NO.6 Detailed Function Description
25
No.6
Detailed Function Descriptions
6.1 Basic function parameters
P000
Setting range
Unit
Ex-factory value
Change
Parameter locking
0-1
1
0
╳
0: Invalid
1: Valid
i.e. parameter locking, meaning other parameters are unchangeable
except this parameter.
This parameter can avoid mistake operation of non-operators which may cause unnecessary
danger and mistake. But after locking parameters, the current frequency can be changed
through keys
▲ and ▼.
P001
Setting range
Unit
Ex-factory value
Alteration
Selection of control mode
0-2
1
0
╳
0: Keyboard setting
Operating command is set by keyboard.
1: External terminals setting
Operating command is set by 6-way programmable input
terminals.
2: Communication interface setting
Operating
command
is
set
by
transmission of communication interface
P002
Setting range
Unit
Ex-factory value
Alteration
Frequency setting selection
0-3
1
0
╳
0: Keyboard setting
P003 of former operating frequency is set by keyboard.
1: Analog quantity setting Former operating frequency is controlled by input analog signals
and signal type is decided by P070.
Refer to P070-P076 for relevant parameters.
2
:
Communication interface setting Current operating frequency is set by serial port
communication.
3: Potentiometer of manipulator Current operating frequency is set by potentiometer knob
on manipulator.
P003
Setting range
Unit
Ex-factory value
Alteration
Main frequency
0.00-400.00 Hz
0.01 Hz
*
╳