![Denyo DCA-30ESX Instruction Manual Download Page 44](http://html1.mh-extra.com/html/denyo/dca-30esx/dca-30esx_instruction-manual_2485065044.webp)
(4) After engine starts up, release the starter key.
Check the Oil pressure failure lamp goes off.
(5) Drive the machine for warming up the engine
for about 5 minutes at the "START / IDLING"
position o f the throttle lever.
(6) After wanning up the engine, set the throttle
lever to the "RUN" position. And check on the
idling speed is as specified in the following table
by the frequency meter. If the idling speed is
not as specified or change
of
frequency is
required, adjust the idling speed by the
frequency adjusting screw.
Commercial frequency
Idling speed
Operation at 60Hz
52. б Ш Ш Б т т - 1)
Operation at 60Hz
62. 5Hz(l875m in ])
I f the idling speed set above speed, frequency
becomes nearly 50Hz or 60Hz in the rated load.
(7) Set the voltage to the rated by the voltage
regulator, and turn the breaker to "ON". The
machine starts power transmission state.
-
43 -