OWNER’S MANUAL

 WARNING: Read all instruc-

tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property damage
or loss of life. Operation of im-
properly installed and maintained
venting system could result in
serious injury, property damage
or loss of life.

 WARNING: Seal all vent con-

nections. Seal only the outer pipe
connections with high temperature
silicone (600

°

F/316

°

 C). Before join-

ing elbows and pipes, apply a bead
of high temperature silicone seal-
ant (GE RTV 106/Loctite RTV 81585)
to the male end of the elbow or
pipe. High temperature silicone
must also be used to re-seal any
connections after maintenance to
venting system.

NOTICE: Failure to follow these
instructions will void the warranty.

INSTALLATION
PRECAUTIONS

Consult local building codes before beginning
the installation. The installer must make sure
to select the proper vent system for installa-
tion. Before installing vent kit, the installer
must read this fireplace manual and vent kit
instructions.

Only a qualified service person should in-
stall venting system. The installer must fol-
low these safety rules:

• Wear gloves and safety glasses for

protection

• Use extreme caution when using ladders

or when on roof tops

• Be aware of electrical wiring locations

in walls and ceilings

The following actions will void the war-
ranty on your venting system:

• Installation of any damaged venting

component

• Unauthorized modification of the vent-

ing system

VENTING
INSTALLATION

 WARNING: This gas fireplace

and vent assembly must be
vented directly to the outside.
The venting system must NEVER
be attached to a chimney serving
a separate solid fuel burning ap-
pliance. Each gas appliance must
use a separate vent system. Do
not use common vent systems.

 WARNING: Horizontal sec-

tions of this vent system require
a minimum clearance of 2" from
the top of the pipe and 1" mini-
mum to the sides and bottom.
Vertical sections of this system
require a minimum of 1" clear-
ance to combustible materials on
all sides of the pipe.

• Installation of any component part not

manufactured or approved by DESA
International

• Installation other than as instructed by

these instructions

INSTALLATION PLANNING

There are two basic types of direct-vent
installation:

• Horizontal Termination

• Vertical Termination

It is important to select the proper length of
vent pipe for the type of termination you
choose. It is also important to note the wall
thickness.

For Horizontal Termination:

 Select the

amount of vertical rise desired. The horizon-
tal run of venting must have 1/4" rise for
every 12" of run towards the termination.

NOTICE: Treatment of firestops
and construction of the chase
may vary from building type to
building type. These instructions
are not substitutes for the re-
quirements of local building
codes. You must follow all local
building codes .

Note:

 When installing in a chase, you should

insulate the chase as you would the outside
walls of your home. This is especially im-
portant in cold climates. Minimum clear-
ance between vent pipes and combustible
materials such as insulation is 1".

After framing the chase (see Framing and
Finishing
 on page 4) install the vent system
by following the installation instructions.

Installing Vent System in a Chase

A chase is a vertical box-like structure built
to enclose venting that runs along the out-
side of a building. A chase is not required for
such venting.

Continued

 WARNING: Never run the vent

downward as this may cause ex-
cessive temperatures which
could cause a fire.

You may use one or two 90

°

 elbows in this

vent configuration. See Horizontal Termina-
tion Configurations
 on pages 10 and 11.

For Vertical Termination:

 Measure the dis-

tance from the fireplace flue outlet to the
ceiling. Add the ceiling thickness, the verti-
cal rise in an attic or second story, and allow
for sufficient vent height above the roofline.

You may use one or two 90

°

 elbows in this

vent configuration. See Vertical Termination
Configurations
 on pages 13 and 14.

Note:

 You may use two 45

°

 elbows in place

of a 90

°

 elbow. You must follow rise to run

ratios when using 45

°

 elbows.

For two-story applications, firestops are re-
quired at each floor level. If an offset is
needed in the attic, additional pipe and el-
bows will be required.

You may use a chase with a vent termination
with exposed pipe on the exterior of the
house. See Installing Vent System in a Chase,
below.

Your Comfort Glow direct-vent fireplace
has been tested for a minimum 3' rise with a
maximum 10" wall thickness. The maxi-
mum horizontal run is 20' with 8' vertical
rise (see Installation for Horizontal Termi-
nation
, page 8). The maximum vertical run
is 30' (see Installation for Vertical Termina-
tion
, page 12).

It is very important that the venting system
maintain its balance between the combus-
tion air intake and the flue gas exhaust.
Certain limitations apply to vent configura-
tions and must be strictly followed.

Summary of Contents for Comfort Glow CHDV37N

Page 1: ...itional information consult a qualified installer service agency or the gas supplier Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING If the information in this m...

Page 2: ...indicated on fire place nameplate 14 This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electri cal Code ANS...

Page 3: ...a piezo ignitor This sys tem requires no matches batteries or other sources to light fireplace Figure 1 Comfort Glow Direct Vent Fireplace HDV Series Glass Door Assembly Blower Adjustment Optional In...

Page 4: ...tain a minimum 1 clearance to combustibles 37 1 2 41 1 2 34 3 4 20 Vertical Termination 19 Horizontal Termination Note Where two numbers are given the top number is exclusive to the 37 Fireplace and t...

Page 5: ...delines OnlyuseComfortGloworSimpsonDura Vent GS venting components or kits spe cifically approved for this fireplace Minimum clearance between vent pipes and combustible materials is 1 25 mm except wh...

Page 6: ...above paved side walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minim...

Page 7: ...r length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount of vertical rise desired The horizon tal run o...

Page 8: ...ion of pipe and el bows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have four locking lugs indentations T...

Page 9: ...p Position the vent cap in the center of the 7 1 2 or 10 hole on the exterior wall with the arrow on the vent cap pointing up Insure proper clearance of 1 to combustibles is maintained At tach the ven...

Page 10: ...figuration for use with corner installation Horizontal Venting See information in Figure 17 for Vertical V and Horizontal H maximums and minimums The same amounts apply for flexible venting Note Figur...

Page 11: ...x 8 min 8 min 20 max 20 max 8 max 20 max Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max 20 max 20 max Figure 19 Horizontal Termina...

Page 12: ...g members Note Pay spe cial attention to these installation in structions for required clearances air space to combustibles when passing through ceilings walls roofs enclo sures attic rafters etc Do n...

Page 13: ...e Figure 23 Align the support box vertically and horizontally using a level Temporarily tack the support box in place through the inside walls and into the roof sheathing 4 Using tin snips cut the sup...

Page 14: ...Vertical Rigid Venting Configuration With No Horizontal Run VENTING INSTALLATION Continued Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note V...

Page 15: ...2 Firestop Support Roof Flashing RTV Silicone Vertical Termination and 26 screws CD1000 7 x 12 Galvanized Coaxial Pipe Qty 1 CD1010 7 x 24 Galvanized Coaxial Pipe Qty 1 CD1020 7 x 48 Galvanized Coaxia...

Page 16: ...ating system you may run system scirculatingblowerwhile using heater This will help circu late the heat throughout the house In the event of a power outage you can use this heater as your primary heat...

Page 17: ...port bracket if exiting through the right side see Figure 33 Route power cord through both plastic bushing s and plug the power cord into a properly grounded 3 prong wall receptacle near the firebox...

Page 18: ...lator with the vent pointing down as shown in Figure 34 Pointing the vent down protects it from freezing rain or sleet WARNING A qualified ser vice person must connect fire place to gas supply Follow...

Page 19: ...rough one of the access holes on side of fireplace 3 Attach a 45 flare union gas connector to flexible gas line from gas supply see Figure 36 Connect flare union to flex ible gas line attached to gas...

Page 20: ...l shutoff valve see Fig ure 37 2 Open propane LP supply tank valve for propane LP fireplace or main gas valve located on or near gas meter for natu ral gas fireplace 3 Make sure control knob of firepl...

Page 21: ...ire hazard will occur 7 Connect one bare wire end to each ter minal W and R of the thermostat base see Figure 42 8 Install the base to the wall with screws provided with thermostat 9 Move the temperat...

Page 22: ...y both sides and ease it upward off of the lower bracket see Figure 46 4 To replace glass door follow the above instructions in reverse Figure 46 Removing Replacing Glass Door Figure 45 Removing Top L...

Page 23: ...brackets to grate Brackets are adjustable left to right to allow proper placement of panel These will hold rear panel in place while installing side panels 5 Install left side brick panel by sliding...

Page 24: ...der burner Placing lava rock on burner could cause performance problems It is not necessary to use all of the lava rock provided Each log is marked with a number These numberswillhelpyouidentifythelog...

Page 25: ...wise to PILOT 9 Push in gas control knob all the way and hold Immediately light the pi lot by repeatedly depressing the piezo spark ignitor until a flame appears Continue to hold for about one 1 minu...

Page 26: ...omfort level you select The ideal comfort setting will vary byhouseholddependingupontheamount of space to be heated the output of the central heating system etc 1 After lighting let pilot flame burn f...

Page 27: ...r leveling Upon installation the thermostat must be allowed to stabilize at room tempera ture for a minimum of 30 minutes for proper operation To turn the fireplace off adjust thermo stat to the lowes...

Page 28: ...corrosion of caps pipes and fittings and can be caused by having excessive lateral runs too many el bows or exterior portions of the sys tem being exposed to cold weather 4 Inspect joints to verify t...

Page 29: ...ose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holdin...

Page 30: ...urner until air is removed from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Mainte nance page 28 or replace burner orifice 1 Adjust the log s...

Page 31: ...2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas od...

Page 32: ...hen servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor...

Page 33: ...WITH SQUARE LEG STYLING UNFINISHED GMC511U 37 GMC513U 41 For use with all models This oak veneer mantel is unfinished and ready to stain or paint Complete assembly instructions are in cluded along wi...

Page 34: ...P REMOTE OFF ON 28 5 44 1 2 3 4 5 6 5 5 7 7 8 9 10 11 Included in Hardware Pack 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 29 30 31 6 6 38 32 33 34 35 59 36 33 37 39 2 39 3 39 1 42 43 45 48 47 46...

Page 35: ...01 Rear Burner Natural 41 1 27 104488 03 Burner Manifold 1 28 104489 01 Burner Gasket 1 29 104506 04 Orifice 1 30 104506 08 Orifice 37 1 104506 11 Orifice 41 1 31 104507 01 Brass Elbow 1 32 104574 01...

Page 36: ...P REMOTE OFF ON 28 5 44 1 2 3 4 5 6 5 5 7 7 8 9 10 11 Included in Hardware Pack 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 29 30 31 6 6 38 32 33 34 35 59 36 33 37 39 2 39 3 39 1 42 43 45 48 47 46...

Page 37: ...104574 01 Brass Elbow 1 33 104508 01 Brass Fitting 3 34 104608 02 Aluminum Tubing Assy 37 1 104608 01 Aluminum Tubing Assy 41 1 PARTS LIST DIRECT VENT FIREPLACE CHDV37P AND CHDV41P This list contains...

Page 38: ...pairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRES...

Reviews: