DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)

CHDV37N/P AND CHDV41N/P

PILOT AND BURNERS

• Remove ember material before cleaning

burners and replace when cleaning is
complete.

• Burner and controls should be cleaned

with compressed air to remove dust, dirt,
or lint.

• Use a vacuum cleaner or small, soft

bristled brush to remove excess dust, dirt,
or lint.

LOGS

• If you remove logs for cleaning, refer to

Installing Logs, Lava Rock, and Glowing
Embers
, page 24, to properly replace logs.

• Use a vacuum cleaner to remove any car-

bon build-up on logs.

• Replace log(s) if broken. See Replace-

ment Parts on page 32.

• Replace ember material periodically as

needed. See Replacement Parts on page 32.

 WARNING: Only parts sup-

plied by the manufacturer should
be used when replacing broken
or damaged glass door panel (see
Replacement Parts, page 32). This
glass door panel is a complete
unit. No substitute materials may
be used.

CLEANING AND
MAINTENANCE

If glass has been broken, carefully remove
glass door (see Removing/Replacing Glass
Door,  
page 22). Vacuum all glass pieces
with a shop vac.

 CAUTION: Wear gloves and

safety glasses while handling or
removing broken glass. Do not
remove if glass is hot. Keep chil-
dren and pets away from glass.

 WARNING: Do not operate

fireplace with the glass door re-
moved, cracked, or broken.

VENTING SYSTEM

Conduct annual inspection of the venting
system following these guidelines:
1.

Check areas of venting system that are
exposed to the weather for corrosion (rust
spots or streaks and, in extreme cases,
holes). Have these items replaced imme-
diately by a qualified service person.

2.

Remove the vent cap and shine a flash-
light into the vent. Remove any foreign
material.

3.

Check for evidence of excessive con-
densation. Continuous condensation
can cause corrosion of caps, pipes, and
fittings and can be caused by having
excessive lateral runs, too many el-
bows, or exterior portions of the sys-
tem being exposed to cold weather.

4.

Inspect joints to verify that no pipe sec-
tion or fitting has been disturbed and
loosened. Check mechanical supports
such as wall straps for rigidity.

 WARNING: Turn off fireplace

and let cool before cleaning.

 CAUTION: You must keep con-

trol areas, burners, and circulat-
ing air passageways of fireplace
clean. Inspect these areas of fire-
place before each use. Have fire-
place inspected yearly by a quali-
fied service person. Fireplace may
need more frequent cleaning due
to excessive lint from carpeting,
bedding material, pet hair, etc.

 WARNING: Do not use abra-

sive cleaners as this may damage
glass. Use a non-abrasive house-
hold glass cleaner to clean glass.
Do not clean glass when hot.

  WARNING: Handle glass door

panel with care. Do not strike,
slam, or otherwise abuse glass.
Do not operate fireplace with the
glass door removed, cracked, or
broken.

GLASS DOOR

Glass must be cleaned periodically. During
start-up it is normal for condensation to
form on the inside of the glass causing lint,
dust, and other airborne particles to cling to
the glass surface. During initial start-up a
slight film may form on the glass due to
paint curing. The glass should be cleaned
several times with a non-amonia, non-
abrasive household cleaner and warm water
after the first two weeks of operation. There-
after, clean the glass two or three times
during each heating season, depending on
the usage and circumstances present. Refer
to Removing/Replacing Glass Door on page
22 of this manual when removing glass door
for cleaning.

Use only the ceramic glass door replace-
ment intended for this fireplace (see Re-
placement Parts
, page 32 for detail on or-
dering). No substitutions may be made. See
Removing/Replacing Glass Door, page 22
for instructions for replacing glass door.

 CAUTION: Do not vacuum if

pieces are hot.

Summary of Contents for Comfort Glow CHDV37N

Page 1: ...itional information consult a qualified installer service agency or the gas supplier Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING If the information in this m...

Page 2: ...indicated on fire place nameplate 14 This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electri cal Code ANS...

Page 3: ...a piezo ignitor This sys tem requires no matches batteries or other sources to light fireplace Figure 1 Comfort Glow Direct Vent Fireplace HDV Series Glass Door Assembly Blower Adjustment Optional In...

Page 4: ...tain a minimum 1 clearance to combustibles 37 1 2 41 1 2 34 3 4 20 Vertical Termination 19 Horizontal Termination Note Where two numbers are given the top number is exclusive to the 37 Fireplace and t...

Page 5: ...delines OnlyuseComfortGloworSimpsonDura Vent GS venting components or kits spe cifically approved for this fireplace Minimum clearance between vent pipes and combustible materials is 1 25 mm except wh...

Page 6: ...above paved side walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minim...

Page 7: ...r length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount of vertical rise desired The horizon tal run o...

Page 8: ...ion of pipe and el bows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have four locking lugs indentations T...

Page 9: ...p Position the vent cap in the center of the 7 1 2 or 10 hole on the exterior wall with the arrow on the vent cap pointing up Insure proper clearance of 1 to combustibles is maintained At tach the ven...

Page 10: ...figuration for use with corner installation Horizontal Venting See information in Figure 17 for Vertical V and Horizontal H maximums and minimums The same amounts apply for flexible venting Note Figur...

Page 11: ...x 8 min 8 min 20 max 20 max 8 max 20 max Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max 20 max 20 max Figure 19 Horizontal Termina...

Page 12: ...g members Note Pay spe cial attention to these installation in structions for required clearances air space to combustibles when passing through ceilings walls roofs enclo sures attic rafters etc Do n...

Page 13: ...e Figure 23 Align the support box vertically and horizontally using a level Temporarily tack the support box in place through the inside walls and into the roof sheathing 4 Using tin snips cut the sup...

Page 14: ...Vertical Rigid Venting Configuration With No Horizontal Run VENTING INSTALLATION Continued Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note V...

Page 15: ...2 Firestop Support Roof Flashing RTV Silicone Vertical Termination and 26 screws CD1000 7 x 12 Galvanized Coaxial Pipe Qty 1 CD1010 7 x 24 Galvanized Coaxial Pipe Qty 1 CD1020 7 x 48 Galvanized Coaxia...

Page 16: ...ating system you may run system scirculatingblowerwhile using heater This will help circu late the heat throughout the house In the event of a power outage you can use this heater as your primary heat...

Page 17: ...port bracket if exiting through the right side see Figure 33 Route power cord through both plastic bushing s and plug the power cord into a properly grounded 3 prong wall receptacle near the firebox...

Page 18: ...lator with the vent pointing down as shown in Figure 34 Pointing the vent down protects it from freezing rain or sleet WARNING A qualified ser vice person must connect fire place to gas supply Follow...

Page 19: ...rough one of the access holes on side of fireplace 3 Attach a 45 flare union gas connector to flexible gas line from gas supply see Figure 36 Connect flare union to flex ible gas line attached to gas...

Page 20: ...l shutoff valve see Fig ure 37 2 Open propane LP supply tank valve for propane LP fireplace or main gas valve located on or near gas meter for natu ral gas fireplace 3 Make sure control knob of firepl...

Page 21: ...ire hazard will occur 7 Connect one bare wire end to each ter minal W and R of the thermostat base see Figure 42 8 Install the base to the wall with screws provided with thermostat 9 Move the temperat...

Page 22: ...y both sides and ease it upward off of the lower bracket see Figure 46 4 To replace glass door follow the above instructions in reverse Figure 46 Removing Replacing Glass Door Figure 45 Removing Top L...

Page 23: ...brackets to grate Brackets are adjustable left to right to allow proper placement of panel These will hold rear panel in place while installing side panels 5 Install left side brick panel by sliding...

Page 24: ...der burner Placing lava rock on burner could cause performance problems It is not necessary to use all of the lava rock provided Each log is marked with a number These numberswillhelpyouidentifythelog...

Page 25: ...wise to PILOT 9 Push in gas control knob all the way and hold Immediately light the pi lot by repeatedly depressing the piezo spark ignitor until a flame appears Continue to hold for about one 1 minu...

Page 26: ...omfort level you select The ideal comfort setting will vary byhouseholddependingupontheamount of space to be heated the output of the central heating system etc 1 After lighting let pilot flame burn f...

Page 27: ...r leveling Upon installation the thermostat must be allowed to stabilize at room tempera ture for a minimum of 30 minutes for proper operation To turn the fireplace off adjust thermo stat to the lowes...

Page 28: ...corrosion of caps pipes and fittings and can be caused by having excessive lateral runs too many el bows or exterior portions of the sys tem being exposed to cold weather 4 Inspect joints to verify t...

Page 29: ...ose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holdin...

Page 30: ...urner until air is removed from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Mainte nance page 28 or replace burner orifice 1 Adjust the log s...

Page 31: ...2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas od...

Page 32: ...hen servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor...

Page 33: ...WITH SQUARE LEG STYLING UNFINISHED GMC511U 37 GMC513U 41 For use with all models This oak veneer mantel is unfinished and ready to stain or paint Complete assembly instructions are in cluded along wi...

Page 34: ...P REMOTE OFF ON 28 5 44 1 2 3 4 5 6 5 5 7 7 8 9 10 11 Included in Hardware Pack 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 29 30 31 6 6 38 32 33 34 35 59 36 33 37 39 2 39 3 39 1 42 43 45 48 47 46...

Page 35: ...01 Rear Burner Natural 41 1 27 104488 03 Burner Manifold 1 28 104489 01 Burner Gasket 1 29 104506 04 Orifice 1 30 104506 08 Orifice 37 1 104506 11 Orifice 41 1 31 104507 01 Brass Elbow 1 32 104574 01...

Page 36: ...P REMOTE OFF ON 28 5 44 1 2 3 4 5 6 5 5 7 7 8 9 10 11 Included in Hardware Pack 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 29 30 31 6 6 38 32 33 34 35 59 36 33 37 39 2 39 3 39 1 42 43 45 48 47 46...

Page 37: ...104574 01 Brass Elbow 1 33 104508 01 Brass Fitting 3 34 104608 02 Aluminum Tubing Assy 37 1 104608 01 Aluminum Tubing Assy 41 1 PARTS LIST DIRECT VENT FIREPLACE CHDV37P AND CHDV41P This list contains...

Page 38: ...pairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRES...

Reviews: