Outlet Box Wiring
For proper clockwise rotation the outlet box is wired as follows:
Standard 230V (High voltage) output:
•
Leads numbered 4 & 7 together
•
Leads numbered 5 & 8 together
•
Leads numbered 6 & 9 together
•
Lead numbered 1 to the X terminal on the outlet
•
Lead numbered 2 to the Y terminal on the outlet
•
Lead numbered 3 to the Z terminal on the outlet
•
Terminal W on the outlet is wired to the outlet frame and serves as the ground
Optional 115V (Low voltage) output:
•
Leads numbered 4, 5, & 6 together
•
Leads numbered 1 & 7 are combined to terminal X on the outlet
•
Leads numbered 2 & 8 are combined to terminal Y on the outlet
•
Leads numbered 3 & 9 are combined to terminal Z on the outlet
•
Terminal W on the outlet is wired to the outlet frame and serves as the ground
Caution:
Reconnection for low voltage (115V) requires heavier 10 gauge stranded jumper wires from
the primary outlet terminals to the corresponding outlets on the secondary outlet.
Reconnection wiring or outlet replacement should be performed by a competent qualified electrician.
9