Quick installation guide for RPI M6A M8A M10A inverters

 Setting the inverter ID

If you connect multiple inverters via RS485, for each of the inverters a different inverter ID has to be set 
The inverter ID is needed to identify each inverter  For a description of the RS485 connection, see 

“ Con-

necting RS485 (optional)”, p  11

  

E r t r a g   h e u t e :       0 k W h

L e i s t u n g :               0 W

S t a t u s :             A m   N e t z

    1 0 . S e p   2 0 1 4   1 5 : 3 2

1. 

When the default information is displayed, press any button to open the main menu 

I n v e r t e r   I n f o .
G e n e r a l   S e t t i n g s
I n s t a l l   S e t t i n g s
A c t i v e / R e a c t i v e   P w r  
F R T

2. 

Use the buttons 

 and 

 to select 

Install Settings

 

To confi rm your selection, press the button 

ENT

 

 

          0   *   *   *

          P a s s w o r t

 

3. 

The menu is protected by password 5555  Use the buttons 

 and 

 to set each 

digit 

To confi rm a digit, press the button 

ENT

 

G r i d   S e t t i n g s

C o u n t r y        

I n s u l a t i o n

I n v e r t e r   I D :         0 0 1

4. 

Use the buttons 

 and 

 to select 

Inverter ID

  

To confi rm your selection, press the button 

ENT

  

 

          I D = 0 0 1

        O m v o r m e r - I D

 

5. 

Use the buttons 

 and 

 to change the value (range: 001    255)  

To confi rm your setting, press the button 

ENT

  

Setting the AC connection type

Per default, the AC connection type is set to 3P4W (3 N + PE)  Only if you use an AC connection 
with 3 PE (3P3W), you need to change this setting  For a description of the AC connection, see 

“ Connecting Digital inputs, EPO and Dry contacts (optional)”, p  12

 

E - T o d a y :                 0 k W h

P o w e r :                       0 W

S t a t u s :             O n   G r i d

    1 0 . S e p   2 0 1 4   1 5 : 3 2

1. 

When the default information is displayed, press any button to open the main menu 

I n v e r t e r   I n f o .
G e n e r a l   S e t t i n g s
I n s t a l l   S e t t i n g s
A c t i v e / R e a c t i v e   P w r  
F R T

2. 

Use the buttons 

 and 

 to select 

Install Settings

 

To confi rm your selection, press the button 

ENT

 

 

          0   *   *   *

          P a s s w o r d

 

3. 

The menu is protected by password 5555  Use the buttons 

 and 

 to set each 

digit 

To confi rm a digit, press the button 

ENT

 

 

      3 P 3 W   /   3 P 4 W

  C o n n e c t i o n   t y p e :

 

4. 

Use the buttons 

 and 

 to select 

Connection type 3P3W

 

To confi rm your selection, press the button 

ENT

 

Summary of Contents for RPI M10A

Page 1: ...Quick Installation Guide RPI M6A RPI M8A RPI M10A Europe ...

Page 2: ...f 17 13 Technical data 18 Service Europe 20 Copyright Delta Energy Systems Germany GmbH All rights reserved This manual is included with our solar inverter and is intended for use by the installer and end user The technical instructions and illustrations in this manual are to be treated as confidential and no part of this manual may be reproduced without prior written permission from Delta Energy ...

Page 3: ... this reason be sure to observe and follow all instructions Installation and commissioning may only be performed by qualified electricians using the installation and commission ing instructions found in this manual The solar inverter must be disconnected from power and the solar modules before any work on it can be performed The solar inverter has a high leakage current value The ground wire must ...

Page 4: ...value setting Move down Move downwards in menu Set value decrease Move up Move upwards in menu Set a value increase ENT Enter Select menu item Open configurable value for editing Finish editing adopt set value DC1 DC2 DC2 DC1 Display buttons LEDs Type label Electrical connectors Mounting holes for screwing the inverter to the mounting plate and for grounding the inverter housing AC DC Disconnectio...

Page 5: ...structions contained in the manual Risk of injury from hot surfaces When in operation the housing of the solar inverter can become very hot Do not dispose of the inverter in your general household waste Always follow the local laws and regulations regarding the disposal of electrical devices Regulatory Compliance Mark RCM mark The inverter is compliant with the Australian Electrical Safety and EMC...

Page 6: ...stalled indoors or in protected outdoor areas that means outdoor but protected by a roof against direct sun rain or snow Mount the solar inverter vertically Where to mount the inverter Mount the solar inverter so that the LEDs and display can be easily seen and that the buttons can be operated Make sure the reading angle and instal lation height are sufficient Always use the mounting plate supplie...

Page 7: ... one side fasten the inverter with one mounting screw to the mounting plate and additionally ground the inverter housing Washer spring Washer M4 Screw Washer spring Washer M4 Screw Grounding cable Toothed ring Hang the inverter into the mounting plate Check that the rail of the inverter hangs correctly in the mounting plate Fasten the mounting plate with 8 screws to the wall 1 2 3 4 ...

Page 8: ...4 wires L1 L2 L3 N PE Wiring for 3P3W grid systems 3 phases with 3 wires L1 L2 L3 PE Permitted earthing systems 3P3W 3P4W L1 L2 400 VAC 20 L1 N 230 VAC 20 L1 L3 400 VAC 20 L2 N 230 VAC 20 L2 L3 400 VAC 20 L3 N 230 VAC 20 AC grid voltage requirements TT is not recommended The voltage of N has to be very close to PE difference 20 Vrms Use wire end sleeves on each wire Use wire end sleeves on each wi...

Page 9: ...nt of the residual current device is dependent on the design of the PV installation and the number of connected inverters The tripping current of the residual cur rent device must not however be less than the specified minimum tripping current Important information regarding safety AC cable requirements Connect properly sized wires to the correct poles see table AC connector Amphenol C16 3 Current...

Page 10: ...0001 UR 5 5 9 32 0013P0001 UR 4 6 3 6 32 0015P0001 UR 5 5 9 32 0017P0001 UR a b DISCONN AC DC OFF ON DANGER Risk of death or serious injury from electrocution Potentially fatal voltage may be applied to the DC connections of the solar in verter When light is falling on solar modules they immediately start producing energy They do so even when the sun is not shining Turn the AC DC isolating switch ...

Page 11: ...Gateway Default baud rate is 19200 which can be changed on the inverter see Setting the baud rate for RS485 p 14 RS485 connector Connecting multiple inverters to a datalogger ON OFF ON OFF ON OFF Datalogger Termination resistor ON RS485 Termination resistor OFF Termination resistor OFF Connecting a single inverter to a datalogger Datalogger Termination resistor ON If you connect multiple inverters...

Page 12: ...ts are closed The digital inputs can be used to connect an external ripple con trol receiver for controlling the active power Dry contacts Communication port The relay for EPO can be set on the display to normally open or normally closed see Setting EPO Emergency Power Off p 17 Dry contacts Digital inputs and EPO RJ45 On the display see Setting dry contacts p 17 the dry con tacts can be connected ...

Page 13: ...s 50HZ 2 Use the buttons and to select your country or grid type To confirm your selection press the button ENT YES NO ENGLAND set country Are you sure to 3 If the selected country is correct use the buttons and to select the entry YES To confirm your selection press the button ENT If you want to change your selection press the button ESC The inverter starts a self test which takes approximately 2...

Page 14: ... The selection moves to the next value which you can set now To move back to previous value press the button ESC Commissioning Further settings 12 The settings described in this section may not be relevant for your installation Check each setting whether it is needed for you E Today 0kWh Power 0W Status On Grid 10 Sep 2014 15 32 1 When the default information is displayed press any button to open ...

Page 15: ... to select Inverter ID To confirm your selection press the button ENT ID 001 Omvormer ID 5 Use the buttons and to change the value range 001 255 To confirm your setting press the button ENT Setting the AC connection type Per default the AC connection type is set to 3P4W 3 phases N PE Only if you use an AC connection with 3 phases PE 3P3W you need to change this setting For a description of the AC ...

Page 16: ...om Delta Support Use the buttons and to set each digit To confirm a digit press the button ENT Reactive Power Ctrl Active Power Ctrl 4 Use the buttons and to select Active Power Ctrl To confirm your selection press the button ENT P V Power vs Frequency Power limit 5 Use the buttons and to select Power limit To confirm your selection press the button ENT Set Point 100 Mode OFF 6 Use the buttons and...

Page 17: ...ption To confirm your selection press the button ENT Setting EPO Emergency Power Off E Today 0kWh Power 0W Status On Grid 10 Sep 2014 15 32 1 When the default information is displayed press any button to open the main menu Otherwise repeatedly press the button ESC until the main menu is displayed Inverter Info General Settings Install Settings Active Reactive Pwr FRT 2 Use the buttons and to selec...

Page 18: ...imum asymmetry 60 40 Number of DC inputs total DC1 DC 2 2 1 1 2 1 1 3 2 1 Galvanic isolation No Overvoltage category 2 II Output AC RPI M6A RPI M8A RPI M10A Maximum apparent power 3 6300 VA 8400 VA 10500 VA Nominal apparent power 6000 VA 8000 VA 10000 VA Voltage range 4 230 20 400 VAC 20 3 phase PE or 3 phase N PE Nominal current 8 7 A 11 6 A 14 5 A Maximum current 9 7 A 13 A 16 A Inrush current 3...

Page 19: ...cy 98 3 98 3 98 3 EU efficiency 97 6 97 9 98 0 Operating temperature range 25 60 C Operating temperature range without derating 25 40 C Storage temperature range 25 60 C Relative humidity 0 100 non condensing Maximum operating altitude 2000 m above sea level Standards and Directives RPI M6A RPI M8A RPI M10A Protection degree IP65 Safety class I Pollution degree II Overload behavior Current limitat...

Page 20: ... solar inverter com 0800 800 9323 call free Greece support greece solar inverter com 49 7641 455 549 Israel supporto israel solar inverter com 800 787 920 call free Italy supporto italia solar inverter com 800 787 920 call free Netherlands ondersteuning nederland solar inverter com 0800 022 1104 call free Portugal suporte portugal solar inverter com 49 7641 455 549 Slovakia Poland podpora slovensk...

Reviews: