NO.5 Function List
21
P115
P116
Internally controlled multi-segment speed timer XV
Internally controlled multi-segment speed timer XVI
0.0-6500.0s
0.0-6500.0s
0.0
0.0
P117
Internally controlled multi-segment speed memory
function
0-1
0
╳
5.6 Protection function parameters
Function
code
Function
Setting range and
function description
Ex-factory
value
Alteration
P118
Selection of over-voltage stall
0-1
1
╳
P119
Stalling level during accelerating
0-200%
150
╳
P120
Stalling level during constant
speed
0-200%
0
╳
P121
Stalling deceleration time during
constant speed
0.1-25.5s
5
○
P122
Stalling level during decelerating
0-200%
150
╳
P123
Selection of over-torque
detection mode
0-3
0
╳
P124
Over-torque detection level
0-200%
0
╳
P125
Over-torque detection time
0.1-20.0s
1.0
╳
P126
Pulse counter memory
0-1
0
╳
P127-P129
Reserve
5.7 Function parameters of constant-pressure water supply
Function
node
Function description
Setting range and
function description
Ex-factory
value
Alteration
P130
Quantity of auxiliary pumps
0-2
0
╳
P131
Continuous time of auxiliary
pump
1-9000min
60
╳
P132
Interlocking time of auxiliary
1-250s
5
○