Quick Installation Guide for Solar Power Inverter M125HV EU V1 EN 2019-04-01
Connecting the mains (AC) – general notes
Grounding the inverter
If the selected grounding system contains a PE/PEN conduc-
tor (TN-C, TN-S, TN-S, TN-C-S) and this is contained in the AC
cable, use the PE terminal provided for this purpose (near the AC
connection terminal block). In addition, for the protection of users,
the inverter enclosure must always be grounded via one of the
external terminals.
In an IT type earth connection scheme, the inverter housing can
be connected to earth, either through one of the external termi-
nals or by using the provided PE terminal (near the AC connec-
tion terminal).
Permissible grounding systems
Grounding system
TN-S TN-C TN-C-S TT
IT
Allowed
Yes
Yes
Yes
No
Yes
TN-S 347/600 V
IT 347/600 V
M125HV
L1
L2
L3
N
PE
L1 L2 L3 PE
TN-C 347/600 V
M125HV
L1
L2
L3
PE/N
L1 L2 L3 PE
TN-C-S 347/600 V
M125HV
L1
L2
L3
PE
N
L1 L2 L3 PE
M125HV
L1
L2
L3
L1 L2 L3
Permissible grounding systems