background image

                                                                                                       - 6 -                                           

For more information, visit www.desatech.com

 

If the adapter is needed, secure it onto the firestop using holes 
provided (see figure 10).  The row of holes on the sides of the 
thimble is provided to allow for pitch variances.  Position the 
firestop assembly and thimble to desired angle and secure with 
screws provided.  Insert the thimble and firestop into the 
prepared opening and secure to the ceiling by nailing through 
the firestop flanges.  The thimble should be even with or 
above the roofline.  Thimble extensions are available (as an 
option) when required.  See “accessories” on page 12. 

NOTE: If there is a second story in the home, firestop 
spacer V3600FS-8DM will be required.  See “Firestop 
Spacer”. 

INSTRUCTIONS WHEN ELBOW OFFSET (30E-8DM) 

OF CHIMNEY IS NEEDED 

TO INSTALL ELBOWS 
1.  To achieve desired offset, you may install combinations of                                                                             
12”, 18”, 24”, 36” and 48” length of double wall pipe (SEE 
SINGLE OFFSET CHARTAND FIGURE 12). 

OFFSET CHART  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
2.  Chimney  weight  above  offset  rests  on  return  elbow.              
Straps must be securely nailed to rafters or joists (see figure 
12, details a & b). 
3.  Maximum length of pipe between supports (return elbow or 
12S-8DM) is 2’ of angle run. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

FIRESTOP SPACERS (V3600FS-8DM) 

Firestop spacers are required at each point where the chimney 
penetrates a floor space.  Their purpose is to establish and 
maintain the required clearance between the chimney and the 
combustible materials.  When the pipe passes through a 
framed opening into a living space above, the firestop must be 
placed onto the ceiling from below as shown in figure 13.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

PENETRATING THE ROOF 

 
To maintain a 1-inch clearance to the pipe on a roof with a 
pitch, a rectangular opening must be cut. 

STEP 1:

 Determine the center point through which the pipe 

will penetrate the roof. 

STEP 2:

  Determine the center point of the roof.  Pitch is the 

distance the roof drops over a given span, usually 12 inches.  
A 6/12 pitch means that the roof drops 6 inches for each 12 
inches one measure horizontally down from the roof rafters. 

STEP 3:

  Use the roof opening chart (figure 14) to determine 

the correct opening length and flashing required. 

STEP 4:

  Remove the shingles around the opening measured 

and cut out this section. 

STEP 5:

  Add the next sections of the pipe until the end 

penetrates the roofline.  Check to see that the proper 
clearances are maintained.  Extend chimney by adding 
sections of double wall pipe until pipe is a minimum of 30 
inches above the highest point of the roof cutout.  Termination 
and chimney must extend a minimum of 36 inches above the 
highest point where it passes through roof. 

OFFSET

RISE

A

B

48"

36"

24"

18"

12"

4 - 3/8

16 -3/8

9 - 3/4

25 - 1/2

1

12 - 3/4

30 - 3/4

1

15

34 - 3/4

1

18

40

1

1

21 - 1/4

46 - 1/4

1

23 - 3/4

49 - 1/4

1

1

27 - 3/4

56 - 3/4

1

30

60 - 3/4

1

1

33

66 1

1

36

71

1

1

38 - 1/4

75

2

41 - 1/4

80 - 1/4

1

1

1

45

86 - 3/4

2

46 - 3/4

89 - 1/2

1

1

1

51

97

1

1

53 - 1/4

101

2

1

56 - 1/4

106 - 1/4

2

59 - 1/4

111 - 1/2

1

1

1

61 - 3/4

115 - 1/2

2

1

64 - 3/4

120 - 3/4

2

1

68 - 1/4

127

1

2

70

130

2

1

1

74 - 1/4

137 - 1/2

1

2

1

76 - 3/4

141 - 1/2

1

2

1

79 - 3/4

146 - 3/4

4

ELBOW  SET ONLY

CHIMNEY LENGTH

 

Figure 11         CEILING SUPPORT PIPE 

 

Figure 12                 ELBOW OFFSET 

All joints (where two pipes are
joined) should be secured with
two screws, only on the outer
pipe, and shall not penetrate
the inner stainless. 

Figure 13               FIRESTOP SPACER 

Summary of Contents for C36EMW

Page 1: ...proved to ANS Z21 60 Z21 84 or RGA 2 72 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard A DESA hood must be installed when using a vent free gas log heater see A...

Page 2: ...ION PG 4 7 FAN KIT ASSEMBLY PG 4 8 CHIMNEY PIPE PG 4 5 9 FIRESTOP THIMBLE AND SPACERS PG 5 6 10 FLASHING AND TERMINATION PG 7 11 FINISHING YOUR FIREPLACE PG 8 12 MANTEL PG 8 13 GLASS DOORS PG 8 14 GAS...

Page 3: ...lace to the flue gas outlet of the termination is 11 5 feet for straight flue or a flue with one elbow set The maximum distance between elbows is 2 feet For systems with 2 elbow sets minimum height is...

Page 4: ...N A hearth extension projecting a minimum of 16 in front of and a minimum of 8 beyond each side of the fireplace opening is required to protect combustible floor construction in front of the fireplace...

Page 5: ...gh the strain relief opening and electrical cover plate and make all the necessary connections iv Slide all wiring connections in the electrical housing as shown in figure 6b v Secure the electrical c...

Page 6: ...c space of a manufactured home To install the thimble assembly determine the distance between the ceiling joist and the roof framing Attach the adjustable thimble to the firestop spacer so that the as...

Page 7: ...n in figure 13 PENETRATING THE ROOF To maintain a 1 inch clearance to the pipe on a roof with a pitch a rectangular opening must be cut STEP 1 Determine the center point through which the pipe will pe...

Page 8: ...ly waterproof caulk around the perimeter of the collar to provide a proper seal Note Storm collar is required but can be installed after the home is sited TERMINATIONS SPARK ARRESTOR The fireplace sys...

Page 9: ...A mantel may be installed if desired see figure 20 Woodwork such as wood trims mantels or any other combustible material projecting from the front face must not be placed within 9 inches of the firep...

Page 10: ...r Use only a inch black iron pipe and appropriate fittings When installing a gas line a shut off valve designed for installation outside the appliance is recommended STEP 1 To install remove the knock...

Page 11: ...re 25 Pulling the handle out will free the outside air door to open Pushing the handle in will lock the door close FOR FURTHER OPERATING GUIDELINES INSTRUCTIONS AND WARRANTY INFORMATION PLEASE REFER T...

Page 12: ...11 For more information visit www desatech com ILLUSTRATED PARTS...

Page 13: ...ONT 1 50 16502 BAG POLY 1 16 106683 01 LEG FIREBOX SUPPORT 2 51 16901 STRAPPING 7 16 10 5 17 56090 COLEMAN DECAL 1 52 20023 COLLAR STARTER 1 18 106687 01 COLLAR DAMPER CAN 1 53 20027 RETAINER REFRACTO...

Page 14: ...24 8DM 24 Double Wall Pipe 1 0 18 8DM 18 Double Wall Pipe 0 2 FST A Adjustable Firestop Thimble 1 1 V6F 8DM Roof Flashing 1 1 VSC1 8DM Storm Collar 1 1 RTL 8DM Round Cap Termination 1 1 VENT KITS USE...

Page 15: ...DM 36 8DM DOUBLE WALL PIPE 36 SECTION 9736A1236 36 8DM 48 8DM DOUBLE WALL PIPE 48 SECTION 9736A1248 48 8DM V6F 8DM ROOF FLASHING 0 6 12 PITCH 9736 5241 V6F 8DM V12F 8DM ROOF FLASHING 6 12 12 12 PITCH...

Reviews: