7.Error message and Trouble Shooting
ERROR
Message
Possible cause
Action
AC Freq
High
1. Actual utility frequency is over
the OFR setting
2. Incorrect country setting
3. Detection circuit malfunction
1. Check the utility frequency on the
inverter terminal
2. Check country setting
3. Check the detection circuit inside the
inverter
AC Freq
Low
1. Actual utility frequency is under
the UFR setting
2. Incorrect country or Grid setting
3. Detection circuit malfunction
1. Check the utility frequency on the
inverter terminal
2. Check country & Grid setting
3. Check the detection circuit inside the
inverter
Grid Quality
Non-linear load in Grid and near
to inverter
Grid connection of inverter need to be
far away from non-linear load if necessary
HW Con.
Fail
1. Wrong connection in AC plug
2. Detection circuit malfunction
1. Check the AC connection, must accords
to manual
2. Check the detection circuit inside the
inverter
No Grid
1. AC breaker is OFF
2. Disconnect in AC plug
1. Switch on AC breaker
2. Check the connection in AC plug and
make sure it connects to inverter
AC Volt
Low
1. Actual utility voltage is under
the UVR setting
2. Incorrect country or Grid setting
3. Wrong connections in AC plug
4. Detection circuit malfunction
1. Check the utility voltage connection
to the inverter terminal
2. Check country & Grid setting
3. Check the connection in AC plug
4. Check the detection circuit inside the
inverter
AC Volt
High
1. Actual utility voltage is over the
OVR setting
2. Utility voltage is over the Slow
OVR setting during operation
3. Incorrect country or Grid setting
4. Detection circuit malfunction
1. Check the utility voltage on the inverter
terminal
2. Check the utility voltage on the inverter
terminal
3. Check country & Grid setting
4. Check the detection circuit inside the
inverter
Solar1
High
1. Actual Solar1 voltage is over
1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Check the detection circuit inside the
inverter
40
Error message and Trouble Shooting
Summary of Contents for RPI Series
Page 2: ......
Page 52: ......
Page 53: ...RPI M15A M20A The power behind competitiveness www deltaww com English 1 53 103...
Page 55: ...55...
Page 57: ...2 1 RPI M15A M20A 2 1 2 2 1 2 2 2 1 2 2 57...
Page 58: ...2 2 RPI M15A RPI M20A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 4 sets DC 2 1 58...
Page 59: ...2 3 2 3 2 3 59...
Page 61: ...PV array IEC 61730 Class A 3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 3 1 61...
Page 63: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 M6 Screw 63...
Page 64: ...3 5 25 60 40 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 64...
Page 89: ...6 1 6 1 PV Inverter 6 AC DC 6 1 89...
Page 90: ...6 2 6 3 6 2 6 3 6 3 4 90...
Page 97: ...8 AC DC OFF voltmeter AC DC AC DC RS 485 97...
Page 103: ...RPI M15A M20A The power behind competitiveness www deltaww com English 1 53 103...
Page 105: ...105...
Page 107: ...2 1 RPI M15A M20A 2 1 2 2 1 2 2 2 1 2 2 107...
Page 108: ...2 2 RPI M15A RPI M20A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 4 sets DC 2 1 108...
Page 109: ...2 3 2 3 2 3 109...
Page 111: ...PV array IEC 61730 Class A 3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 3 1 111...
Page 113: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 M6 Screw 113...
Page 114: ...3 5 25 60 40 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 114...
Page 139: ...6 1 6 1 PV Inverter 6 AC DC 6 1 139...
Page 140: ...6 2 6 3 6 2 6 3 6 3 4 140...
Page 147: ...8 AC DC OFF voltmeter AC DC AC DC RS 485 147...
Page 153: ......
Page 154: ...Version 05190319 5013242902...