Quick installation guide for RPI M6A M8A M10A inverters
Setting the inverter ID
If you connect multiple inverters via RS485, for each of the inverters a different inverter ID has to be set
The inverter ID is needed to identify each inverter For a description of the RS485 connection, see
“ Con-
necting RS485 (optional)”, p 11
E r t r a g h e u t e : 0 k W h
L e i s t u n g : 0 W
S t a t u s : A m N e t z
1 0 . S e p 2 0 1 4 1 5 : 3 2
1.
When the default information is displayed, press any button to open the main menu
I n v e r t e r I n f o .
G e n e r a l S e t t i n g s
I n s t a l l S e t t i n g s
A c t i v e / R e a c t i v e P w r
F R T
2.
Use the buttons
and
to select
Install Settings
To confi rm your selection, press the button
ENT
0 * * *
P a s s w o r t
3.
The menu is protected by password 5555 Use the buttons
and
to set each
digit
To confi rm a digit, press the button
ENT
G r i d S e t t i n g s
C o u n t r y
I n s u l a t i o n
I n v e r t e r I D : 0 0 1
4.
Use the buttons
and
to select
Inverter ID
To confi rm your selection, press the button
ENT
I D = 0 0 1
O m v o r m e r - I D
5.
Use the buttons
and
to change the value (range: 001 255)
To confi rm your setting, press the button
ENT
Setting the AC connection type
Per default, the AC connection type is set to 3P4W (3 N + PE) Only if you use an AC connection
with 3 PE (3P3W), you need to change this setting For a description of the AC connection, see
“ Connecting Digital inputs, EPO and Dry contacts (optional)”, p 12
E - T o d a y : 0 k W h
P o w e r : 0 W
S t a t u s : O n G r i d
1 0 . S e p 2 0 1 4 1 5 : 3 2
1.
When the default information is displayed, press any button to open the main menu
I n v e r t e r I n f o .
G e n e r a l S e t t i n g s
I n s t a l l S e t t i n g s
A c t i v e / R e a c t i v e P w r
F R T
2.
Use the buttons
and
to select
Install Settings
To confi rm your selection, press the button
ENT
0 * * *
P a s s w o r d
3.
The menu is protected by password 5555 Use the buttons
and
to set each
digit
To confi rm a digit, press the button
ENT
3 P 3 W / 3 P 4 W
C o n n e c t i o n t y p e :
4.
Use the buttons
and
to select
Connection type 3P3W
To confi rm your selection, press the button
ENT