23
ENGLISH
Operation and installation manual SOLIVIA 2.5 EU G3
If has been pressed the display shows, for example:
L: 49.70 Hz LFT
A: 49.99 Hz RUN
The limit „L:” will increase till crossing the actual measured grid frequency „A:”. Reached this condi-
tion the inverter disconnects from grid and the display shows, for example:
L: 49.99 Hz 0.044 S
A: 49.99 Hz LF pass
If the test is confi rmed, the autotest routine is fi nished. The display shows, for example:
Autotest Passed
Esc to continue
First line shows the actual autotest status. If all the single test are passed and confi rmed, the actual
autotest status will be passed. Pressing „ESC” the display goes back to the main menu or the inver-
ter returns automatically to normal operation after 10 seconds.
If the actual autotest status is failed, press „ESC” and the display goes back to the main menu and
the inverter is in error condition. The display shows “ AUTOTEST FAILED”. If the actual status is
failed it is possible to restart the autotest routine. If the autotest permanently fails please contact
the customer service.
If during the autotest is performed any grid or inverter error occurs, the autotest routine is aborted
and the display shows the actual failed autotest status directly after new calibration.
The inverter resets and performs a restart if the previous status was passed.
The autotest can be started only if the inverter is in normal operating conditions. It is not possible
to entry the autotest routine if the grid is not in the defi ned tolerances, if any internal inverter error
occurs or the solar plant do not respect the specifi cations.
A restart of the inverter will be done after the autotest, when the result of the current autotest is
different from the result from the autotest before.
While the autotest routine is ongoing, green LED is fl ashing, the red LED shows isolation measure-
ment status and the yellow LED shows the status of last autotest (yellow LED on: last autotest was
failed; yellow LED off: last autotest was ok).
The fi rst line shows the limits according the standard. The second line shows the actual measured
trip limit and the test status if positive (pass). (If the test is negative (failed), press „ESC“ and the
display goes back to the main menu and the inverter is in error condition.).
Pressing the test is confi rmed and the autotest routine continue. If is not pressed, the result
is shown for 10 seconds. After this time, the result is confi rmed automatically.
Summary of Contents for SOLIVIA 2.5 EU G3
Page 1: ...Operation and installation manual for SOLIVIA 2 5 EU G3 2 5 EU...
Page 2: ......
Page 4: ...2 Operation and installation manual SOLIVIA 2 5 EU G3...
Page 40: ...Bedienungsanleitung SOLIVIA 2 5 EU G3 38...
Page 42: ...40 Bedienungsanleitung SOLIVIA 2 5 EU G3 Bedienungsanleitung SOLIVIA 2 5 EU G3...
Page 78: ...76 Bedienungsanleitung SOLIVIA 2 5 EU G3...
Page 80: ...78 Manuale di istruzioni SOLIVIA 2 5 EU G3...
Page 116: ...Manuel de fonctionnement et d installation SOLIVIA 2 5 EU G3 114...
Page 154: ...Manual de funcionamiento y de instalaci n SOLIVIA 2 5 EU G3 152...
Page 192: ...190 Manual de funcionamiento y de instalaci n SOLIVIA 2 5 EU G3...
Page 194: ...192 Manual de instru es SOLIVIA 2 5 EU G3...
Page 230: ...228 Manual de instru es SOLIVIA 2 5 EU G3...
Page 232: ...230 N vod k obsluze SOLIVIA 2 5 EU G3...
Page 268: ...N vod na prev dzku a in tal ciu SOLIVIA 2 5 EU G3 266...
Page 305: ...303 SLOVENSK N vod na prev dzku a in tal ciu SOLIVIA 2 5 EU G3...
Page 306: ...304 Handleiding SOLIVIA 2 5 EU G3 Handleiding SOLIVIA 2 5 EU G3...
Page 308: ...306 Handleiding SOLIVIA 2 5 EU G3 Handleiding SOLIVIA 2 5 EU G3...
Page 344: ...342 Handleiding SOLIVIA 2 5 EU G3...
Page 346: ...344 SOLIVIA 2 5 EU G3...
Page 351: ...349 SOLIVIA 2 5 EU G3 4 3 1 2 DC 3 4 RS485 EIA485 5 6 3 1 2 3 5 6 4...
Page 359: ...357 SOLIVIA 2 5 EU G3 MPP Booster DC Bus DC DC DC A B C AC 6 9 Solar Inverter...
Page 378: ...376 SOLIVIA 2 5 EU G3 DC 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3 Solivia 2 5...
Page 381: ...379 SOLIVIA 2 5 EU G3 12 https guarantee solar inverter com SOLIVIA 5 10 5...
Page 382: ...380 SOLIVIA 2 5 EU G3...
Page 383: ...381 Operation and installation manual SOLIVIA 2 5 EU G3 13 Certificates...
Page 384: ...382 Operation and installation manual SOLIVIA 2 5 EU G3...
Page 391: ...389 Operation and installation manual SOLIVIA 2 5 EU G3 Notes...