10
102393
PROPANE/LP GAS HEATER
BLUE FLAME 10,000 BTU
TO TURN OFF GAS
TO APPLIANCE
1.
Remove front panel (see Figure 10,
page 7).
2.
Follow steps 1 through 5 under Light-
ing Instructions.
3.
With control knob pressed in, strike
match. Hold match to pilot until pi-
lot lights.
4.
Keep control knob pressed in for 30
seconds after lighting pilot. After 30
seconds, release control knob.
5.
Replace front panel.
OPERATING
HEATER
Continued
4.
Wait five (5) minutes to clear out any
gas. Then smell for gas, including
near the floor. If you smell gas,
STOP! Follow “B” in the safety in-
formation at the top of column 3,
page 9. If you don’t smell gas, go to
the next step.
5.
Turn control knob counterclockwise
C-clockwise
to the PILOT position.
Press in control knob for five (5) sec-
onds (see Figure 16).
Note:
You may be running this
heater for the first time after hook-
ing up to gas supply. If so, the con-
trol knob may need to be pressed in
for 30 seconds. This will allow air to
bleed from the gas system.
• If control knob does not pop up
when released, contact a qualified
service person or gas supplier for
repairs.
6.
With control knob pressed in, push
down and release ignitor button. This
will light pilot. The pilot is attached
to the front of burner. The pilot can
be seen through the glass panel. If
needed, keep pressing ignitor button
until pilot lights.
CAUTION: Do not try to adjust
heating levels by using the
manual shutoff valve.
Pilot Burner
Figure 17 - Pilot
Ignitor Electrode
Thermocouple
IGNITOR
PILOT
LO
OFF
HI
Control Knob
Figure 16 - Control Knob In The OFF
Position
Ignitor Button
LIGHTING
INSTRUCTIONS
1.
STOP! Read the safety information
column 3, page 9.
2.
Make sure manual shutoff valve is
fully open.
3.
Turn control knob clockwise
Clockwise
to the OFF position.
Note:
If pilot does not stay lit, refer
to Troubleshooting, pages 12 through
14. Also contact a qualified service
person or gas supplier for repairs.
Until repairs are made, light pilot
with match. To light pilot with match,
see Manual Lighting Procedure.
7.
Keep control knob pressed in for 30
seconds after lighting pilot. After 30
seconds, release control knob.
• If control knob does not pop up
when released, contact a qualified
service person or gas supplier for
repairs.
Note:
If pilot goes out, repeat steps
3 through 7. This heater has a safety
interlock system. Wait one (1) minute
before lighting pilot again.
8.
Turn control knob counterclockwise
C-clockwise
to desired heating level. The
main burner should light. Set control
knob to any heat level between HI
and LO.
Shutting Off Heater
1.
Turn control knob clockwise
Clockwise
to the OFF position.
2.
Turn off all electric power to the ap-
pliance if service is to be performed.
Shutting Off Burner Only (pilot
stays lit)
1.
Turn control knob clockwise
Clockwise
to the PILOT position.
THERMOSTAT
CONTROL
OPERATION
The thermostatic control used on these mod-
els differs from standard thermostats. Stan-
dard thermostats simply turn on and off the
burner. The thermostat used on this heater
senses the room temperature. The thermo-
stat adjusts the amount of gas flow to the
burner. This increases or decreases the burner
flame height. At times the room may exceed
the set temperature. If so, the burner will
shut off. The burner will cycle back on when
room temperature drops below the set tem-
perature. The control knob can be set to any
heat level between HI and LO. Selecting the
HI setting will cause the burner to remain
fully on without modulating down in most
cases.
Note:
The thermostat sensing bulb mea-
sures the temperature of air near the heater
cabinet. This may not always agree with
room temperature (depending on housing
construction, installation location, room size,
open air temperatures, etc.). Frequent use of
your heater will let you determine your own
comfort levels.
MANUAL LIGHTING
PROCEDURE