NO.6 Detailed Function Description
64
P154
Setting range
Unit
Ex-factory value
Alteration
Allowable outage duration
0.1-5.0s
0.1s
0.5
╳
The maximum duration of outage can be determined via this parameter; in case of going
beyond set time, the inverter shall still stop outputting after power recovery; restart shall
proceed as per general startup sequence.
P155
Setting range
Unit
Ex-factory value
Alteration
Times of fault restart
00-10
1
00
╳
The inverter shall be automatically reset and restarted in case of abnormal situation (such as
overcurrent and overvoltage); in case of common starting mode, this mode shall be followed;
in case of frequency tracking start, the start shall be conducted in the manner of tracking start.
After starting, if no anomaly occurs within 60s, set times shall be recovered; if any anomaly
occurs and set number is achieved, the converter shall no longer output, and restart shall be
conducted after resetting. If P155 is at 0, no automatic reset or restart function shall be
performed in case of anomaly.