![Denyo DCA-30ESX Instruction Manual Download Page 27](http://html1.mh-extra.com/html/denyo/dca-30esx/dca-30esx_instruction-manual_2485065027.webp)
Installation procedure
* Install the machine horizontally on a solid foundation.
* Provide a space o f more than about lm at the side o f the control panel and fuel
feed port to ensure correct operation and supply.
* Provide a
space o f more than about 1.2m on the left and
right sides for check of
the engine, oil supply and cable connection work.
* A sufficient space is required at the top o f the machine to allow hot air (exhaust
air) from the radiator and exhaust gases to be discharged and to supply water to the
radiator.
* When the
machine is operated in a place with much dust
or salt, careful
maintenance is required to prevent clogging or damage to the radiator or poor
insulation of electric parts.
Indoor installation
* Exhaust gases should be discharged outdoors using an exhaust pipe.
* Exhaust air should also be discharged outdoors using a duct or the like.
* Insufficient indoor ventilation will raise the (indoor) temperature and
affects the performance o f the machine.
* For details o f required volume o f ventilation, contact distributor or our office.
- 26 -