

This heater shall not be installed in a con-
fined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

PROVIDING ADEQUATE
VENTILATION

The following are excerpts from National
Fuel Gas Code, NFPA 54/ANS Z223.1, Sec-
tion 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three
following ventilation classifications:

1.

Unusually Tight Construction

2.

Unconfined Space

3.

Confined Space

The information on pages 4 through 6 will
help you classify your space and provide
adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of

PRODUCT
FEATURES

OPERATION

This vent-free fireplace is clean burning. It
requires no outside venting. There is no heat
loss out a vent or up a chimney. Heat is
generated by both realistic flames and glow-
ing embers. When used without the blower,
the fireplace requires no electricity making
it ideal for emergency backup heat.

SAFETY DEVICE

This fireplace has a pilot with an Oxygen
Depletion Sensing (ODS) safety shutoff sys-
tem. The ODS/pilot is a required feature for
vent-free room heaters. The ODS system
shuts off the fireplace if there is not enough
fresh air.

PIEZO IGNITION SYSTEM

This fireplace has a piezo ignitor. This sys-
tem requires no matches, batteries, or other
sources to light fireplace.

BLOWER ASSEMBLY
(GA3750 & GA3650T SERIES)

This fireplace accepts an optional blower
assembly. The GA3750 blower has a manual
variable control. The GA3650T blower
operates thermostatically. The blower
circulates heated air from the fireplace into
the room. Use of blower is optional. See
Accessories,  pages 24 and 25.

 

 WARNING: This heater shall

not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ven-
tilation air. Read the following in-
structions to insure proper fresh
air for this and other fuel-burning
appliances in your home.

unusually tight construction, you must
provide additional fresh air.

Unusually tight construction is de-
fined as construction where:

a.

walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6 x 10

-11 

kg

per pa-sec-m

2

) or less with open-

ings gasketed or sealed 

and

b. weather stripping has been

added on openable windows and
doors 

and

c.

caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See 

Ventilation Air

From Outdoors, page 6.

If your home does not meet all of the
three criteria above, proceed to 

Deter-

mining Fresh-Air Flow for Fireplace
Location on page 5.

Summary of Contents for Comfort Glow LFP33PRA

Page 1: ...justment alteration ser vice ormaintenancecancause injury or property damage Re fer to this manual for correct installationandoperationalpro cedures For assistance or ad ditional information consult a...

Page 2: ...instructions in Cleaning and Main tenance page 18 9 Before using furniture polish wax car pet cleaner or similar products turn heater off If heated the vapors from these products may create a white p...

Page 3: ...top corners of the fireplace screen Remove and discard these screws Lift fireplace screen up and pull out to remove 3 Remove protective packaging applied to logs log base assembly and fireplace 4 Chec...

Page 4: ...Unusually Tight Construction Theairthatleaksarounddoorsandwindows mayprovideenoughfreshairforcombustion and ventilation However in buildings of PRODUCT FEATURES OPERATION This vent free fireplace is...

Page 5: ...____ Btu Hr Do not include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual am...

Page 6: ...rovide two per manent openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors orspacesopentotheoutdoors Thesespaces include attics and crawl s...

Page 7: ...crews two adjust ing plates with set screws and two shims in the hardware packet 3 Align shim under adjusting plate as shown in Figure 5 4 Slide one end of adjusting plate shim in slot on mitered edge...

Page 8: ...earth top to run flexible gas line to fireplace see Figure 8 Make sure to locate access hole so cabi net mantel will cover it when installed Note You can secure base to floor us ing wood screws Counte...

Page 9: ...see Acces sories pages 24 and 25 3 Install gas piping to fireplace location This installation includes an approved flexible gas line if allowed by local codes after the equipment shutoff valve The fl...

Page 10: ...ling fireplace make sure you have the items listed below external regulator supplied by installer piping check local codes sealant resistant to propane LP gas equipment shutoff valve test gauge connec...

Page 11: ...t is resistant to liquid pe troleum LP gas We recommend that you install a sediment trap in supply line as shown in Figure 17 Locate sediment trap where it is within reach for cleaning Install in pipi...

Page 12: ...con nected 3 Pressurize supply piping system by ei ther using compressed air or opening propane LP supply tank valve 4 Check all joints of gas supply piping system Apply mixture of liquid soap and wat...

Page 13: ...ure the front of the middle log is resting on the tabs of the grate base and the cutout area is cen tered over the burner U bend 2 Locate pegs on the bottom of back log 2 Slide these pegs into the hol...

Page 14: ...f re mote control unit following direction of arrow 2 Insert twoAAAbatteries following dia gram in battery housing area 3 Replace battery cover onto remote con trol unit Figure 31 Installing Battery i...

Page 15: ...he battery Place battery into the battery housing 3 Replace battery cover onto remote con trol unit Figure 36 Installing Battery in Hand Held Remote Control Unit Battery Cover 9 Volt Battery Terminal...

Page 16: ...or loss of life FOR YOUR SAFETY READ BEFORE LIGHTING OPERATING FIREPLACE WARNING Burnerswillcome on automatically within one minute when the selector switch is in the ON position after the pilot is li...

Page 17: ...ies pages 24 and 25 Follow instructionsincludedwiththeremotecontrol Figure 38 Pilot Ignitor Electrode Pilot Burner After lighting let pilot flame burn for about one minute Turn control knob to ON posi...

Page 18: ...cool Either remove blockage or replace burner Blocked burner flame holes will create soot CLEANING BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE The primary air inlet holes allow the proper amount...

Page 19: ...ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind base panel 4 Replace ign...

Page 20: ...irements page 4 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Observe minimum...

Page 21: ...statement above 1 Improper log placement 2 Drafts or other air currents affecting flame pattern 3 Air holes at burner inlet blocked 4 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces a c...

Page 22: ...ay be low When Gas Quality Is Bad pilot will not stay lit burners will produce flames and soot heater will backfire when lit Youmayfeelyourgaspressureistoolowor gas quality is bad If so contact your l...

Page 23: ...514 0322 1 800 397 7553 203 248 7553 Parts Department Portable Heater Parts 342 N County Rd 400 East Valparaiso IN 46383 9704 All States 219 462 7441 1 800 362 6951 sales portableheaterparts com techs...

Page 24: ...ERIMETER BRASS TRIM Not Shown GMC36F Series Walnut Finished Birch Veneer GMC37U Series Unfinished Birch Veneer Ready to Stain or Paint Space saving corner mantels feature mold ings fluting and medalli...

Page 25: ...erated in a manually or thermostatically controlled mode Youcanturnthegaslogheateronand off without ever leaving the comfort of your easy chair BRASS TRIM ACCESSORY GA7090 Not Shown Optional with buil...

Page 26: ...NVENTED PROPANE LP GAS FIREPLACE LFP33PRA ILLUSTRATED PARTS BREAKDOWN REMOTE READY MODEL LFP33PRA 20 30 O F F P I L O T O N H I L O 11 15 29 10 9 7 6 5 1 2 4 3 8 12 7 17 16 28 18 19 24 14 13 19 23 22...

Page 27: ...rner Orifice Injector 1 11 102772 01 Burner 2 12 M11084 38 Screw 8 x 38 2 13 104236 01CK Painted Base Assy 1 14 M12461 26 Screw 10 x 32 4 15 104238 01CK Firebox Bottom 1 16 103284 03 Wiring Harness 1...

Page 28: ...28 107064 UNVENTED PROPANE LP GAS FIREPLACE LFP33PRA 1 2 3 4 15 10 11 9 18 6 17 12 16 16 16 7 8 16 16 5 14 16 13 13 13 ILLUSTRATED PARTS BREAKDOWN FIREPLACE LFP33PRA...

Page 29: ...K Cover 1 6 101784 01 Snap in Magnet 2 7 103411 01CK Louver Hood 1 8 101838 03CK Firebox Wrapper 1 9 103412 01CK Louver Door 1 10 101727 02 Screen Assembly 1 11 101348 01 Firebox Support 2 12 103207 0...

Page 30: ...elated to repairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL...

Reviews: