19
Quick installation guide for RPI M15A M20A inverters
Setting a power limitation
You should set a power limitation only when requested by country regulations, authorities or your grid
operator
1.
When the default information is displayed, press the button
ESC
to open the main menu. Otherwise, repeatedly press
the button
ESC
until the main menu is displayed
20
15
10
5
0 4
8
12
16
20
24
P(w)
Runtime: 8.2Hrs
Power: 12103W
On Grid
21. Jun 2013 09:30
E-Today: 47kWh
2.
Use the buttons
and
to select
Settings
To confirm your selection, press the button
ENT
E-Today
E-Today
Power Meter
Energy Log
Event Log
Inverter Information
Settings
Operation Data
21. Jun 2013 09:30
Menu
3.
Use the buttons
and
to select
Active/Reactive
Power Control
To confirm your selection, press the button
ENT
Personal Settings
Personal Settings
Coefficients Settings
Install Settings
Install Settings
Active/Reactive Power Control
FRT
21. Jun 2013 09:30
Settings
4.
The menu is protected by password 5555. Use the buttons
and
to set each digit
To confirm a digit, press the button
ENT
3
3
3
3
ENT
21. Jun 2013 09:30
Password
5.
Use the buttons
and
to select
Active Power Con-
trol
. To confirm your selection, press the button
ENT
Active Power Control
Reactive Power Control
21. Jun 2013 09:30
Active / Reactive Power
6.
Use the buttons
and
to select
Power limit
To confirm your setting, press the button
ENT
Power Limit
Power vs. Frequency
P(V)
21. Jun 2013 09:30
Active Power Control
7.
Use the buttons
and
to select an entry and press
the button
ENT
[
[
[
]%
]
]
Set Point
Actual / Rated Power
Mode
100
Rated
OFF
21. Jun 2013 09:30
Active Power Control
8.
Use the buttons
and
to change the value, then
press the button
ENT
To activate the function, set
Mode
to
ON