ERROR
Message
Possible cause
Action
Solar2
High
1. Actual Solar2 voltage is over
1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Check the detection circuit inside the
inverter
Insulation
1. PV array insulation fault
2. Large PV array capacitance
between Plus to Ground or
Minus to Ground or both.
3. Detection circuit malfunction
1. Check the insulation of Solar inputs
2. Check the capacitance, dry PV panel
if necessary
3. Check the detection circuit inside the
inverter
Table 7-1 Error Message
Warning
Message
Possible cause
Action
Solar1
Low
1. Actual Solar1 voltage is under
the limit
2. Some devices were damaged
inside the inverter if the actual
Solar1 voltage is close to "0"
3. Detection circuit malfunction
1. Check the Solar1 voltage connection
to the inverter terminal
2. Check all switching devices in boost1
3. Check the detection circuit inside the
inverter
Solar2
Low
1. Actual Solar2 voltage is under
the limit
2. Some devices were damaged
inside the inverter if the actual
Solar2 voltage is close to "0"
3. Detection circuit malfunction
1. Check the Solar2 voltage connection
to the inverter terminal
2. Check all switching devices in boost2
3. Check the detection circuit inside the
inverter
HW FAN
1. One or more fans are locked
2. One or more fans are defective
3. One ore more fans are
disconnected
4. Detection circuit malfunction
1. Remove the object that stuck in the
fan(s)
2. Replace the defective fan(s)
3. Check the connections of all fans
4. Check the detection circuit inside the
inverter
SPD Fail
1. Inverter was struck by lighting.
2. One or more SPD are defective
3. One or more SPD are
disconnected
4. Detection circuit malfunction
1. Check inverter’s status
2. Replace the defective SPD
3. Check the connections of SPDs
4. Check the detection circuit inside the
inverter
Table 7-2 Warning Message
41
Error message and Trouble Shooting
Summary of Contents for RPI Series
Page 2: ......
Page 52: ......
Page 53: ...RPI M15A M20A The power behind competitiveness www deltaww com English 1 53 103...
Page 55: ...55...
Page 57: ...2 1 RPI M15A M20A 2 1 2 2 1 2 2 2 1 2 2 57...
Page 58: ...2 2 RPI M15A RPI M20A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 4 sets DC 2 1 58...
Page 59: ...2 3 2 3 2 3 59...
Page 61: ...PV array IEC 61730 Class A 3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 3 1 61...
Page 63: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 M6 Screw 63...
Page 64: ...3 5 25 60 40 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 64...
Page 89: ...6 1 6 1 PV Inverter 6 AC DC 6 1 89...
Page 90: ...6 2 6 3 6 2 6 3 6 3 4 90...
Page 97: ...8 AC DC OFF voltmeter AC DC AC DC RS 485 97...
Page 103: ...RPI M15A M20A The power behind competitiveness www deltaww com English 1 53 103...
Page 105: ...105...
Page 107: ...2 1 RPI M15A M20A 2 1 2 2 1 2 2 2 1 2 2 107...
Page 108: ...2 2 RPI M15A RPI M20A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 4 sets DC 2 1 108...
Page 109: ...2 3 2 3 2 3 109...
Page 111: ...PV array IEC 61730 Class A 3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 3 1 111...
Page 113: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 M6 Screw 113...
Page 114: ...3 5 25 60 40 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 114...
Page 139: ...6 1 6 1 PV Inverter 6 AC DC 6 1 139...
Page 140: ...6 2 6 3 6 2 6 3 6 3 4 140...
Page 147: ...8 AC DC OFF voltmeter AC DC AC DC RS 485 147...
Page 153: ......
Page 154: ...Version 05190319 5013242902...