Delta MCS-600 Power Shelf
Installation, Operations and
Maintenance Manual
REV.: 03
2-3
Customer Specification Confidential
2.3.3.3 Status/Alarm Indicators
The Power Shelf has the following status/alarm indicators:
Load Current, % of Output
AC ON
Rectifier Fail Alarm (RFA)
Current Limit (CL)
Float/Equalize (FL/EQU)
Major Alarm (MAJ)
Minor Alarm (MIN)
High Voltage Alarm (HV)
High Voltage Shutdown (HVSD)
Low Voltage Alarm (LV)
Low Voltage Disconnect Open (LVDS OPEN)
Fuse Blown (FUSE ALM)
AC Fail (AC FAIL)
2.3.3.4 Mechanical Data
Table 3 displays the system mechanical data.
Table 3 System Mechanical Data
Dimension Value
Height
5.22 in. (132.6mm)
Depth
12 in. (304.4mm)
Width
19 in. (483mm)
2.3.3.5 Environmental Data
Table 4 displays the system environmental data.
Table 4 System Environmental Data
Specification Value
Operating temperature
-0
℃
to +50
℃
-20
℃
to +65
℃
OPTION
Storage temperature
-40
℃
to +85
℃
Humidity
0% to 95% RH
Altitude
-300 ft. to 10,000 ft.
Weight Approximately
48
lbs.
EMI/FRI
FCC Part 15, Class B and CISPR 22, Class B
Lightning/surge
ANSI/IEEE C62.41-1, and IEC 1000-4-5
Seismic
Bellcore GR-63-CORE, Zone 4
Safety C
UL
and UL Listed and CE Marked