29
ENGLISH
Operation and installation manual SOLIVIA 2.5 EU G3
8.2
Display messages
LED STATUS
DISPLAY
MESSAGE
CAUSE
ELIMINATION
green: <on>
red: <on>
yellow: <on>
-
Display communication
faulty.
- If the fault persists after the device has
been reset, please inform your service
technician.
green: <off>
red: <off>
yellow: <on>
AC frequency
failure
Grid frequency overshoo-
ting or undershooting
specified limit range.
- Check the grid frequency via the display
in the N menu.
green: <off>
red: <off>
yellow: <on>
AC voltage
failure
Grid voltage overshooting
or undershooting specified
limit range.
- Check the grid voltage via the display in
the N menu.
- If no voltage present, check grid auto-
matic circuit breaker.
green: <off>
red: <off>
yellow: <on>
Autotest failed
(only for Italy)
The autotest status is in
error.
Repeat the autotest routine.
green: <flashes>
red: <off>
yellow: <off>
Calibration
ongoing
Check internal settings.
Normal function before input mode.
green: <off>
red: <off>
yellow: <on>
DC injection
failure
DC component of input-
side alternating current is
too high.
- If the fault persists after the device has
been reset, please inform your service
technician.
green: <off>
red: <off>
yellow: <on>
Error # 301
Internal communication
error or hardware fault.
- If the fault persists after the device has
been reset, please inform your service
technician.
green: <off>
red: <off>
yellow: <on>
Error # 302
The device trips and
reverts to grid input mode
once the temperature has
dropped.
- Check the installation site (no direct
sunlight, air circulation).
green: <off>
red: <on>
yellow: <off>
Error # 506
Error # 508
Isolation resistance fault
on the DC side during
start-up phase (# 508) or
running phase (# 506).
- Check the isolation resistance on the DC
side of the PV modules.
green: <on>
red: <on>
yellow: <off>
Isolation start-
up warning
Isolation run-
ning warning
Isolation resistance fault
on the DC side during
start-up phase or running
phase.
- You must check the isolation resistance
on the DC side of the PV modules.
Solar inverter is still feeding!
green: <on>
red: <on>
yellow: <off>
PV+ groun-
ding fault
PV- grounding
fault
Connection PV+ (PV-)
to GND is interrupted or
wrong pole is connected
to GND.
- Check that the GND connection has been
made correctly and/or check the fuse in
the grounding path. Change the fuse if
necessary. The solar inverter remains in
feed-in operation.
green: <off>
red: <off>
yellow: <on>
Relay error
One of the anti-islanding
protection output relays is
faulty / defective.
- The solar inverter is defective.
- Return the device.
green: <off>
red: <off>
yellow: <on>
Revision error
Versions of hard- and soft-
ware are not compatible.
- If the fault persists after the device has
been reset, please inform your service
technician.
Summary of Contents for SOLIVIA 2.5 EU G3
Page 1: ...Operation and installation manual for SOLIVIA 2 5 EU G3 2 5 EU...
Page 2: ......
Page 4: ...2 Operation and installation manual SOLIVIA 2 5 EU G3...
Page 40: ...Bedienungsanleitung SOLIVIA 2 5 EU G3 38...
Page 42: ...40 Bedienungsanleitung SOLIVIA 2 5 EU G3 Bedienungsanleitung SOLIVIA 2 5 EU G3...
Page 78: ...76 Bedienungsanleitung SOLIVIA 2 5 EU G3...
Page 80: ...78 Manuale di istruzioni SOLIVIA 2 5 EU G3...
Page 116: ...Manuel de fonctionnement et d installation SOLIVIA 2 5 EU G3 114...
Page 154: ...Manual de funcionamiento y de instalaci n SOLIVIA 2 5 EU G3 152...
Page 192: ...190 Manual de funcionamiento y de instalaci n SOLIVIA 2 5 EU G3...
Page 194: ...192 Manual de instru es SOLIVIA 2 5 EU G3...
Page 230: ...228 Manual de instru es SOLIVIA 2 5 EU G3...
Page 232: ...230 N vod k obsluze SOLIVIA 2 5 EU G3...
Page 268: ...N vod na prev dzku a in tal ciu SOLIVIA 2 5 EU G3 266...
Page 305: ...303 SLOVENSK N vod na prev dzku a in tal ciu SOLIVIA 2 5 EU G3...
Page 306: ...304 Handleiding SOLIVIA 2 5 EU G3 Handleiding SOLIVIA 2 5 EU G3...
Page 308: ...306 Handleiding SOLIVIA 2 5 EU G3 Handleiding SOLIVIA 2 5 EU G3...
Page 344: ...342 Handleiding SOLIVIA 2 5 EU G3...
Page 346: ...344 SOLIVIA 2 5 EU G3...
Page 351: ...349 SOLIVIA 2 5 EU G3 4 3 1 2 DC 3 4 RS485 EIA485 5 6 3 1 2 3 5 6 4...
Page 359: ...357 SOLIVIA 2 5 EU G3 MPP Booster DC Bus DC DC DC A B C AC 6 9 Solar Inverter...
Page 378: ...376 SOLIVIA 2 5 EU G3 DC 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3 Solivia 2 5...
Page 381: ...379 SOLIVIA 2 5 EU G3 12 https guarantee solar inverter com SOLIVIA 5 10 5...
Page 382: ...380 SOLIVIA 2 5 EU G3...
Page 383: ...381 Operation and installation manual SOLIVIA 2 5 EU G3 13 Certificates...
Page 384: ...382 Operation and installation manual SOLIVIA 2 5 EU G3...
Page 391: ...389 Operation and installation manual SOLIVIA 2 5 EU G3 Notes...