NOTE:

If there is a power interruption while the UPS is in the bypass mode, the 

connected load won’t be protected.

5

  Turn off the UPS’s INPUT BREAKER.

6

  Turn off each connected external battery pack’s circuit breaker.

7

  Turn off the Maintenance Bypass Box’s OUTPUT BREAKER.

8

  Disconnect the battery cables from the UPS and the external battery pack(s).

9

  Disconnect the power cables from the ‘TO UPS INPUT’ and ‘TO UPS OUTPUT’ 

terminals on the Maintenance Bypass Box.

10

  Disconnect all of the communication cables from the rear panel of the UPS.

11

  Now, the UPS and the external battery pack(s) can be removed to perform 

maintenance.

12

  Once the maintenance is complete, re-install the UPS and the external battery 

pack(s).

13

  Reconnect all of the battery cables, the power cables and the communication 

cables.

14

  Turn on each connected external battery pack’s circuit breaker.

15

  Turn on the UPS’s INPUT BREAKER.

16

  Turn on the Maintenance Bypass Box’s OUTPUT BREAKER.

17

  Switch the Maintenance Bypass Box’s BYPASS SWITCH to the NORMAL position 

(see 

Figure 14

).

(Figure 14)

NORMAL

BY

PASS

BYPASS SWITCH

旁路开关

OFF

ON

输出断路器

OUTPUT BREAKER

Bypass Switch 

NORMAL

BY

PASS

18

  Re-install the cover plate of the BYPASS SWITCH on the Maintenance Bypass 

Box. This will automatically inactivate the manual bypass detector.

19

  Press and hold the UPS’s ON button for 3 seconds and release it after you hear 

one beep to turn the UPS on.

20

  The UPS system is ready for normal operation. Please refer to the UPS’s user 

manual for more information.

y

y

PDB1512A510035

1

  Press and hold the UPS1’s OFF button for 3 seconds and release it after you hear 

one beep. The inverter will be off and the UPS1 will transfer to run in bypass mode.

2

  Press and hold the UPS2’s OFF button for 3 seconds and release it after you hear 

one beep. The inverter will be off and the UPS2 will transfer to run in bypass mode.

3

  Remove the front panel of the Maintenance Bypass Box.  

Please refer to 

How to Remove the Front Panel

5

.

4

  Remove the screw shown in 

Figure 15

 to remove the cover plate of the BYPASS 

BREAKER.

(Figure 15)

旁路断路器

UPS2 

输出断路器

UPS2 

OUTPUT BREAKER

UPS1 

输出断路器

UPS1 

OUTPUT BREAKER

BYPASS BREAKER

OFF

ON

OFF

ON

警告

:     

开 起 此 盖 板 时 , 会 即 刻 关 闭 逆 变 器 输 出 . 非

授 权 合 格 人 员 , 严 禁 开 起 .

W A R N IN G :

O P E N I N G   T H I S   C O V E R   P L A T E   W I L L

C A U S E   I N V E R T E R   S H U T D O W N .   O N L Y

A U T H O R I Z E D   S E R V I C E   P E R S O N N E L

C A N   O P E N   A N D   O P E R A T E   I T .

Screw

NOTE:

Under the cover plate, there is a manual bypass detector (see 

Figure 16

) that 

will be automatically activated to send the UPS a message of transferring in to 

bypass mode once the cover plate is removed.

(Figure 16)

OFF

ON

旁路断路器

UPS2 

输出断路器

UPS2 

OUTPUT BREAKER

UPS1 

输出断路器

UPS1 

OUTPUT BREAKER

BYPASS BREAKER

OFF

ON

OFF

ON

Manual Bypass

Detector

5

 

After you confirm that both of UPS1 and UPS2 have been run in bypass mode, switch 

the Maintenance Bypass Box’s BYPASS BRAKER to the ON position. The ON/ OFF 
printing is marked on the BYPASS BREAKER (see 

Figure 17

). Now, the connected 

load is being powered by the utility power.

(Figure 17)

旁路断路器

UPS2 

输出断路器

UPS2 

OUTPUT BREAKER

UPS1 

输出断路器

UPS1 

OUTPUT BREAKER

BYPASS BREAKER

OFF

ON

OFF

ON

OFF

ON

OFF

ON

Bypass Breaker 

NOTE:

If there is a power interruption while the UPS1 and UPS2 are both in bypass 

mode, the connected load won’t be protected.

6

  Turn off the UPS1’s INPUT BREAKER.

7

  Turn off the UPS2’s INPUT BREAKER.

8

  Turn off each connected external battery pack’s circuit breaker.

9

  Turn off the Maintenance Bypass Box’s UPS1 OUTPUT BREAKER.

10

  Turn off the Maintenance Bypass Box’s UPS2 OUTPUT BREAKER.

11

  Disconnect the battery cables from the UPS1 and the external battery pack(s).

12

  Disconnect the battery cables from the UPS2 and the external battery pack(s).

13

  Disconnect the power cables from the ‘TO UPS1 INPUT’ and ‘TO UPS1 OUTPUT’ 

terminals on the Maintenance Bypass Box.

14

  Disconnect the power cables from the ‘TO UPS2 INPUT’ and ‘TO UPS2 OUTPUT’ 

terminals on the Maintenance Bypass Box.

15

  Disconnect all of the communication cables from the rear panel of the UPS1 and 

UPS2.

16

  Now, the UPS1, the UPS2 and the external battery pack(s) can be removed to 

perform maintenance.

17

  Once the maintenance is complete, re-install the UPS1 and UPS2 and the external 

battery packs.

18

  Reconnect all of the battery cables, the power cables and the communication cables.

19

  Turn on each connected external battery pack’s circuit breaker.

22

  Turn on the UPS1’s INPUT BREAKER.

21

  Turn on the UPS2’s INPUT BREAKER.

22

  Turn on the Maintenance Bypass Box’s UPS1 OUTPUT BREAKER.

23

  Turn on the Maintenance Bypass Box’s UPS2 OUTPUT BREAKER.

24

  Switch the Maintenance Bypass Box’s BYPASS BREAKER to the OFF position. The 

ON/ OFF printing is marked on the BYPASS BREAKER (see 

Figure 18

).

(Figure 18)

OFF

ON

旁路断路器

UPS2 

输出断路器

UPS2 

OUTPUT BREAKER

UPS1 

输出断路器

UPS1 

OUTPUT BREAKER

BYPASS BREAKER

OFF

ON

OFF

ON

Bypass Breaker 

OFF

ON

Copyright © 2017 by Delta Electronics Inc. 

All Rights Reserved. This Quick Guide is 

subject to change without prior notice.

25

  Re-install the cover plate of the BYPASS BREAKER on the Maintenance Bypass 

Box. This will automatically inactivate the manual bypass detector.

26

  Press and hold the UPS1’s ON button for 3 seconds and release it after you hear 

one beep to turn the UPS1 on.

27

  Press and hold the UPS2’s ON button for 3 seconds and release it after you hear 

one beep to turn the UPS2 on.

28

  The UPS system is ready for normal operation. Please refer to the UPS’s user 

manual for more information.

NOTE:

If you encounter any problems that you cannot solve, please ask your local 

dealer or customer service for more information. Do not attempt to solve the 

problems if you are not trained for it.

Technical Specifications

12

Model No.

PDB1511A530035

PDB1512A510035

Input

Nominal Voltage

200/ 208/ 220/ 230/ 240 Vac

Frequency

50/ 60Hz

Current (Max.)

63A

125A

Connection

Terminal Block

Output

Nominal Voltage

200/ 208/ 220/ 230/ 240 Vac

Frequency

50/ 60Hz

Power (Max.)

10kVA/ 10kW

20kVA/ 20kW

Connection

Terminal Block 

Environment

Operating Altitude

1000 meters (without derating)

Operating Temperature

0 ~ 40°C (32 ~ 104°F)

Storage Temperature

-15 ~ 50°C (5 ~ 122°F)

Relative Humidity

5 ~ 95% (non-condensing)

Physical

Dimensions (W x D x H) 190 x 408 x 142.7 mm 382 x 390 x 142.7 mm
Weight

4 Kg

7.6 Kg

NOTE:

1.  Refer to the rating label for the safety rating.

2.  All specifications are subject to change without prior notification.

Warranty

13

Seller warrants this product, if used in accordance with all applicable instructions, to be 

free from original defects in material and workmanship within the warranty period. If the 

product has any failure problem within the warranty period, Seller will repair or replace the 

product at its sole discretion according to the failure situation.

This warranty does not apply to normal wear or to damage resulting from improper 

installation, operation, usage, maintenance or irresistible force (i.e. war, fire, natural 

disaster, etc.), and this warranty also expressly excludes all incidental and consequential 

damages. Maintenance service for a fee is provided for any damage out of the warranty 

period. If any maintenance is required, please directly contact the supplier or Seller.

WARNING:

  

The individual user should take care to determine prior to use whether the 

environment and the load characteristic are suitable, adequate or safe for the 

installation and the usage of this product. The Quick Guide must be carefully 

followed. Seller makes no representation or warranty as to the suitability or fitness 

of this product for any specific application.

No. 501324610101
Version : V 1.1
Release Date : 2017_2_9

Summary of Contents for PDB1511A530035

Page 1: ...Cable 1 PCS y y Model PDB1512A510035_ Maintenance Bypass Box for Parallel UPSs Application 2 6 5 1 11 10 3 13 12 7 4 8 9 No Item Q ty 1 Heat Shrink Tube 12 PCS 2 CU Terminal Type B 4 PCS 3 CU Terminal Type C 6 PCS 4 Terminal Holder 4 PCS 5 Screw for Fastener 12 PCS 6 Fastener Type A 4 PCS 7 Fastener Type B 1 PCS 8 Wire 1 2 PCS 9 Wire 2 2 PCS 10 Cable Tie 6 PCS 11 Cable Gland 2 PCS 12 Screw for Ter...

Page 2: ...源 输 入 端 子 排 TO UPS 1 INPUT 连 接 UPS 1输 出 端 子 排 TO UPS 1 O UTPUT N L 输 入 端 子 排 IN PU T N L 输 出 端 子 排 O U TPU T Rear L N 连 接 UP S2 主 电 源 输 入 端 子 排 TO UP S2 INPUT 连 接 UP S2 输 出 端 子 排 TO UP S2 O UTPUT UP S1 PA RA LL EL 连 接 UP S1 PA RA LL EL TO UP S2 PA RA LL EL 连 接 UP S2 PA RA LL EL TO L N 连 接 UP S1 主 电 源 输 入 端 子 排 TO UP S1 INPUT 连 接 UP S1 输 出 端 子 排 TO UP S1 O UTPUT N L 输 入 端 子 排 IN PU T N L 输 出 端 子 排 ...

Page 3: ...cceptable AC voltage present Please refer to the UPS s user manual for more information NOTE The cover plate of the Maintenance Bypass Box s bypass switch must still be installed 1 Turn on the input utility breaker at the service panel 2 Turn on the Maintenance Bypass Box s OUTPUT BREAKER 3 Turn on each connected external battery pack s circuit breaker 4 Turn on the UPS s INPUT BREAKER The fans wi...

Page 4: ...nd the external battery pack s 13 Disconnect the power cables from the TO UPS1 INPUT and TO UPS1 OUTPUT terminals on the Maintenance Bypass Box 14 Disconnect the power cables from the TO UPS2 INPUT and TO UPS2 OUTPUT terminals on the Maintenance Bypass Box 15 Disconnect all of the communication cables from the rear panel of the UPS1 and UPS2 16 Now the UPS1 the UPS2 and the external battery pack s...

Reviews: