Delta MCS-600 Power Shelf
Installation, Operations and
Maintenance Manual
REV.: 03
2-2
Customer Specification Confidential
(5) Load Distribution:
10A Breaker×4 @ Single Pole
(6) Low Voltage Disconnect Switch:
100A×1 @ Single Pole at Battery Side
(7) Battery
Breaker:
100A×1
Figure 1-1 shows a front view of shelf.
2.3.3 Electrical Data
The system electrical data is provided in the following tables
.
2.3.3.1 Input
Table 1 displays the system input specifications.
Table 1 System Input Specifications
Specification Value
Nominal range
90-275 VAC
Operational range
175-275 VAC
Frequency 45-65
Hz
Power Factor
>0.99
THD <5%
Efficiency >90%
2.3.3.2 Output
Table 2 displays the system output specifications.
Table 2 System Output Specifications
Specification Value
DC Volts
40-60 VDC
Power
Each module, HL
Each module, LL
System, HL
System, LL
600W
300W
3Kw
1.5Kw
Load regulation
<0.5%
Line regulation
<0.1%
Current Limit
110%
Current share
<5%
Noise:
Audio band
Wide band
Acoustic
<2mv
<10 mVrms
<55 dBA
Battery breakers
1, 50 Amps CB
Temperature Compensation
50 to 100 mV/string